Technical data

Control cabinet PC and display to
UPS
10 mm
²
(green/yellow)
6 mm
²
(blue)
PE bar
A
B
A
Overvoltage category I
(4)
to be connected to FE of VDP xx.3 .
to be connected to FE of VPB 40.3 , VPP xx.3 , VSB 40.3 , VSP xx.3 .
to be connected to FE of the UPS (VAU 01.1 ).
X1S2
UPS
FE = functional earth
(VAU 01.1 )
0V OUT
24V OUT
X1S1
0V IN
24V IN
VDP xx.3
X1S1
+
-
FE
X10
VPB 40.3
+
-
FE
(2)
+24V
O V
10 mm
² (green/yellow)
A
= Terminal block 4 mm²
B
= Terminal block 10 mm²
(1)
(2)
(3)
(4)
(5)
(1)
(4)
(3)
(3)
(5)
16 A
24 V
VPP xx.3
Terminal block UK6-FSI/6
with automatic cut-out TCP 10 A
(PHOENIX CONTACT) is recommended
Terminal block UK6-FSI/6
with automatic cut-out TCP 4 A
(PHOENIX CONTACT)
Easily removable and visible
FE
Cable length between UPS and VPB 40.3 and VPP xx.3 max. 2 m at a minimum
cross-section of 2.5 mm
².
Polarity reversal of the X1S1 and X10 connectors can destroy the device,
if there is no additional external protection (fire danger). This is caused by the
Cable length between +24 V power supply unit and UPS max. 2 m at a minimum
cross-section of 5 mm
² (see project planning manual of the UPS VAU 01.1).
Cable length between +24 V power supply unit and VDP xx.3 max. 30 m at a minimum
cross-section of 1.5 mm
². An additional power supply unit is required if the length exceeds 30 m.
VSP xx.3
VSB 40.3
simultaneous grounding of the 0 V of the device and the 0 V (PELV) (1).
6 mm
²
6 mm
²
6 mm
²
Fig.5-8: PC (VSB 40.3, VSP xx.3, VPB 40.3, VPP xx.3) and display (VDP xx.3)
connected to an UPS
Only control cabinet PC connected
to UPS
10 mm
²
(green/yellow)
6 mm
²
(blau)
PE bar
A
B
A
Overvoltage category I
(4)
6 mm
² a
to be connected to FE of VDP xx.3 .
6 mm
²
a to be connected to FE of the UPS (VAU 01.1 ).
X1S2
UPS
(VAU 01.1 )
0V OUT
24V OUT
X1S1
0V IN
24V IN
VDP xx.3
X1S
+
-
FE
+
-
FE
(2)
+24V
O V
10 mm
² (green/yellow)
A
= terminal block 4 mm²
B
= terminal block 10 mm²
(1)
(4)
(3)
(5)
16 A
24 V
Terminal block UK6-FSI/6
with automatic cut-out TCP 10 A
(PHOENIX CONTACT) is recommended
Terminal block UK6-FSI/6
with automatic cut-out TCP 4 A
(PHOENIX CONTACT) is recommended
FE
VPB 40.3
VPP xx.3
VSP xx.3
VSB 40.3
X10
(3)
6 mm
²
a to be connected to FE of VPB 40.3 , VPP xx.3 , VSB 40.3 , VSP xx.3 .
FE = functional earth
(1)
(2)
(3)
(4)
(5)
Easily removable and visible.
cross-section of 2.5 mm
².
Cable length between +24 V power supply unit and UPS max. 2 m at a minimum
cross-section of 5 mm
² (see project planning manual of the UPS VAU01.1).
Cable length between +24 V power supply unit and VDP xx.3 max. 30 m at a minimum
cross-section of 1.5 mm
². An additional power supply unit is required if the length exceeds 30 m.
Polarity reversal of the X1S1 and X10 connectors can destroy the device,
if there is no additional external protection (fire danger). This is caused by the
simultaneous grounding of the device and the 0 V (PELV) (1).
Cable length between UPS and VPB 40.3 and VPP xx.3 max. 2 m at a minimum
Fig.5-9: PC (VSB 40.3, VSP xx.3, VPB 40.3, VPP xx.3) connected to an UPS.
Display (VDP xx.3) not connected to an UPS
Project Planning Manual | Rexroth IndraControl VSB 40.3 Electric Drives
and Controls
| Bosch Rexroth AG 31/101
Dimensions, Installation and Wiring