Data Sheet for Product

Siemens
Smart Infrastructure Building Products
5
usa.siemens.com/fire
Supported Sub-Systems and Protocols
Fire Safety
Desigo Fire Safety
Modular
MP1.x
Up to four
#
(4) XNET networks per server or FEP
Up to five (5) Front End Processors (FEP) for a
maximum of 24 XNET networks per system
Up to 63 panels per XNET network
Desigo Fire Safety Compact
(FC20-series / FV20-series)
MP1.x | MP2.x | MP3.0
Up to four
(4) fire or voice networks
Up to 16 panels per SafeDLINK or
32 panels per FCnet
FireFinder XLS and XLSV
MP8 | MP10 | MP11 | MP12
Up to four
#
(4) XNET networks per server or FEP
Up to five (5) Front End Processors (FEP) for a
maximum of 24 XNET networks per system
Up to 63 panels per XNET network
MXL / MXLV
MXL/MXLV system with Model MMB-3 running
firmware 35.06J and CSGM 18
Up to four
#
(4) XNET networks per server or FEP
Up to five (5) Front End Processors (FEP) for a
maximum of 24 XNET networks per system
Up to 63 panels per XNET network
Cerberus PRO Modular
MP1.x
Up to four
#
(4) XNET networks per server or FEP
Up to five (5) Front End Processors (FEP) for a
maximum of 24 XNET networks per system
Up to 63 panels per XNET network
Cerberus PRO Compact
(FC92-series / FV92-series
MP1.x | MP2.x | MP3.0
Up to four
(4) fire or voice networks
Up to 16 panels per SafeDLINK or
32 panels per C-WEB
NOTIFIER Onyx Series
Monitoring only integration
for NFS/NFS2 series panels
Security
Video
Siveillance VMS50 | VMS100 | VMS200 | VMS200
(embedded), and VMS300
Milestone XProtect Essential+ | Express+ |
Professional+ | Expert, and Corporate
Supported versions: 2017 R2 (v11.2a)
up to 2020 R2 (v20.2a)
Up to 128 cameras for UL / ULC applications
Up to 1000 cameras for non-UL / ULC applications
Up to 16 independent video streams per client
Access Control
SiPass integrated 2.7 SP1 | 2.75 |
2.76 SP1 & SP2 | 2.80
Up to 25 SiPass integrated servers
Up to 1,000 doors
Building Automation
APOGEE
BACnet PXC, MBC, MEC controllers
(firmware 3.2.4- 3.5.2)
BACnet FLN DXR, PTEC, PXC UEC, PPM
P2 PXC, MBC, MEC controllers P2 Ethernet
(firmware 2.8.10-2.8.18) and RS-485 via
AEM (firmware 2.8)
P1 FLN TEC, Point Expansion Modules, PXC
Compact on P1, P1 BIM, DEM, P1 Drivers,
and P1 VFDs
Open System Standard Protocols
BACnet:
Building Automation Control
network, Revision 1.15
OPC DA
OLE for Process Control OPC DA 2.05, 3.0
Modbus TCP
Modbus IP communication protocol
SNMP
SNMP Agents monitoring (V2 and V3)
Notification Protocols and Devices
Email
POP3/IMAP/SMTP with SSL/TLS
Pager
ESPA 4.4.4; Ascom
Mobile
SMS
#
The maximum number of XNET networks per server or FEP is determined by the "Hardware Category" computer selected.
Refer to the "Technical Data" section below for max. number of XNET Interface cards per computer