10.
TerminatethefirstandlastSolarEdgedeviceinthechainbyswitchingaterminationDIP-switchinside
theinvertertoON(movetheleftswitchup).Theswitchislocatedonthecommunicationboardand
ismarkedSW7SW1.
Figure 36: RS485 termination switch
NOTE
Only the first and last SolarEdge devices in the chain should be terminated. The other inverters in
the chain should have the termination switch OFF (down position).
11. Ifnotusingsurgeprotection,connectthegroundingwiretothefirstinverterintheRS485chain;
makesurethegroundingwireisnotincontactwithotherwires.ForinverterswithaSafetySwitch,
connectthegroundingwiretothegroundingbus-barintheSafetySwitch.
To connect to the monitoring platform:
1. DesignateasingleinverterastheconnectionpointbetweentheRS485busandthemonitoring
platform.Thisinverterwillserveasthemasterinverter.
2. ConnectthemastertothemonitoringplatformviatheLANoption(refertoCreatinganEthernet
(LAN)Connectiononpage54)oranyoftheotheroptions.
To configure the RS485 bus:
Allinvertersareconfiguredbydefaultasslaves.Toconfigurethemaster:
1. VerifytheON/OFF/PswitchisOFF.
2. VerifythatACison.
3. UseSetApptoaccesstheCommissioningmenuscreenasdescribedinCommunicationonpage43.
4.
FromtheCommissioningmenutapCommunication.TheCommunicationscreenisdisplayed.
5.
Selectthefollowingtoconfiguretheconnection:
l ServerèLAN
l RS485-1èProtocolè SolarEdge Master
l RS485-1èSlave Detect
Thesystemstartsautomaticdetectionoftheslaveinvertersconnectedtothemasterinverter.The
invertershouldreportthecorrectnumberofslaves.Ifitdoesnot,verifytheconnectionsand
terminations.
6. TochecktheslaveIDsandlastcommunicationtime,selectRS485-1èSlave List.
7. Verifytheconnectionofthemastertothemonitoringplatform,asdescribedinthenextsection.
Verifying the Connection
Afterconnectingandconfiguringacommunicationoption,performthefollowingstepstocheckthat
theconnectiontothemonitoringserverhasbeensuccessfullyestablished.
Chapter 6: Setting Up Communication
-Three Phase System Installation Guide MAN-01-00527-1.1
59