FDCIO223 Input/Output Module (Transponder) Technical Manual Valid for product Version ES ≥ 50 009122_k_en_-2018-10-03 Building Technologies Control Products and Systems
Imprint Imprint Technical specifications and availability subject to change without notice. Transmittal, reproduction, dissemination and/or editing of this document as well as utilization of its contents and communication thereof to others without express authorization are prohibited. Offenders will be held liable for payment of damages. All rights created by patent grant or registration of a utility model or design patent are reserved. Issued by: Siemens Switzerland Ltd.
Table of contents 1 1.1 1.2 1.3 1.4 About this document ............................................................................. 5 Applicable documents ................................................................................. 8 Download center ......................................................................................... 8 Technical terms and abbreviations .............................................................. 9 Revision history ..............................................
3.5 3.6 3.7 Diagnosis levels......................................................................................... 43 Behavior in degraded mode ....................................................................... 45 Accessories ............................................................................................... 46 3.7.1 Mounting foot FDCM291 ............................................................. 46 3.7.2 U-rail TS35 ...................................................................
About this document Applicable documents 1 1 About this document ● Specialist electrical engineering knowledge is required for installation. ● Only an expert is permitted to carry out installation work. Incorrect installation can take safety devices out of operation unbeknown to a layperson. Goal and purpose This document contains all information on the input/output module (transponder) FDCIO223 with a product version ES ≥50.
1 About this document Applicable documents Target groups The information in this document is intended for the following target groups: Target group Activity Qualification Product Manager ● ● ● Project Manager ● ● Installation personnel ● ● Commissioning personnel ● ● ● Maintenance personnel ● ● ● Is responsible for information passing between the manufacturer and regional company. Coordinates the flow of information between the individual groups of people involved in a project.
About this document Applicable documents 1 Conventions for text marking Markups Special markups are shown in this document as follows: ⊳ Requirement for a behavior instruction 1. 2.
1 About this document Applicable documents 1.
About this document Technical terms and abbreviations 1 1.
1 About this document Revision history 1.4 Revision history The reference document's version applies to all languages into which the reference document is translated. The first edition of a language version or a country variant may, for example, be version 'd' instead of 'a' if the reference document is already this version.
About this document Revision history Modification index Edition date Brief description ● f 2015-06-17 ● ● ● ● ● ● ● ● ● – Compatibility – Defining the mounting site of the module and configuration of the lines – Planning the detector line – Planning the control line – Planning contact input – Connecting input/output module – Calibrating the control line Technical data Document applies to devices with ES ≥50 Change to date format in line with ISO 8601 specifications (yyyy-mm-dd format); editorial ad
2 Safety Safety instructions 2 Safety 2.1 Safety instructions The safety notices must be observed in order to protect people and property. The safety notices in this document contain the following elements: ● Symbol for danger ● Signal word ● Nature and origin of the danger ● Consequences if the danger occurs ● Measures or prohibitions for danger avoidance Symbol for danger This is the symbol for danger. It warns of risks of injury. Follow all measures identified by this symbol to avoid injury or death.
Safety Safety instructions 2 How risk of injury is presented Information about the risk of injury is shown as follows: WARNING Nature and origin of the danger Consequences if the danger occurs ● Measures / prohibitions for danger avoidance How possible damage to property is presented Information about possible damage to property is shown as follows: NOTICE Nature and origin of the danger Consequences if the danger occurs ● Measures / prohibitions for danger avoidance Building Technologies Fire Safety
2 Safety Safety regulations for the method of operation 2.2 Safety regulations for the method of operation National standards, regulations and legislation Siemens products are developed and produced in compliance with the relevant European and international safety standards.
Safety Safety regulations for the method of operation 2 Mounting, installation, commissioning and maintenance ● ● ● ● If you require tools such as a ladder, these must be safe and must be intended for the work in hand. When starting the fire control panel ensure that unstable conditions cannot arise. Ensure that all points listed in the 'Testing the product operability' section below are observed.
2 Safety Standards and directives complied with 2.3 Standards and directives complied with A list of the standards and directives complied with is available from your Siemens contact. 2.4 Release Notes Limitations to the configuration or use of devices in a fire detection installation with a particular firmware version are possible. WARNING Limited or non-existent fire detection Personal injury and damage to property in the event of a fire.
Structure and function Overview 3 3 Structure and function 3.1 Overview The input/output module FDCIO223 is operated on the FDnet/C-NET and has two inputs/outputs. These can be configured as follows: ● Collective detector line and conventional detector line ● Control line ● Contact input The graphic below shows the integration of the module in the fire detection system.
3 Structure and function Overview 3.1.1 Details for ordering Type Order number Designation FDCIO223 S24218-B102-A1 Input / output module (transponder) Scope of delivery ● ● ● ● ● ● ● ● 18 | 72 Building Technologies Fire Safety 1x input/output module FDCIO223 2x resistors 560 Ω, 0.25 W 2x resistors 680 Ω, 0.25 W 2x resistors 2.7 kΩ, 0.25 W 2x resistors 3.3 kΩ, 0.
Structure and function Overview 3 3.1.2 Product version ES The product version ES provides the technical status of a device in terms of software and hardware. The product version is provided as a two-digit number.
3 Structure and function Setup 3.2 Setup The modules consist of the module carrier, the printed circuit board and the cover cap. The printed circuit board includes several LEDs. The LEDs indicate the status of the inputs and outputs and the operating condition of the modules. The cover cap of the printed circuit board is transparent such that the statuses of the LEDs are visible even when the housing is closed.
Structure and function Setup 3 3.2.
3 Structure and function Setup 3.2.3 Indication elements The position numbers in the following chapters relate to the graphic in chapter 'Printed circuit board view [➙ 21]'. 3.2.3.
Structure and function Setup Operating condition Flashing mode Fault in localization mode 'PWR PRIM' off 'FAULT PRIM' flashes yellow every second and flashes yellow twice every four seconds 3 Graphic 0 1 2 3 4 5 6 7 8 9 10 11 12 [s] 0 1 2 3 4 5 6 7 8 9 10 11 12 [s] t t ¹ The 'PWR PRIM' and 'FAULT PRIM' LEDs do not flash in sync in test mode Secondary side LEDs – Position number 11 Operating condition Flashing mode Normal 'PWR SEC' flashes green every second 'FAULT SEC
Structure and function 3 Setup 3.2.3.2 Status display for the lines One green (a) and one red (b) LED indicates the status of each input/output (LEDs with position numbers 9a, 9b and 10a, 10b). Their meaning depends on how the input/output is configured.
Structure and function 3 Setup Operating condition Flashing mode Graphic Input not monitored, e.g.
Structure and function 3 Setup Input/output is configured as an output (control line) – Position numbers 9 and 10 Operating condition Flashing mode ● ● ● Both LEDs off Not active No supply Incorrectly configured Standby LED(a) lights up green continuously Graphic 0 1 2 3 4 5 6 7 8 9 10 11 12 [s] 0 1 2 3 4 5 6 7 8 9 10 11 12 [s] 0 1 2 3 4 5 6 7 8 9 10 11 12 [s] 0 1 2 3 4 5 6 7 8 9 10 11 12 [s] 0 1 2 3 4 5 6 7 8 9 10 11 12 [s] 0
Structure and function Setup 3 3.2.
3 Structure and function Function Jumper plugged in: The internal fuse of the input/output module is bridged Jumper not plugged in: The internal fuse is active ● ● ● ● ● Only the settings detailed above are permitted. If the 'Fuse' jumper is activated, fuses provided by the customer must be used instead of the internal fuses. You will find more information on protecting the control lines in chapter 'Power supply [➙ 29]'.
Structure and function Function 3 3.3.2 Input/output module primary side Communication The communication with the control panel is performed via the FDnet/C-NET detector line. Configuration is performed on the control panel. Line separator All FDnet/C-NET devices are equipped with a line separator. The FDnet/C-NET device is equipped with electronic switches which isolate the defective part in case of a short-circuit on the FDnet/C-NET detector line. The rest of the detector line remains serviceable.
3 Structure and function Function 3.3.4 Operation modes The input/output module FDCIO223 has the following operation modes: ● Normal operation ● Test/inspection ● Localization Normal operation The input/output module FDCIO223 is running in intended operation. The inputs are monitored and evaluated. The outputs can be triggered. Test/inspection With test mode/inspection mode, the input/output module functions according to how the input/output and fire control panel are configured.
Structure and function Input/output configuration options (secondary side) 3 3.3.5 Earth fault monitoring The secondary side is monitored for ground faults regardless of mode. Ground fault monitoring can be deactivated with a jumper. The setting for ground fault monitoring always applies to both inputs/outputs. Switch off ground fault monitoring if a safety barrier SB3 with intrinsically safe detectors for potentially explosive atmospheres is connected.
3 Structure and function Input/output configuration options (secondary side) 3.4.1 Using two detector lines simultaneously The following conditions apply when using two detector lines at input/output 1 and 2 simultaneously: ● Without a safety barrier SB3, a maximum of 32 devices may be connected per detector line and the DC 24 V secondary side power supply has to comply with standard EN 54-4.
Structure and function Input/output configuration options (secondary side) 3.4.2.2 3 Conventional detectors which can be connected ● Conventional detector line configured as SynoLINE300: – Synova 300 series fire detector ● Third-party products in accordance with 'Industrial conventional', e.g.
3 Structure and function Input/output configuration options (secondary side) 3.4.2.3 Detector line design Permissible cable types The detector line is compatible with the following cables: ● Shielded cables ● Unshielded cables The table below shows the permissible cable values: Cable value Detector line without safety barrier SB3 Detector line with safety barrier SB3 Inductance Max. 5 mH Max. 1.6 mH Capacitance Max. 4 µF Max. 83 nF Resistance Max. 150 Ω Max.
Structure and function Input/output configuration options (secondary side) 3 De-energization of the detector line With product version ES ≥41, the collective detector lines are de-energized as soon as the FDnet/C-NET is current-free. With all ES versions, the collective detector lines can also be de-energized individually (control panel-specific). You will find more detailed information in the fire detection system documentation. 3.4.2.
3 Structure and function Input/output configuration options (secondary side) 3.4.2.5 Alarm verification To help prevent false alarms, the input/output module FDCIO223 features a form of alarm verification that can be activated as required. When alarm verification is activated, any alarm (1) that occurs will first be stored by the input/output module. Then the detector line will be reset and powered up again.
Structure and function Input/output configuration options (secondary side) 3.4.2.6 3 Monitoring The input/output module monitors the detector line for the following criteria: ● Alarm ● Open line ● Short-circuit ● Ground fault (only both inputs/outputs jointly, no line-specific fault message) 3.4.3 Configuration as a contact input The inputs/outputs of the input/output module can be configured as contact inputs.
3 Structure and function Input/output configuration options (secondary side) Circuit The graphic below shows the various circuit options available for contact inputs: 2 2.7 kΩ 560 Ω 2.7 kΩ + 4 3.3 kΩ 40 mAT 3 680 Ω I/O 3.3 kΩ 1 FDCIO223 560 Ω Figure 9: Circuit for contact inputs 1…3 Monitoring for open line and short circuit 4 Monitoring for open line only Recommendation: Install a 40 mAT fuse as shown in the graphic to protect the monitoring resistors from commissioning errors.
Structure and function Input/output configuration options (secondary side) 3 3.4.4 Configuration as a control line 3.4.4.1 Overview Current limiting Within the context of control, the secondary side external supply voltage (DC 24 V) is applied directly to the relevant output for the control lines via a relay. In the input/output module FDCIO223, internal fuses (0.7 AT self-resetting fuses: PTCs) are present on the control lines. Protect the contacts either with the internal fuses (max. 0.
3 Structure and function Input/output configuration options (secondary side) 3.4.4.2 Identical-polarity monitoring With this type of monitoring, the connected load's internal resistance is monitored. As a result, no monitoring resistors need to be installed. Calibration is only possible with the push button. Circuit featuring identical-polarity monitoring FDCIO223 I/O 2 24 V 1 + 4V R L= 30...3,3 k 0V 0V Figure 10: Circuit for control lines with identical-polarity monitoring 1 Internal fuse (0.
Structure and function Input/output configuration options (secondary side) 3.4.4.3 3 Reverse-polarity monitoring With this type of monitoring, the control voltage polarity is reversed in relation to that of the monitoring voltage. The monitoring resistor is 3.3 kΩ and parallel with the load. The load must be isolated from the monitoring voltage by means of a diode. Reverse-polarity monitoring must always be used in the case of electronic loads.
3 Structure and function Input/output configuration options (secondary side) 3.4.4.4 Control without confirmation Configuration The following configurations are supported in the case of control without confirmation: ● Once activated, the control remains permanently active ● Once activated, the control only remains active for a certain time. How long the contact remains active can be configured (pulse duration). ● Once activated, the control remains astable (symmetrical pulse pattern of 1 s).
Structure and function Diagnosis levels 3 Control methods involving pulse patterns Control methods involving pulse patterns reduce the service life of the relay contacts on the input/output module. Contact wear is also dependent on the load. Up to 300,000 switching cycles are permitted. At one switching cycle per second, 300,000 switching cycles are reached after approx. 3.5 days.
3 Structure and function Diagnosis levels Information displayed on Meaning the detector exchanger and tester 'No deviation' 'maybe excha.' 1 'advice excha.' 1 'needed excha.
Structure and function Behavior in degraded mode 3 3.6 Behavior in degraded mode Applicable for the FDnet/C-NET: When the main processor of the fire control panel fails, the control panel works in degraded mode operation. Depending on the control panel type, the fire control panel can continue to perform the most important alarming and signaling functions in degraded mode operation. Behavior of control panels that support degraded mode operation: ● Alarming is still ensured in degraded mode operation.
3 Structure and function Accessories 3.7 Accessories 3.7.1 Mounting foot FDCM291 ● ● ● ● For device mounting on a DIN rail TS35 Two mounting feet must always be used Compatible with: – Input module FDCI22x(-CN) – Input/output module FDCIO22x(-CN) – Output module FCA1209-Z1 – Multi line separator module FDCL221-M – Zone module, external powered FDCI223, FDCI723 – Sounder module FCA2005-A1 Order number: A5Q00003855 3.7.
Structure and function Accessories 3 3.7.3 Housing FDCH221 ● ● ● To protect against dust and wetness Compatible with: – Multi line separator module FDCL221-M – Input module FDCI22x(-CN) – Input/output module FDCIO22x(-CN) – Output module FCA1209-Z1 – Radio gateway FDCW241 – Zone module, external powered FDCI223, FDCI723 – Sounder module FCA2005-A1 Order number: S54312-F3-A1 3.7.4 Connection terminal DBZ1190-AB ● ● ● ● ● Auxiliary terminal for connecting cables For T-branches of additional cabling, e.
3 Structure and function Accessories 3.7.6 M20 x 1.5 metal counter nut ● ● For use with metal cable gland M20 x 1.5 Order number: A5Q00004479 ● For strain relief on the connection wires or generally for attachment Made from polyamide Compatible with: – Input module FDCI22x(-CN) – Input/output module FDCIO22x(-CN) – FDCL221 line separator – Multi line separator module FDCL221-M – Radio gateway FDCW221 and FDCW241 – Zone module, external powered FDCI223, FDCI723 Order number: BPZ:1825330001 3.7.
Planning Compatibility 4 4 Planning When planning a project, proceed as follows: 1. Define the mounting site and configuration of the lines 2. Plan the various line types: – Collective detector line – Collective detector line for areas at risk of explosion (zone 1 and zone 2) – Conventional detector line – Control lines – Contact inputs 4.
4 Planning Defining the mounting site of the module and configuration of the lines 4.2 Defining the mounting site of the module and configuration of the lines ● Define the type of application for the input/output module. See annex 'Planning the type of application, configuration overview [➙ 68]'. Using housing FDCH221 ● Use housing FDCH221 to protect the input/output module against unauthorized access.
Planning Filling out the configuration sheet 4 4.7 Filling out the configuration sheet 1. Copy out the configuration sheet. You will find the configuration sheet in the attachment. 2. Fill out the configuration sheet. 3. Hand over copies of the completed configuration sheet to the installer and the service technician.
5 Mounting / Installation Mounting with housing 5 Mounting / Installation The mounting procedure depends on whether the input/output module FDCIO223 is installed on a U-rail TS35 in a fire control panel or with housing FDCH221. WARNING Electrical voltage on output cables! Mortal danger due to electric shock! ● Ensure that the cables are not supplied with voltage during installation.
Mounting / Installation Mounting with housing 5 Cable with diameter >1.5 mm² If the cable diameters on the inputs/outputs are greater than 1.5 mm2, auxiliary terminals must be used: ● In the case of cables with a diameter of 1.5…2.5 mm2, the connection terminal DBZ1190-AB (accessories) can be used. ● In the case of cables with a diameter of >2.5 mm2, an appropriate terminal must be provided by the customer. The terminal can be positioned inside the housing.
5 Mounting / Installation Mounting in a fire control panel 5.2 Mounting in a fire control panel To make sure that the LEDs on the module remain visible at all times, the cover cap is transparent. Pick a suitable mounting position, ensuring that the LEDs will remain visible at all times during operation. When installing the module on a DIN rail, proceed as follows: 1. Insert the two mounting feet FDCM291 supplied into the side of the module. 2.
Mounting / Installation 5 Connecting input/output module 5.3 Connecting input/output module Connect the module in accordance with the corresponding connection diagrams. NOTICE Incorrectly connected input/output module Damage to the device ● Never connect the external DC 24 V power supply or the FDnet/C-NET detector line to the green terminals of input/output 'I/O 1' or input/output 'I/O 2'. ● Observe the assignment of terminals as per chapter 'Printed circuit board view [➙ 21]'.
5 Mounting / Installation Connecting input/output module Note the following with regard to the device connections. You will find an overview of the terminal assignments in chapter 'Printed circuit board view [➙ 21]'. ● The shielding of the FDnet/C-NET detector line must be connected to terminal 15. ● The shielding of the 24 V secondary side power supply must be connected to terminal 16.
Commissioning Calibrating the control line 6 6 Commissioning The device is commissioned via the control panel. The exact procedure is described in the control panel documentation. NOTICE Before commissioning the device, check that the configuration of the inputs/outputs corresponds to the circuit. Conduct a performance check once commissioning is complete. Measure the current at the activated outputs.
7 Maintenance / Repair Status query 7 Maintenance / Repair 7.1 Status query Status query on the detector exchanger and tester The FDCIO223 input/output module is equipped with the MC link (Maintenance and Commissioning Link). You will find more information in documents 007227 and 009718. Status queries with detector exchanger and tester FDUD292 or intelligent detector tester FDUD293 are only possible with devices of the 'Sinteso' product line on the FDnet.
Specifications Technical data 8 8 Specifications 8.1 Technical data You will find information on approvals, CE marking, and the relevant EU directives for this device (these devices) in the following document(s); see 'Applicable documents' chapter: ● Document 009168 FDnet/C-NET detector line Line separator Operating voltage DC 12…33 V Operating current Max. 0.
8 Specifications Technical data Detector lines at I/O1, I/O2 Can be configured as: ● ● ● Collective detector line Collective detector line for areas at risk of explosion Conventional detector line Number of detectors per detector line Max. 32 Collective detector key figures KMK 32 Max. number of devices in total when using one or two safety barriers SB3 32 Operating voltage / quiescent current: ● Collective / collective Ex 20 V / 6.
Specifications Technical data 8 Message evaluation for: ● Alarms 1 s (can be increased by the alarm response time) ● Faults 1 s (can be increased by the filter time) ● Ground fault 60 s Compatibility Contact input ● ● Collective Collective detector line for areas at risk of explosion ● Conventional detector line For details, see 'List of compatibility' and 'Annex' chapter Measurement voltage ● With effective terminating resistance 560 Ω Approx. 1.
8 Specifications Technical data Control line Output voltage in active state 24 V nominal (= secondary-side supply voltage) Output current per control line in active state ● Max. 2 x 1 A or 1x 1.5 A in housing FDCH221 and an operating temperature of max. 60° C Monitored for: ● ● ● Open line Short-circuit Ground fault monitoring (both inputs/outputs jointly) Reverse-polarity monitoring voltage ● With effective terminating resistance 3.3 kΩ Approx. 10 V ● Open Approx.
Specifications Technical data Ambient conditions 8 Operating temperature/permissible ambient temperature -25…+60 °C Storage temperature -30…+65 °C Air humidity ≤85 % rel.
8 Specifications Dimensions 43.5 46.5 8.2 8.2 Dimensions 24 118 132 A 102 A = Ø 4.5 5.
Specifications Master gauge for recesses 8 8.3 Master gauge for recesses 55 55 6.4 110 187.2 200 B B = Ø 5.0 6.4 B Figure 16: Master gage for recesses of housing FDCH221 8.4 Environmental compatibility and disposal This equipment is manufactured using materials and procedures which comply with current environmental protection standards as best as possible.
9 Annex Compatibility 9 Annex 9.1 Compatibility The table below shows the devices which, together with the FDCIO223, are approved according to EN 54-13. It is possible to connect additional devices as per the 'List of compatibility'. However, these devices have not been tested according to EN 54-13.
Annex Compatibility 9 110 series collective and conventional point detectors OP110 G212033 OH110 G212059 HI110 G212004 HI112 G212015 Manual call points (collective) DM1101 - DM1103 G295036 DM1104 G299068 FDM1101 G209148 Manual call points (conventional) FDM1101A G209149 Collective devices and manual call points for potentially explosive atmospheres Safety barrier SB3 - DM1101 - DM1103 G295036 DM1104 G299068 FDF241-9 G204010 FDL241-9 G204063 Special detectors Building Technol
9 Annex Configuration sheets 9.2 Configuration sheets 9.2.
Annex Configuration sheets 9 9.2.
Index Index A Adjustment element Jumper ........................................................... 28 Application area Ambient conditions ......................................... 50 Approvals........................................................ 59 C Calibrating the control line Control............................................................ 57 CE marking ..................................................... 59 Collective behavior Degraded mode operation ..............................
Index J Jumper ................................................ 21, 27, 31 Adjustment element ........................................ 28 L LED FDCIO223 status display ................................ 23 Line status display .......................................... 24 Line separator Function.......................................................... 29 Line status display LED ................................................................ 24 List of compatibility .................................
Issued by Siemens Switzerland Ltd Building Technologies Division International Headquarters Theilerstrasse 1a CH-6300 Zug +41 58 724 2424 www.siemens.com/buildingtechnologies Document ID: 009122_k_en_-Edition: 2018-10-03 © Siemens Switzerland Ltd, 2006 Technical specifications and availability subject to change without notice.