Data Sheet for Product

ARCHITECT AND ENGINEER SPECIFICATIONS
Data Sheet
A comprehensive fire-protection system
Answers for infrastructure
Cerberus
TM
PRO
Fire Safety & Security Products
Cerberus PRO
9800C
System Overview
Product Overview
The Cerberus PRO System, a comprehensive fire-
protection system from Siemens
Fire Safety, is a
technologically advanced fire-and-life-safety system.
Each Cerberus PRO system provides easy operation via
its push-button soft keys; a backlit LCD screen, and a
(4) four-way navigation push button
all located in
the upper portion of each panel.
Through the use of its unique multiprocessor
Network design
along with its ability to utilize
intelligent detection devices
Cerberus PRO
epitomizes a flexible and highly configurable fire
system. SureWire addressable-loop technology is
supported by Cerberus PRO.
Cerberus PRO is ideally suited for mid-market
applications via its 252 and 504-point addressable fire-
alarm-control panel (FACP), which are each
networkable systems.
In conjunction with these new, improved FACPs is a
state-of-the-art line of intelligent detectors. For
example, the Multi-Criteria Fire / CO Detector [with
ASAtechnology
TM
] is cutting-edge technology for
specialized applications
such as carbon-monoxide
detection. The Photoelectric Smoke Detector uses
microcontroller circuitry and surface-mount
technology for peak dependability.
Standard 252-point and 504-point
fire systems
Remote viewing for the 252-
point and 504-point systems
One (1) or (2) two-height-
unit enclosures
Powerful, but user-
friendly system interface
Softkey buttons
RS485 interface
Four-way navigation menu
with extended-views capability
Primary, regulated power
300-Watts is rated at 11.5 Amps
170-Watts is rated at 6.5 Amps
Universal AC power input:
120VAC or 240VAC
50 / 60Hz @ 2.0A max.
Fully field programmable, via a
Windows
®
-laptop PC
Built-in strobe synchronization protocol
Global annunciation and control
capability
Several relay commands: Alarm,
Trouble, Supervisory, etc.
Light-emitting diodes (LEDs) for:
Power, Alarm, Supervisory, Silenced,
Ground Fault, Trouble, and system-
status LEDs
Alarm command has a larger, distinctive LED
LED-option provides LED annunciation
of system activity
Backlit liquid-crystal display (LCD)
SureWire
TM
addressable-loop technology
Patented polarity-insensitive detection circuits
Intelligent / analog detection
circuits: ‘Class A’ or ‘Class B’
Supports FirePrint
TM
detection
applications
Supports single-person, ‘Walk Test
Sprinkler Supervision
End-user ‘Help’ screens
Multiple command stations
Supports pre-action, deluge and
Sinorix
TM
-agent releasing for
252 / 504-point systems
Releasing-valve monitoring
Supervised remote printer, via the
Remote Peripheral Module
for the 252 / 504-point systems
Menu-driven operator commands
5,000-event history-logging capability
with on-line and off-line reports
Off-line reports can be viewed the custom-
configuration programming tool
EEPROM software compatible
Multiple levels of password protection
Automatic environmental
compensation for smoke detectors
Pre-alarm operation
Alarm verification (by device or zone)
Degrade-mode operation
Logic-controlled output functions
Optional city-tie / leased-line module
Distributed processing
Emergency Alarm events for CO
detection, per NFPA 720
for the 252 / 504-point systems
Optional notification-appliance-circuit
(NAC) expansion module
Up to 3.0 amps (24VDC) load per output
Module used for 252/ 504-point systems
Detector Sensitivity Readout / Printout
per NFPA 72
NEC 760 power-limited circuits
ULC compliant
ULC Listed;
FM (#3010), CSFM (#7165-0067:0259)
and FDNY (#6104) Approved

Summary of content (8 pages)