Installation Instructions

Siemens Building Technologies, Inc.
8 Fernwood Road
Florham Park, New Jersey 07932
P/N 315-049700-2 PAGE 1 OF 4
Fire Safety
INSTALLATION INSTRUCTIONS
Model FS-RD3
REMOTE LCD ANNUNCIATOR
The FS-RD3 Remote LCD Annunciator is an optional accessory for the FS-250 Fire Alarm System
Control Unit. The FS-RD3 provides a 4 x 20-character LCD display along with the system status LEDs
that display the event status of the system. The enable keyswitch allows system reset, trouble
silence/acknowledge, alarm silence and menu access for partial system control. The lamp test operation
is also enabled by the keyswitch and is limited to the annunciator. The annunciator mounts to a
horizontally mounted 6-gang box, 2” deep minimum. The FS-RD-SB/-R Surface Backbox may be used for
surface mounting. The FS-RD-SB is black and the FS-RD-SB-R is red.
PARTS SUPPLIED
1 Remote LCD Annunciator
4 Mounting Screws
1 Instruction Sheet
1 Operating Instructions
FS-RD3 DIMENSIONS
ABORT
DISCHARGE
PRE-
DISCHARGE
TROUBLE
PRE-
ALARM
ALARM
SILENCED
ALARM
SUP
POWER
BUTTON ENABLE
ON
OFF
MENU
SYSTEM RESET
ALARM SILENCE
ACKNOWLEDGE
M3
M4
M1
M2
4-1/2”
11-13/16”
FS-RD3 WIRING
TB1
GND
GND
Step 1.) Installation is to be done by qualified personnel
who have thoroughly read and understood this
instruction sheet.
Step 2.) Disconnect BATTERY and AC prior to working on
equipment.
Step 3.) Mount 6-gang backbox horizontally as required
(see mounting below).
Step 4.) Set the dip switch for proper remote address (see
page 2).
Step 5.) Attach conduit and run wires as required.
Step 6.) Connect IN wires from fire alarm system control
unit or previous remote as required.
Step 7.) Connect OUT wires to next remote or 120 ohm
E.O.L. Resistor Assembly (P/N 140-050008-1), if
last remote.
Step 8.) Attach unit to backbox, using four P/N 906-220608
screws.
Step 9.) Apply power to system.
Step 10.) Check for proper operation of functions.
FS-RD-SB/-R DIMENSIONS
Notes:
1.) Units to be installed in accordance with all local
codes.
2.) T-Tapping is not allowed! Communication wiring
must be daisy chained from remote to remote.
3.) Terminal block will accept a maximum of 12 AWG
wiring and minimum of 18 AWG.
4.) Use twisted pair cable with a characteristic
impedance of approximately 120 ohms. 4000 feet
Cable for power (+ & -) and
Twisted pair Cable for data
(X+ & X-) from panel or
previous remote and to next
remote or 120 ohm E.O.L.
Resistor Assembly (P/N 140-
050008-1) on the last
remote.
Power Limited and Supervised

Summary of content (4 pages)