Operating Instructions
SED2 VFD Electronic Bypass Option Operating Instructions
26 Siemens Building Technologies, Inc.
Parameter Description Action
Setting/
Default
P0640
Motor Overload Factor
10% to 400%
Limited to the maximum SED2
output current rating, or to 400%
of the rated current (P0305),
whichever is lower.
NOTE:
This parameter is available when
P0003 = 3 and
P0010 = 1.
1. Press
to advance to
parameter P0640.
2. Press
to access the
parameter values level.
3. Press
to advance to
desired value.
4. Press
to confirm and save
the setting.
Setting =
As applicable
Default = 110
P0700(0)**
Selection of Command Source
(Start Command)
Selects the command source as
follows:
0 = Factory default setting
1 = BOP (keypad)
2 = Terminal digital input
4 = USS on BOP link (AOP)
5 = USS on COM link
6 = CB (Communications board
or module) on COM link (P1/N2)
1. Press
to advance to
parameter P0700.
2. Press
to access the
parameter indexes.
3. Press
to advance to index
[0], IN000, AUTO.
4. Press
to confirm index
selection.
5. Press
to advance to 2.
6. Press
to confirm and save
the setting.
Setting = 2
Default = 2
NOTE:
Changing this parameter resets (to default) all settings on the selected item. For example, changing from 1
to 2 resets all digital inputs to default settings.
** Parameters have two index settings: IN000 = Auto and IN001 = Hand.