User Manual

1/2
Building Technologies 13-01-950 E.doc
Fire Safety & Security Products
Pressure regulator ENGLISH
13-01-950
PED-category:
Pressure reducer (L10/200 LabLine)
10 bar output
PRED-200 10
Index Description Date
Fluid group: 25.05.09
Product line
Sinorix ™
a VdS approved 25.01.10
b CO2 gaseous 18.05.18
SAP
A5Q00036889
GLA 09066
Technical data
OEM type 17652901
agent (gaseous form) N2, Ar, CO2, compressed air
outlet pressure range 10 bar, factory adjusted
operation inlet pressure max 250bar
safety valve release pressure 12-13 bar
flow 45 Nm
3
/h bei 10bar
inlet G1 L8 mm cutting ring Swagelok,stainless steel
outlet G2 L8 mm cutting ring Swagelok,stainless steel
pressure gauge inlet none
pressure gauge outlet 0-16 / 10bar (DIN EN 562), class 2.5
weight 1.5 kg
dimensions 200 x 190 x 75 mm
marking N200MJJ (MJJ=manufacturing date)
material
membrane metallmembrane SS321 (1.4541), chrome-plated
valve body brass chrome-plated
Usage
This pressure reducer is used in Sinorix
TM
extinguishing systems. It reduces the control cylinder pressure to 10bar. This
reduced pressure is used for pneumatic time delay devices, pneumatic actuators on extinguishing cylinders, pneumatic
horns and selector valve drive gears for 10 bar.

Summary of content (2 pages)