Cerberus™ PRO Fire control panel FC722 Compact, pre-assembled fire control panel with integrated, user-friendly operating unit.
Features and Functions System The diagrams have been simplified and do not include additional network hardware or security components. Permissible applications are described in the A6V101039439 Network Security Guidelines document. Contact your Siemens IT security expert for more information.
1 Remote access with Cerberus-Remote 2 FS cloud applications 3 Customer network 4 Management platform 5 Remote access to management platform 6 Remote access with Cerberus Mobile 7 Router + firewall + virtual private network 8 Fire damper with actuator Transmission of a fault signal Transmission of an alarm signal You will find a detailed labeled version of the diagram above along with further information in the A6V10332842 planning guide, see chapter 'Product documentation'.
Networking of fire control panels The diagrams have been simplified and do not include additional network hardware or security components. Permissible applications are described in the A6V101039439 Network Security Guidelines document. Contact your Siemens IT security expert for more information. Up to 32 control panels and terminals can be linked to form one C-WEB network. If the CWEB network is connected to a danger management system via BACnet, up to 16 control panels and terminals can be networked.
An optical C-WEB/LAN network allows up to 14 sub-nets with up to 16 stations to be operated in one network. A maximum of 64 stations is supported in total.
Control panels General features and functions ● Fast Ethernet interface for a heterogeneous network ● Process signals from Cerberus PRO ● Siemens danger management system can be connected ● Slots for RS232 and RS485 serial interfaces ● Floor repeater devices, alarm devices, and mimic displays on the C-NET detector line ● All detector lines are monitored for ground faults.
FC722-YZ Housing (Standard) Detector line (C-NET) ● 252 addresses ● 2 loops/4 stubs Properties ● Operating unit (+LED indicator) ● 70 W power supply ● Max. battery capacity 12 Ah Options of the operating unit ● Key switch (Kaba) FTO2005-C1 ● Key switch (nordic) FTO2006-B1 FC722-ZA Housing (Comfort) Detector line (C-NET) ● 252 addresses ● 2 loops/4 stubs Properties ● Operating unit ● Operating add-on (empty) ● 150 W power supply ● Max.
Extensions You will find information on the integrated extinguishing system and the individual extinguishing components that are available in a separate data sheet with the document ID 'A6V10880701'. FCM7213-Y3 Operating add-on (2xLED indicator) ● FCM7214-Y3 Operating add-on (4xLED indicator) ● FH7202-Z3 Empty housing for free use 430 x 398 x183 mm E.g.
FTO2001-A1 Event printer ● ● ● DL3750+ Thermal printer for installation in operating units or operating add-ons Can be controlled via the RS232 module FCA2001-A1 (order separately) Logs all important events, such as alarms, faults, isolations, and test functions Matrix printer (external) ● ● ● ● External matrix printer recommended by Siemens Supports monitoring for printing faults Can be controlled via the RS232 module FCA2001-A1 (order separately) Can be controlled via Ethernet via the print server PS
Design Function elements Operating unit The following elements are available on the operating unit: ● CPU module and electronics ● Ethernet connection ● Slots for RS232 and RS485 modules ● Space for 'Kaba' or 'nordic' key switch ● Space for event printer (depending on version) Periphery board The following elements are available on the periphery board: ● Connection terminals for: – C-NET lines – Remote transmission (alarm, fault) – Horn output – Configurable control inputs and outputs – Monitored alarm and
Setup FC722 inside housing (Standard) FC722 Standard Building Technologies Fire Safety 11 A6V10206525_k_en_-2019-02-08
Position Designation Type Comment Items 1-5: Basic equipment Basic equipment 1 Housing (Standard) FH7202-Z3 2 Periphery board (2-loop) FCI2002-A1 3 Power supply (70 W) FP2015-A1 4 Mains terminals on TS35 DIN rail - Space for socket, relay modules, etc.
FC722 inside housing (Comfort) FC722 Comfort Building Technologies Fire Safety 13 A6V10206525_k_en_-2019-02-08
Position Designation Type Comment Items 1-5: Basic equipment Basic equipment 1 Housing (Comfort) FH7203-Z3 2 Periphery board (2-loop) FCI2002-A1 3 Power supply (SV 24 V-150 W) V24230-Z6-A5 4 Mains terminals on TS35 DIN rail - Space for socket, relay modules, etc.
Type Overview Housing (Standard) Type Order number Housing (Comfort) FC722-ZZ FC722-YZ FC722-ZA FC722-ZE S54400-C29-A5 S54400-C29-A4 S54400-C29-A2 S54400-C29-A1 252 Number of CNET addresses Number of lines: Loops (with loop extension) or 2 (4) Stubs (with loop extension) 4 (8) Power supply 70 W 150 W Battery size 12 Ah 25 Ah Indicator groups with one red/green + one yellow LED each Building Technologies Fire Safety - 24 - 48 15 A6V10206525_k_en_-2019-02-08
Details for ordering Control panels Type Designation Weight Order number FC722-ZA Fire control panel (2-loop) 14.958 kg S54400-C29-A2 FC722-ZE Fire control panel (2-loop) 15.207 kg S54400-C29-A1 FC722-ZZ Fire control panel (2-loop) 8.576 kg S54400-C29-A5 FC722-YZ Fire control panel (2-loop) 8.696 kg S54400-C29-A4 Type Designation Weight Order number FCA2001-A1 RS232 module (isolated) 0.033 kg A5Q00005327 FCA2002-A1 RS485 module (isolated) 0.
Auxiliary power supply Type Designation Weight Order number FP2004-A1 1.286 kg Power supply kit (150 W, A) for EN-compliant installation in empty housing A5Q00020825 FP2005-A1 Power supply kit (150 W, B) for extension 1.181 kg A5Q00018779 FP2015-A1 Power supply (70 W) for ENcompliant installation in empty housing 1.300 kg S54400-B121-A1 FP120-Z1 Power supply kit A 70 W 3.
Product documentation Title Document ID System documentation System description A6V10210355 Product data A6V10210368 Planning A6V10210362 Mounting/Installation A6V10210390 Data sheets FC721 - fire control panel A6V10203220 FC722 - fire control panel A6V10206525 FC723 - fire control panel for modernization A6V10379246 FC724 - fire control panel A6V10207176 FC726 - fire control panel (modular) A6V10263277 FT724 - fire terminal A6V10207898 Fire detection system with integrated single-sect
Technical data FC722 in the housing (Standard) Supply Mains voltage AC 97…127 V / AC 196…253 V Power supply 70 W Operating voltage DC 20.5…28.6 V Operating current Max. 2.5 A Battery capacity 2x 12 V, 7…12 Ah Battery monitoring Yes Network monitoring Yes Inputs / outputs Connectable detector series Cerberus PRO (C-NET) Number of addresses Max.
FC722 in the housing (Standard) Mechanical data Dimensions (W x H x D): ● Without cover cap 430 x 398 x 160 mm ● With cover cap 430 x 398 x 183 mm Protection category (IEC 60529) IP30 Color: ● Housing ~RAL 7035 light gray ● Cover cap ~RAL 000 50 00 Approvals 20 Building Technologies Fire Safety VdS G209076 LPCB 126bn/06 FM 3051081 A6V10206525_k_en_-2019-02-08
FC722 in the housing (Comfort) Supply Mains voltage AC 115 / 230 V +10/-15 % Power supply 150 W Operating voltage DC 21…28.4 V Operating current Max. 5 A Battery capacity 2x 12 V, 25 Ah Battery monitoring Yes Network monitoring Yes Inputs / outputs Connectable detector series Cerberus PRO (C-NET) Number of addresses Max.
FC722 in the housing (Comfort) Mechanical data Dimensions (W x H x D): ● Without cover cap 430 x 796 x 160 mm ● With cover cap 430 x 796 x 183 mm Protection category (IEC 60529) IP30 Color: ● Housing ~RAL 7035 light gray ● Cover cap ~RAL 000 50 00 Approvals 09 VdS G209076 LPCB 126bn/06 FM 3051081 DNV GL (marine) MEDB00003US Siemens Schweiz AG; Theilerstrasse 1a CH-6300 Zug Technical data: see doc. A6V10210355 Fc722 - Control and Indicating Equipment incl.