Installation Instructions

Installation Instructions
Document No. 129-185
September 24, 2018
SKB/C Electronic Valve Actuator
Item Number: 129-185-05, Rev. CA Page 1 of 9
Product Description
The SKB/C actuators require a 24 Vac supply signal to
control either a 3/4-inch (20 mm) or 1-1/2-inch
(40 mm) stroke valve. These actuators work with
Flowrite™ 599 Series valves with a 3/4-inch (20 mm)
stroke (SKB) or a 1-1/2-inch (40 mm) stroke (SKC).
Product Numbers
SKBx 3/4-inch (20 mm) stroke
SKCx 1-1/2-inch (40 mm) stroke
Warning/Caution Notations
WARNING:
Personal injury or loss of
life may occur if you do not
follow a procedure as
specified.
CAUTION:
Equipment damage, or
loss of data may occur you
do not follow a procedure
as specified.
Required Tools
24 mm open-end wrench
3/8-inch open-end wrench
No. 1 Phillips or flat-blade screwdriver
Small adjustable wrench
Expected Installation Time
20 minutes for factory-installed actuator
46 minutes for field replacement of actuator
Prerequisites
WARNING:
If mounting the actuator to a valve already in
line, either close the shut-off valves in the
piping (upstream first, then downstream) or
switch off the pump to allow the differential
and static pressure in the valve to drop.
CAUTION:
Do not damage or scratch the polished
surface of the valve stem.
Figure 1. Acceptable Mounting Positions.
The vertical position is required for mounting and is the
only position for the NEMA Type 3R rating with the
Weather Shield.
Figure 2. SKB\C Weather Shield.
Using the Weather Shield
The SKB/C actuator is UL listed to meet NEMA Type
3R requirements (a degree of protection against rain,
sleet, and damage from external ice formation) when
installed with the Weather Shield, product number
599-10065, and outdoor-rated conduit fittings. The
SKB/C must be in the vertical position. Complete
instructions for the mounting of the Weather Shield are
included with that product. See Figure 31 for Weather
Shield dimensions.