s Installation / Operation / Maintenance Instructions 21-115532-001 PR4018-06 SUPERCEDES 21-115532-001 PR4018-05
TABLE OF CONTENTS Page INTRODUCTION............................................. Inspection for Damage in Shipment……….…. Special Features Polarized Disconnect Switch And Hinged Control Panel………….........…... Remote Mounting of Control Equipment…….. Vari-AMPTM Position Indicator………………... Operation at Less Than Rated Voltage….…… Forced Air Cooling……………………………... Subbase Assembly…………………………….. Parts List Major Components…………………………….. Position Indicator………………………………. Type TLG Dial Switch…………………….…….
INTRODUCTION Page 1 Type JFR single-phase step-voltage regulators are designed to give dependable service and to make installation, operation and maintenance as simple as possible. QUALIFIED PERSON Technology advances, especially in the realm of the control apparatus, make it efficient to provide a separate instruction manual for the Accu/StatTM control provided with this JFR Regulator. For specific control information, refer to the Accu/StatTM control manual included with the regulator.
INTRODUCTION Page 2 INSPECTION FOR DAMAGE IN SHIPMENT STORAGE PRIOR TO INSTALLATION Check each item with the shipping manifest immediately upon receipt of the regulator. Make a thorough visual inspection of the regulator. Check for evidence of damage attributable to mishandling in shipment. Should any shortage or damage be found, notify the local agent of the carrier making the delivery and make appropriate notation on the freight bill. A claim should be made immediately with the carrier.
INTRODUCTION PHYSICAL CONSIDERATIONS • Handling. Type JFR regulators are designed to be lifted either by a forklift at the base or by use of hangar brackets on the side of the tank. Each JFR regulator is provided with either 2 or 4 lifting hooks on the side of the tank. The number of hooks has been established to provide a margin of safety on lifting when all hooks provided are used. WARNING Page 3 • For air cooled (OA) rating, derate kVA rating 0.
INTRODUCTION Page 4 INSTALLATION DIAGRAMS (Figure 4A) (Figure 4B) (Figure 4B) (Figure 4D)
INTRODUCTION Page 5 PROTECTIVE MEASURES Bypass Arrester. All JFR regulators are equipped with a properly sized arrester, connected externally between the 'S' and 'L' line terminals. The arrester is provided to protect the series winding of the regulator from line surges. Of itself, the bypass arrester does not provide lightning protection for the regulator. Lightning Protection.
CONNECTION DIAGRAMS Page 6
CONNECTION DIAGRAMS Page 7
CONNECTION DIAGRAMS Page 8
PLACING THE REGULATOR IN SERVICE Page 9 The following checks will be useful in assuring the regulator is ready for use. The list cannot be all inclusive; careful attention on the part of a qualified operator remains imperative. BEFORE CONNECTING WARNING High pressure or mechanical failure due to improper bypass operation can cause death, severe injury or damage. To prevent: • Check oil level at oil sight window. If low, add sufficient oil (ASTM D-3487 Type II) to bring level to that desired.
REMOVING THE REGULATOR FROM SERVICE Page 10 REMOVING THE REGULATOR FROM THE LINE In order to remove a regulator from service without dropping load, it is imperative that the regulator be on the neutral position. The system must first be de-energized (load dropped) before removal. If the regulator being removed is in a closed delta bank, it is necessary to bypass and isolate all regulators in the bank.
MAINTENANCE Page 11 GENERAL INSTRUCTIONS Failure to properly maintain the regulator can result in severe personal injury and product failure. The instructions contained herein should be carefully reviewed, understood and followed. The following maintenance procedures should be performed regularly: 1. Operational checks • Control performance • Tapchanger performance • Vari-AmpTM limit performance. 2.
MAINTENANCE Page 12 PERIODIC INSPECTION A sample of oil from the regulator should be subjected to dielectric breakdown test, per ASTM D-877. It is recommended that oil testing less than 24 kV be filtered. Other tests, especially Neutralization Number, Interfacial Tension and Power Factor are also useful and may be preferred by particular users. Contacts, both movable and stationary, show normal burning and wear after 1,500,000 operations.
SPECIAL FEATURES Page 13 POLARIZED DISCONNECT SWITCH (JACK PLUG) AND HINGED CONTROL PANEL The Accu/StatTM control panel is hinged and may be removed completely from the regulator control box by removing the wing nuts on the polarized jack plug and pulling the jack from its fixed portion. This will automatically de-energize the control. It is not necessary to bypass or de-energize the regulator to remove the control.
SPECIAL FEATURES Page 14 Catalog OPERATION AT LESS THAN RATED VOLTAGE JFR regulators may be operated at less than the voltage for which they were designed. All system voltages for which control system taps have been provided are shown on the nameplate. When this is to be accomplished it may be necessary to reconnect particular leads at the upper 19-pin terminal block as illustrated on page 5.
SPECIAL FEATURES Page 15 FORCED AIR COOLING SUBBASE ASSEMBLY Certain regulators may be equipped for forced-air cooling and include fans mounted on the radiators. The fans are usually automatically controlled by means of the change in oil temperature (see Connection Diagram). The thermometer located in the top transformer oil contains two identical switches which control fan operation when fan control switch is in “Auto” position.
PARTS LIST Page 16 MAJOR COMPONENTS PARTS LIST INSTRUCTIONS FOR ORDERING PARTS When ordering parts give the quantity of parts required, the regulator serial number, parts list item number, complete description, and method of shipping. State whether for emergency repair, maintenance, spare part, etc. All shipments will be made F.O.
PARTS LIST Page 17 POSITION INDICATOR PARTS LIST Item 01-11 5083 5060 5061 5062 5065 5067 5068 5069 5071 5072 5073 5274 Item 01-11 5063C 5062C 5065C 5067C 5068C 5069C 5071C 5072C 5073C 5079C Description Position Indicator - Complete Solenoid Housing Gasket Drag Hand Solenoid Coil Adjusting Knob Faceplate Window Clamping Ring Vari-Amp TM Adjusting Switch Limit Switch (each) Flang Gasket Spacer Ring (not shown) Description Position Indicator - Complete Drag Hand Solenoid Coil Adjusting Knob Faceplate Wind
PARTS LIST Page 18 TYPE TLG DIAL SWITCH Item 01-11 *5320 *5320B 5317A 5321 5322 5323 5324 5325 5326 5327 Description Phenolic Panel Glass Polyester Panel Reversing Main Shaft Main Stationary Contacts Reversing Stationary Contact R Reversing Stationary Contact L Neutral Stationary Contact Collector Ring Collector Hub Reversing Switch Arm Item 01-11 5328A 5328B *5329 *5329A *5329B 5330 5331 5332 5333 5334 5336 Description Reversing Switch Finger Assembly Reversing Switch Hub Finger Assembly Drive Arm -
PARTS LIST Page 19 TYPE TLG QUICK BREAK MECHANISM Item 01-11 *5320 *5320B 5317A 5321 5322 5323 5324 5325 5326 5327 Description Item 01-11 Phenolic Panel Glass Polyester Panel Reversing Main Shaft Main Stationary Contacts Reversing Stationary Contact R Reversing Stationary Contact L Neutral Stationary Contact Collector Ring Collector Hub Reversing Switch Arm 5328A 5328B 5329 5329A 5329B 5330 5331 5332 5333 5334 5336 Description Reversing Switch Finger Assembly Reversing Switch Hub Finger Assembly Driv
PARTS LIST Page 20 TYPE TLF DIAL SWITCH FIGURE 20A Item 01-11 5351 5352 5353 5354 5355 5356 5357 5358A 5359 5360A Description Panel Stationary Contact Neutral Stationary Contact Stationary Contact - LH Stationary Contact - RH Collector Ring Shaft Assembly Main Finger Assembly (each) Contact Finger Assembly Collector Ring Contact Finger Assembly Collector Hub Item 01-11 *5363 5364 5365 *5366 5366A 5367 5368 5369 5370 5373 Description Drive Plate Contact Finger Assembly - Rev.
PARTS LIST Page 21 TYPE TLF QUICK BREAK MECHANISM Figure 21A Item 01-11 5323A 5243B 5251 5252 5256 5257 5259 5260 5262 5263 5264 5265 Description Counter Switch Assembly Neutral Switch* Mounting Frame Motor Drive Spring Tube Drive Spring Spacer Notched Index Plate Latch Latch Spring Latch Pin Reversing Switch Drive Arm *This neutral switch switch became effective with type TLF-30D quick break mechanism.
PARTS LIST Page 22 BYPASS ARRESTERS Item 01-11 Description Volts 5420 Bypass Arrester Assembly 3 kV MOV 5421 5422 5423 5424 5425 5428 5428A 5429 2,500, 5,000, 7,620 Bypass Arrester Crystal, 3 kV MOV Mounting Bracket Assembly Bypass Arrester Assembly, 3 kV MOV 12,000-13,800-14,400 Bypass Arrester Crystal, 3 kV MOV Mounting Bracket Assembly Bypass Arrester Assembly, 6 kV MOV 19,920 Bypass Arrester Crystal, 6 kV MOV Mounting Bracket Assembly Include regulator serial number when ordering Figure 22B Polym
PARTS LIST Page 23 BUSHINGS Item 01-11 Description 5400P Bushing Assembly for 15 kV 5400R Bushing Assembly for 15 kV 5400S Bushing Assembly for 15 kV 5401P Bushing Porcelain for 15 kV 5401R Bushing Porcelain for 15 kV 5401S 5410 5419 5411 5418 5426 Bushing Porcelain for 15 kV Clamping Ring for 5400 and R Ratings Clamping Ring for 5400S Rating Cushion Spring Cap Screw Bushing Cap Line Terminal for 5400P Rating Bushing Cap Line Terminal for 5400R and S Ratings Gasket Gasket 5430 5427 4034 kVA
PARTS LIST Page 24 BUSHINGS Item 01-11 Description 5400T Bushing Assembly 15 kV 5400U 5400V Bushing Assembly, 15 kV Bushing Assembly, 23 kV 5400W Bushing Assembly 15 kV 5400X 5400Y Bushing Assembly, 23 kV Bushing Assembly, 23 kV 5400YY 5400Z 5400AB 5400AC 5401T Bushing Assembly, 15 kV Bushing Assembly, 23 kV Bushing Assembly, 23 kV Bushing Assembly, 15 kV Bushing Porcelain, 15 kV 5401U 5401V Bushing Porcelain, 15 kV Bushing Porcelain, 23 kV 5401W Bushing Porcelain, 15 kV 5401X 5401Y Bushin