Installation Instructions

P/N 315-699466-1
(447300)
1
Fire Safety
INSTALLATION INSTRUCTIONS
Model FS-RU Serial Relay Unit
Model FS-RE8 Serial Relay Extender
The FS-SAU Serial Relay Unit is an optional accessory for the FS-100 Fire Alarm System Control Unit. The
FS-SAU includes a processor board and a relay board. The processor board receives commands from the
control unit for activating the relays and transmits supervision and control functions to the control unit. The
processor board can control up to 3 relay boards. Each relay board provides 8 relays with form C contacts.
The control unit can address up to 8 Serial Relay Units and/or Serial Annunciator Units. Auxiliary power
supplies will be required to power units beyond the control unit capability.
FS-RU PARTS SUPPLIED
1 Processor Board Assembly
1 Relay Board Assembly
1 34 pin Cable Assembly, 3 1/2”
1 PCB Track, 14 1/2”
1 10 pin Cable Assembly, 6”
1 Screwdriver
3 Locking Nut, #6-32
1 Instruction Sheet
FS-RE8 PARTS SUPPLIED
1 Relay Board Assembly
1 34 pin Cable Assembly, 15”
1 34 pin Cable Assembly, 3 1/2”
1 PCB Track, 14 1/2”
3 Locking Nut, #6-32
1 Instruction Sheet
FS-RU DIMENSIONS
FS-RE8 DIMENSIONS
Step 1.) Installation is to be done by qualified personnel
who have thoroughly read and understood this
instruction sheet
Step 2.) Disconnect all
power into system, including
batteries.
Step 3.) Mount enclosure as required.
Note: Enclosure must be UL Listed for Fire Protective
Signaling. Use Model FS-AE Fire Alarm
Accessory Enclosure, if required.
Step 4.) Attach conduit and run wires as required.
Step 5.) Set processor board dip switch for proper
remote address (1- 8).
Step 6.) Set each relay board dip switch for proper relay
set number (1- 8, 9-16, 17-24).
Note: Relays are numbered from left to right:
Relay Set TB1 TB2 TB3 TB4
(1-8) 1 2 3 4 5 6 7 8
(9-16) 9 10 11 12 13 14 15 16
(17-24) 17 18 19 20 21 22 23 24
Step 7.) Set jumper P6 for desired buzzer operation.
J6 BUZZER ACTIVATION
REMOTE (Header P2)
LOCAL (Processor Board Buzzer)
Step 8.) Mount PCB Track(s) using #6-32 locking nuts and
snap in PCB assemblies.
Step 9. Plug in the 34-pin cable assembly(s) to the PCB
assemblies as required.
Step 10. Connect ground wire(s) to chassis ground using
#6-32 locking nut(s).
Step 11.) Connect IN wires from fire alarm system control
unit or previous remote as required.
Step 12.) Connect OUT wires to next remote or 120 ohm
terminating resistor , if last remote.
Step 13.) Connect relay contacts, as required.
Step 14.) Apply power to system.
Step 15.) Program control unit for required relay operation.
Step 16.) Check for proper operation of functions.