Page 26 – Bulletin 40-10
Liquid Line
Ratings and Selection Recommendations
Replaceable Core Type – Refrigerant 22
TYPE
SURFACE
FILTERING
AREA
RATINGS AT AHRI STANDARD CONDITIONS SELECTION RECOMMENDATIONS (Tons)
WATER CAPACITY
DROPS AT 60 PPM
REFRIGERANT
FLOW CAPACITY
REFRIGERATION AIR CONDITIONING
Sq.
Inch
cm
2
75°F
25°C
125°F
50°C
Tons at
1 psi ∆P
kW at
0.07 bar ∆P
Commercial &
Low Temperature
Equipment
O.E.M.
Self
Contained
Field Replacement
or Field Built-Up
Systems
RCW-42 (High Water Capacity Core)
C-R424-G
67 432 902 735
11.4 40.0 5 7-1/2 5
C-R425-G 13.7 48.1
7-1/2 15 10
C-R427-G 18.5 64.9
RCW-48 or RCW-100 (High Water Capacity Cores)
C-485-G
64
413
1109 904
14.6 51.2 10 15 10
C-487-G 23.9 83.9 15 20 15
C-489-G 43.2 151.6 15 30 20
C-967-G
128 826 2218 1808
39.2 137.6 25 35 25
C-969-G 48.7 170.9 35 40 35
C-1449-G
192 1239 3327 2712
59.2 207.8 40 50 40
C-14411-G 67.0 235.2 50 60 50
C-19211-G
256 1652 4436 3616
84.5 296.6 70 80 70
C-19213-G 99.0 347.5 80 100 80
C-19217-G 104 365.0 85 100 85
C-30013-G 294 1897 6786 5532 112 393.1 100 125 100
C-40017-G 392
2529
9048 7376 134 470.3 130 150 130
RC-4864 or RC-10098 (Standard Cores)
C-485-G
64
413
347 288
14.6 51.2 10 15 10
C-487-G 23.9 83.9 15 20 15
C-489-G 43.2 151.6 15 30 20
C-967-G
128 826 694 576
39.2 137.6 25 35 25
C-969-G 48.7 170.9 35 40 35
C-1449-G
192 1239 1041 864
59.2 207.8 40 50 40
C-14411-G 67.0 235.2 50 60 50
C-19211-G
256 1652 1388 1152
84.5 296.6 70 80 70
C-19213-G 99.0 347.5 80 100 80
C-19217-G 104 365.0 85 100 85
C-30013-G 294 1897 2670 1878 112 393.1 100 125 100
C-40017-G 392
2529
3560 2504 134 470.3 130 150 130
NOTE: The variation in flow ratings of filter-driers having the same size core and shell is caused by the difference in connection sizes used. Installing the
secondary filter in C-480 through C-19200 Series shells reduces the flow capacity by approximately 5 percent.
For suction line
filter-driers
see page 30
For sealed model
Catch-Alls
see page 10