Specifications

The FS-250C addressable fire alarm control panel is a
small, low cost fire alarm panel suited for stand-alone
operation in small to medium sized facilities. It features a
single addressable input device circuit and four notification
appliance circuits. The FS-250C is ULC Listed.
Main System
The FS-250C indicates alarm, trouble and supervisory
conditions with an 80 character backlit LCD display, as
well as a 20 zone/4 signal LED annunciator that is built in
to the Front Panel. Acknowledge, alarm silence and
system reset are accomplished with built-in membrane
control buttons. Basic user and maintenance level
functions such as viewing history or system enable/
disable are also accomplished through the membrane
control buttons. Password protection of maintenance
level functions is present. The main system can charge
up to 32 AH battery sets, up to 12 AH will fit inside the
enclosure.
The basic FS-250C features a single addressable signaling
line circuit (Class A or B) capable of supporting up to 252
addressable input devices, whether they are detectors,
manual pull stations, or contact monitoring points. Each
4306C
CATALOG NUMBER
One intelligent signaling line circuit (DCLB + DCLA)
SureWire Polarity insensitive loop wiring
Utilizes S-Series detectors and devices
Supports up to 252 addressable inputs and signal/relay
outputs
Devices operate on standard wire, no twist or shield
required
FirePrint application specific fire detection
4 Class B/2 Class A signal circuits
Up to 6 amps of signal power
Built in strobe synchronization protocol
One man walk test (silent or audible)
80 Character backlit LCD display & 20 Zone/4 signal circuit
LED annunciation on Front Panel
Optional internal DACT capable of transmitting point or
group information
Programmable from front keypad or Windows based PC
configuration tool
Single stage and 2-stage operation
Alarm, pre-alarm, supervisory, trouble
Auto program feature makes system start-up faster
Maintenance and technician level passwords
ULC Listed
FireSeeker Model FS-250C
Addressable Fire Alarm Control Panel
detector can also have an optional audible detector base,
relay detector base, or remote lamp associated with it.
These auxiliary devices are completely controlled through
logic and are not required to activate simultaneously with
the detector.The system also has four class B or 2 class
A Notification Appliance Circuits built into the main board.
Each circuit has a capacity of 1.5 amps of 24 VDC for
powering horns, strobes, chimes, and other notification
appliances. The total base system capacity for the four
circuits in 3.0 amps and can be expanded to 6A. Each
signal circuit is fully programmable and supports standard
and custom coded outputs of audible devices. Systems
can be configured to sound different codes on the same
signal circuit to indicate different conditions.
The FS-250C has four Form C relays on the main board
for monitoring alarm, pre-alarm, supervisory and trouble
conditions. Each relay is rated at 1 amp @ 28VDC.
Auxiliary 24VDC power is also available on the main
board, with a capacity of up to 0.4 amps.