Data Sheet for Product

Periphery Boards
6802
s Industry, Inc.
Building Technologies Division
s
Data Sheet
Fire Safety & Security Products
Desigo
TM
Fire Safety System
System Periphery Boards
Models FCI2016-U1 and FCI2017-U1
Product Overview Specifications
The periphery boards (Models FCI2016-U1 and
FCI2017-U1) are the main components for operation
of the Desigo panels (Models FC2025 and FC2050).
Each module, which is FM (
#
3010); CSFM (
#
7165-
0067:0259) and FDNY (
#
6104) Approved, operates
and monitors input-device identity; as well as
controls the signaling-line circuits that
communicate with smoke detectors and other field
devices (i.e. - FDnet). All functions are supported by
the power supplies of either Model FP2011-U1 or
Model FP2012-U1.
Model FP2011-U1 provides regulated 24VDC,
nominal, 6 amps (max), while Model FP2012-U1
offers regulated 24VDC, nominal, 11.5 amps (max) to
the Models FC2025 and FC2050 Desigo systems.
Each periphery board is equipped with two (2)
programmable ‘Class B’ (Style Y) or ‘one (1) Class A’
(Style Z) NAC, providing 24VDC, nominal @ up to 3A per
circuit of audible / visual notification appliances.
Models FC
I2016-U1/ FCI2017-U1 have integrated
FDNet loop circuit with built-in EM
I surge protection,
which allows automatic devices to be installed and
configured for ‘Class B’ or ‘Class A’ circuit operation.
Model FC
I2016-U1 supports (1) one-to-four (4)
‘Class B’ circuits
or supports (1) one-to-two (2)
‘Class A’ circuits that can supervise and control up to
252 devices. Model FC
I2017-U1 supports (1) one-
to-eight (8) ‘Class B’ circuits
or supports (1) one-to-
four (4) ‘Class A’ circuits that can supervise and
control up to 504 devices.
Used with Desigo panels
Model FCI2016-U1 is used with Model FC2025 panel
Model FCI2017-U1 is used with Model FC2050 panel
Maximum 252 point device addresses per
integrated loop card
Up to 252 addresses are used with Model FCI2016-U1
Up to 504 addresses are used with Model FCI2017-U1
Model FCI2017-U1 has two (2) integrated loop cards
(Loop A / Loop B) with EMC surge protection for eight
(8) Style 4, or four (4) Style 6 / 7 loops
Model FCI2016-U1 has one (1) integrated loop card
(Loop A / Loop B) with EMC surge protection for four
(4) Style 4, or two (2) Style 6 / 7 loops
NAC connection for one (1) Class A or two (2)
‘Class B’ functions
3 Amp, max. per NAC for synchronization and alarms
Two (2) plugs for optional extensions
Leased line / city-tie module
Notification Appliance Circuit (NAC) Expansion Module
or Releasing Module
Additional peripheral-data bus connection for
LED or d
igital alarm communication transmitter
(DACT) modules
Field-wiring connection via removable
terminal blocks
ARCHITECT AND ENGINEER SPECIFICATIONS
Degrade-mode functions
Four (4) configurable relay outputs
Battery charger included
Auxiliary output
(24VDC, nominal; 1.5 Amps)
UL 864 9
th
Edition Listed, ULC Listed;
FM, CSFM and NYC Fire Department Approved
FC
I2016-U1
(Periphery board for 252-pt.
Desi
g
oFire Safet
y
s
y
stem
)
FCI2017-U1
(Periphery board for 504-pt.
Desigo Fire Safety system)

Summary of content (4 pages)