Brochure

Page 14 – Bulletin 40-10
Liquid Line
Ratings and Selection Recommendations
Sealed Type Refrigerant 404A & 507
TYPE
SURFACE
FILTERING
AREA
RATINGS AT AHRI STANDARD CONDITIONS SELECTION RECOMMENDATIONS (Tons)
WATER CAPACITY
DROPS AT 50 PPM
REFRIGERANT
FLOW CAPACITY
REFRIGERATION AIR CONDITIONING
Sq.
Inch
cm
2
75°F
25°C
125°F
50°C
Tons at
1 psi ∆P
kW at
0.07 bar ∆P
Commercial &
Low Temperature
Equipment
O.E.M.
Self
Contained
Field Replacement
or Field Built-Up
Systems
C-032
9 58 71 58
1.0 3.5
1/4 3/4 1/2
C-032-CAP
C-032-S
C-032-F
C-032-FM
C-033 2.3 8.1
C-033-S 2.6 9.1
C-052
15 97 169 138
1.4 4.9
1/3 1 thru 2 3/4 thru 1
C-052-S
C-052-F
C-052-FM
C-0525-S 2.3 8.1
C-053 2.7 9.5
C-053-S 3.1 10.9
C-082
21 135 279 227
1.4 4.9
1/2 thru 1 1 thru 4 3/4 thru 2
C-082-S
C-0825-S 2.4 8.4
C-083 3.0 10.5
C-083-S 3.4 11.9
C-084 5.5 19.3
C-084-S 5.9 20.7
C-162
33 213 424 345
1.4 4.9
3/4 thru 2 2 thru 7-1/2 1 thru 4
C-162-S
C-1625-S 2.4 8.4
C-163 3.0 10.5
C-163-S 3.4 11.9
C-164 6.8 23.9
C-164-S 7.3 25.6
C-165 8.2 28.8
C-165-S 9.2 32.3
C-303
53 342 809 658
3.0 10.5
2 thru 5 4 thru 12 3 thru 7-1/2
C-303-S 3.4 11.9
C-304 6.8 23.9
C-304-S 7.3 25.6
C-305 9.9 34.7
C-305-S 11.3 39.7
C-307-S 14.4 50.5
C-414
67 432 1088 885
7.6 26.7
5 thru 10 5 thru 15 5 thru 12
C-414-S 8.3 29.1
C-415 10.6 37.2
C-415-S 11.8 41.4
C-417-S 14.8 51.9
C-419-S 16.3 57.2
C-607-S
106 684 1618 1316
29.5 103.5
10 15 thru 20 10
C-609-S 22.3 78.3
For suction line
filter-driers
see page 30
For replaceable core Catch-Alls see page 21
NOTE: The variation in flow ratings of filter-driers having the same size core and shell is caused by the difference in connection sizes used.
R-502 water capacities are similar to R-404A and R-507.