Installation Instructions

Siemens Building Technologies, Inc.
8 Fernwood Road
Florham Park, New Jersey 07932
P/N 315-049350-4
Fire Safety
INSTALLATION INSTRUCTIONS
Model FS-DLC
Device Loop Card
INTRODUCTION
The Siemens Device Loop Card (FS-DLC) is the driver for the Siemens P2 Addressable smoke detectors,
manual stations, monitor devices and control devices used on the FS-250 Fire Alarm System Control
Units. The FS-DLC contains 9 LEDs for diagnosis of problems.
OPERATION
The FS-DLC initializes, operates, and maintains all devices residing on the loop. The FS-DLC
communicates all relevant device and event information, such as alarms and troubles, to the Main System
Board. The sensitivity of any intelligent smoke detector and the logic functions of any intelligent output
devices can be checked and adjusted from the system display and keypad. All information about the
devices on the loop can be displayed on the system display. The FS-DLC allows the system polarity
insensitive devices to be connected without generating errors.
The FS-DLC supports one loop of 252 Siemens P2 intelligent field devices (252 addresses) as well as
device accessories (relay bases, audible bases, and remote lamps) in any combination. (The on-board
microprocessor provides the FS-DLC with the ability to function and initiate alarm conditions even if the
main board microprocessor fails.)
The FS-DLC contains one reset switch, and 9 LEDs as shown in Figure 1. Pushing the RESET switch
(S1) re-initializes the FS-DLC operation.
Fig. 1