Data Sheet for Product

ARCHITECT AND ENGINEER SPECIFICATIONS
Data Sheet
System Periphery Boards
Models FCI2016-U1 and FCI2017-U1
Answers for infrastructure
Cerberus
TM
PRO
Fire Safety & Security Products
Cerberus PRO Fire Safety
9802
Periphery Boards
Product Overview
The periphery boards (Models FC
I2016-U1 and
FCI2017-U1) are the main components for operation
of the Cerberus PRO panels (Models FC922 and
FC924). Both models are FM (
#
3010); CSFM (
#
7165-
0067:0259) and FDNY (
#
6104) Approved.
Each module operates and monitors input-device
identity; as well as controls the signaling-line circuits
that communicate with smoke detectors and other
field devices (i.e.
C-NET). All functions are
supported by the power supplies of either Model
FP2011-U1 or Model FP2012-U1.
Model FP2011-U1 provides regulated 24VDC,
nominal, 6 amps (max), while Model FP2012-U1
offers regulated 24VDC, nominal, 11.5 Amps
(max) to the Models FC922 and FC924 Cerberus
PRO systems.
Specifications
Each periphery board is equipped with two (2)
programmable ‘Class B’ (Style Y) or ‘one (1) Class A’
(Style Z) NAC, providing 24VDC, nominal @ up to 3A
per circuit of audible / visual notification appliances.
Either periphery board has an integrated C-NET loop
circuit with built-in EM
I surge protection, thus
allowing automatic devices to be installed and
configured for ‘Class B’ or ‘Class A’ circuit operation.
Model FCI2016-U1 supports (1) one-to-four (4) ‘Class
B’ circuits
or supports (1) one-to-two (2) ‘Class A
circuits that can supervise and control up to 252
devices. Model FC
I2017-U1 supports (1) one-to-eight
(8) ‘Class B’ circuits
or supports (1) one-to-four (4)
‘Class A’ circuits that can supervise and control up to
504 devices.
FCI2016-U1
(Periphery board for 252-pt.
Cerberus PRO Fire Safety system)
FCI2017-U1
(Periphery board for 504-pt.
Cerberus PRO Fire Safety system)
Degrade-mode functions
Four (4) configurable relay outputs
Battery charger included
Auxiliary output
(24VDC, nominal; 1.5 Amps)
UL 864 9
th
Edition Listed, ULC Listed;
FM, CSFM and NYC Fire Dept. Approved
Used with Cerberus PRO panels
Model FCI2016-U1 is used with Model FC922 panel
Model FCI2017-U1 is used with Model FC924 panel
Maximum 252 point device addresses per
integrated loop card
Up to 252 addresses are used with Model FCI2016-U1
Up to 504 addresses are used with Model FCI2017-U1
Model FCI2017-U1 has two (2) integrated loop cards
(Loop A / Loop B) with EMC surge protection for eight
(8) Style 4, or four (4) Style 6 / 7 loops
Model FCI2016-U1 has one (1) integrated loop card
(Loop A / Loop B) with EMC sur
g
e protection for four (4)
Style 4, or two (2) Style 6 / 7 loops
NAC connection for one (1) Class A or two (2)
‘Class B’ functions
3 Amps max. for NAC for synchronization and alarms
Two (2) plugs for optional extensions
Leased line / city-tie module
Notification Appliance Circuit (NAC) Expansion Module or
Releasing Module
Additional peripheral-data bus connection for
LED or digital alarm communication transmitter
(DACT) modules
Field-wiring configuration via removable
terminal blocks