Installation Instructions

Installation Instructions
Document No. 129-587
October 20, 2016
OpenAir® Electronic Damper Actuators
GDE/GLB Enhanced Rotary Non-spring
Return
a. Actuator
b. Position indicator
c. Mounting bracket
d. Mounting screws
e. 4 mm hex key
f. Shaft insert for use with
3/8-inch (8-10 mm) shafts
Item Number: 129-587, Rev. CA Page 1 of 8
Figure 1. Parts of the GDE/GLB Enhanced Rotary Actuator.
Product Description
Steps for direct-coupled mounting of the OpenAir GDE
and GLB Enhanced Series non-spring return rotary
electronic damper actuators.
Product Numbers
GDE141.1U
GLB141.1P
GDE141.1U/B (24 pk)
GLB141.1Q
GDE141.1P
GLB146.1P
GDE141.1P/B (24 pk)
GLB161.1P
GDE141.1Q
GLB161.1Q
GDE142.1P
GLB166.1P
GDE146.1P
GLB341.1U
GDE161.1P
GLB346.1U
GDE161.1P/B (24 pk)
GDE161.1Q
GDE163.1P
GDE164.1P
GDE166.1P
GDE341.1U
GDE346.1U
Required Tools
4 mm hex key (included)
4 mm (5/32-inch) drill bit and drill
Small flat-blade screwdriver
Marker or pencil
Estimated Installation Time
30 minutes
Warning/Caution Notations
Personal injury/loss of life may
occur if you do not follow a
procedure as specified.
Equipment damage or loss of
data may occur if you do not
follow a procedure as
specified.
Instructions
WARNING:
Do not open the actuator.
NOTE: Place the actuator on the damper shaft so
that the front of the actuator is accessible.
The label is on the front side.
1. Determine whether the damper blades will rotate
clockwise or counterclockwise to open. See Figure
12 and Figure 13.
2. If the blades will rotate counterclockwise, slide the
manual override switch to manual, and move the
adjustment lever to the right. Return the switch to
automatic. See Figure 9.
Mounting and Installation
Mounting Orientation
UL NEMA Type 2 and IP54 approved in all positions
except as shown below:
Figure 2. Unapproved Position for UL NEMA Type 2
and IP54.
NOTE: The GDE/GLB Enhanced actuator comes with
a factory-installed 1/2-inch shaft guide. If the
shaft size is 1/2-inch, proceed with Figure 6.

Summary of content (8 pages)