User Guide

CDV
II 3G
Operating instruction
Refrigerant Valves PS45
for flammable and safety refrigerants
CDV..MVL..
One valve type for expansion, hot-gas and suction throttle applications
Approved according to directive 94/9/EC (ATEX 95)
Certificate: SEV 05 ATEX 0154X
Four valve sizes with k
vs
values from 0.25 to 6.3 m³/h
Selectable standard interface DC 0/2...10 V or DC 0/4...20 mA
Short positioning time (< 1 s)
Closed when deenergized
Hermetically sealed towards outside
Robust and maintenance-free
Use
II 3G EEx nAC IIC T4
Refrigerant valve CDV..MVL.. is a device of device group II, category 3G pursuant to
Directive 94/9/
EG (ATEX 95) Appendix, that can be used pursuant to Directive
99/92/EG (ATEX 137) in zone 2 as well as natural gas groups IIA, IIB, and IIC, that are
a risk of explosion in the range for temperature classes T1 to T4 due to flammable
materials.
Permissible ambient temperature is -25°C to +55°C.