| 7 |
4.2 – Charge Controller Settings
Please review Table 2.0 below for Morningstar charge controller(s) program settings.
Table 2.0 - Settings for SimpliPhi PHI 730, 1.4, 2.9 & 3.8 kWh Batteries w/ Morningstar Charge Controller
CHARGE CONTROLLER
PHI 730, 1.4, 2.9 & 3.8 kWh; 24V / 48V
Setting
Charging Source
Source
12 / 24 / 48
Battery Voltage (V) Custom
Charge
Battery Charge Setpoints
Volts
EQ (V)
Off
Absorb (V)
14 / 28 / 56
Float (V)
13.5 / 27 / 54
ChgTime
Absorb Minimum (Mins)
6 Min / .1 Hour
EQ Time (Mins)
0
EQ Time (Days) 0
Float Timeout Please See Note
Limits
Output Amps
1,2
28.5A per PHI730 12V; 14A per PHI730 24V
40A per PHI1.4 12V; 28.5A per PHI1.4 24V
75A per PHI3.8 24V; 37.5A per PHI3.8 48V
Input Amps
1
Size based on input charging source
Notes:
•
1.
Per PHI battery – Refer to Section 3.0 herein for charge controller PHI battery bank sizing.
•
2.
Per PHI battery – These settings are calculated by multiplying the nominal value per each PHI battery times the # of
PHI batteries. For other batteries, refer to the Warranty and Specification Sheet for the specific model.
•
3.
Float Timeout setting can be used in place of a ReBulk setting. Adjust this setting to the desired time you would like
the battery to remain below the float voltage before entering into a its bulk stage charging cycle. Levels are typical @
25°C and may need adjusting at temperature extremes.
• When performing rapid deep charge/discharge cycles, the PHI battery should be allowed to "rest" 15 minutes in
between.
• Always refer to the SimpliPhi Power Manual and Warranty for the specific PHI battery model.
CAUTION: When PHI battery quantities change, the capacity & charge/discharge current