- Chapter 1: Introducing the SolarEdge Power Harvesting System
- Chapter 2: Installing the Power Optimizers
- Chapter 3: Installing the Inverter
- Chapter 4: Connecting the AC and the Strings to the Safety Switch
- Chapter 5: Commissioning the Installation
- Chapter 6: User Interface
- Chapter 7: Setting Up Communication
- Appendix A: Errors and Troubleshooting
- Appendix B: Mechanical Specifications
- Appendix C: External Fan Maintenance and Replacement
- Appendix D: Replacing and Adding System Components
- Appendix E: Determining the Circuit Breaker Size
- Technical Specifications - Single Phase Inverters (North America)
- Technical Specifications - Three Phase Inverters (North America)
![](/manual/solaredge/se10000a/installation-guide-english-french/images/img-122.png)
Technical Specifications - Three Phase Inverters (North America)
SE9KUS SE10KUS SE14.4KUS SE20KUS SE30KUS SE33.3KUS Units
OUTPUT
Rated AC power output 9000 10000 14400 20000 30000 33300 VA
Maximum AC power output 9000 10000 14400 20000 30000 33300 VA
AC Output Line Connections
4-wire WYE
(L1-L2-L3-N)
plus PE or 3
wire Delta
4-wire WYE
(L1-L2-L3-N)
plus PE
4-wire WYE
(L1-L2-L3-N)
plus PE or 3
wire Delta
4-wire WYE
(L1-L2-L3-N)
plus PE
4-wire WYE
(L1-L2-L3-N)
plus PE
4-wire WYE
(L1-L2-L3-N)
plus PE
AC output voltage minimum-
nominal-maximum (L-N)
(1)
105-120-
132.5
244-277-305
105-120-
132.5
244-277-305 244-277-305 244-277-305 Vac
AC output voltage minimum-
nominal-maximum (L-L)
1
183-208-229
422.5-480-
529
183-208-229
422.5-480-
529
422.5-480-
529
422.5-480-
529
Vac
AC frequency min-nom-max
1
59.3 - 60 - 60.5
(with HI country setting 57 - 60 - 60.5)
Hz
Max. continuous output current
(per Phase)
25 12 40 24 36.5 40 A
Max. output fault current and
duration
73 / 150 51 / 150 92 / 150 73 /150 88 / 150 92 / 150 A / mS
Inrush current AC (Peak /
Duration)
2.6/20 4 /20 4.2 / 20 4.2 / 20
Aac(rms) /
ms
(1)
For other regional settings please contact SolarEdge Support.
SolarEdge-Three Phase System Installation Guide MAN-01-00002-4.3