User and installation manual

4 Product Overview
SMA Solar Technology AG
Installation ManualSBSxx-US-10-IA-xx-1222
4.4 LED Signals
LED signal Explanation
The green LED is flashing
(twoseconds on and
twoseconds off)
Waiting for feed-in conditions
The conditions for feed-in operation are not yet met. As soon as the
conditions are met, the inverter will start feed-in operation.
The green LED is flashing
(1.5s on and 0.5s off)
Secure power supply operation or battery-backup function
The secure power supply operation or battery-backup function is ac-
tivated and the inverter supplies the loads with energy from the bat-
tery.
The green LED flashes
quickly
Update of central processing unit
The central processing unit of the inverter is being updated.
The green LED is glowing Parallel grid operation
The green LED is off The inverter is not feeding into the utility grid.
The red LED is glowing Event occurred
If an event occurs, a distinct event message and the corresponding
event number will be displayed in addition on the inverter user inter-
face or in the communication product.
The blue LED flashes slowly
for approx. one minute
Communication connection is being established
The inverter is establishing a connection to a local network or is es-
tablishing a direct connection to an end device via Ethernet (e.g.
computer, tablet PC or smartphone).
The blue LED flashes quickly
for approx. two minutes.
WPS active
The WPS function is active.
The blue LED is glowing Communication active
There is an active connection with a local network or there is a di-
rect connection with an end device via Ethernet (e.g. computer,
tablet PC or smartphone).
ENGLISH