Instruction Manual

P/N 315-093466-3
Installation Instructions
Model FLASH-UK
MMB-1 Upgrade Kit
Fire Safety
To increase the available FLASH memory
on a SIEMENS Model MMB-1, complete the
following steps in order.
NOTE
Install this upgrade kit if:
The CSG-M indicates that the custom
.mxl file is too large for the standard
amount of factory installed flash.
or
The .mxl file exceeds 80,000 bytes
and the MMB-1 contains Revision
6.00 or higher.
1. Inform the building owner and any other
authority necessary that the System will be
out of service while the changeover is
occurring.
2. Disconnect the standby batteries from the
System.
3. Disconnect the AC Power from the System.
4. Open the door with the MKB-2 installed to
gain access to the MMB-1.
5. For MXL:
Disconnect the ribbon connector that links
the MMB-1 motherboard (P8) with the
ANN-1 on the back of the MKB-2 Annun-
ciator Keyboard.
For MXLV:
Disconnect the ribbon connector that links
the MMB-1 motherboard (P8) with P5 on
the ACM-1.
6. Locate the IC socket numbered 115 on the
MMB-1.
7. Note that:
The IC is installed with the U shaped
cutout on the chip at the bottom of the PC
board.
IMPORTANT
IF THE ICs ARE INSTALLED INCOR-
RECTLY, SEVERE DAMAGE TO THE
MMB-1 CAN OCCUR AT POWER UP.
8. Put the additional IC 115 in an approved IC
insertion tool (like that supplied with the
CSG-2 kit). Very gently insert the IC in the
socket labeled IC 115.
Be sure that:
a. The U cut in the chip is towards the
bottom of the board.
b. All IC pins are properly aligned with
the connector.
9. Inspect the NEWLY installed IC to verify that:
a. All IC pins are properly seated in the
socket.
b. The chip is in the right place and
positioned correctly.
10. Reassemble the System by reversing Steps 1
through 5 above. Please refer to the
MXL/MXLV Manual, P/N 315-092036, for
additional assistance.
11. Once the System has completed its initializa-
tion startup routine and the CSG-M has been
loaded, perform a System checkout satisfac-
tory to the building owner and the local
authority having jurisdiction.
Siemens Building Technologies, Inc.
8 Fernwood Road
Florham Park, New Jersey 07932
Siemens Building Technologies, Ltd.
2 Kenview Boulevard
Brampton, Ontario L6T 5E4 CN
firealarmresources.com