Cerberus™ PRO Fire detection system FS720 Modular, networkable fire detection system for detection, evaluation, sounding an alarm, and extinguishing in the event of a fire.
System System overview The diagrams have been simplified and do not include additional network hardware or security components. Permissible applications are described in the A6V101039439 Network Security Guidelines document. Contact your Siemens IT security expert for more information. Fig.
1 Remote access with Cerberus-Remote 2 FS cloud applications 3 Customer network 4 Management platform 5 Remote access to management platform 6 Remote access with Cerberus Mobile 7 Router + firewall + virtual private network 8 Fire damper with actuator Transmission of a fault signal Transmission of an alarm signal You will find a detailed labeled version of the diagram above along with further information in the A6V10332842 planning guide, see chapter 'Product documentation'.
Features and Functions ● Control panel range with 5 types of station – Microprocessor-controlled fire detection system – Compact and modular fire control panels for between 252 and 1512 addresses – PC-based operation (Cerberus-Remote) via Fast Ethernet – Integrated BACnet interface – Free control logic ● – Phased evacuation C-WEB/SAFEDLINK networking – Redundant networking – Increased security thanks to degraded mode function – Fast data transfer of up to 315 kbit/s ● – Maximum of 32 stations Extended ne
Performance characteristics Optimum use of customer resources ● Individual control panels or an entire network can be operated from a customer PC using the 'Cerberus-Remote' visualization software ● Redundancy cabling replaced by fail-safe network nodes ● Floor repeater display and terminals operated on the C-NET detector line High system availability ● Remote access via GAP or Siemens Cloud ● Efficient troubleshooting thanks to remote transmission of diagnosis data ● Maximum reliability and secure detectio
Networking Networking of fire control panels The diagrams have been simplified and do not include additional network hardware or security components. Permissible applications are described in the A6V101039439 Network Security Guidelines document. Contact your Siemens IT security expert for more information. Up to 32 control panels and terminals can be linked to form one C-WEB network.
Fig. 3: Backbone 1 Remote access with Cerberus-Remote 2 FS cloud applications 3 Customer network 4 Management platform 5 Remote access to management platform 6 Remote access with Cerberus Mobile 7 Router + firewall + virtual private network Transmission of a fault signal Transmission of an alarm signal You will find a detailed labeled version of the diagram above along with further information in the A6V10332842 planning guide, see chapter 'Product documentation'.
Stations Cross-station features and functions ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● Fast Ethernet interface for a heterogeneous network Processes signals from the detector series Cerberus PRO FD720 as well as from earlier detector series Interface to Siemens danger management system Slots for RS232 and RS485 serial interfaces Floor repeater displays, terminals and alarm devices on the C-NET detector line with power supply via C-NET All detector lines are monitored for ground faults.
FC722-YZ Housing (Standard) Detector line (C-NET) ● 252 addresses ● 2 loops/4 stubs Properties ● Operating unit (+LED indicator) ● 70 W power supply ● Max. battery capacity 12 Ah Options of the operating unit ● Key switch (Kaba) FTO2005-C1 ● Key switch (nordic) FTO2006-B1 FC722-ZA Housing (Comfort) Detector line (C-NET) ● 252 addresses ● 2 loops / 4 stubs Properties ● Operating unit ● Operating add-on (empty) ● 150 W power supply ● Max.
FC723 FC723-ZA Housing (Comfort) C-NET detector line: ● 756 addresses ● 2 loops / 4 stubs ● Can be extended with 2 module bus cards Installable module bus cards (option): ● Line card (FDnet/C-NET) FCL2001-A1 or Line card (FDnet/C-NET, P) FCL2008-A1 ● Line card (SynoLOOP) FCL7201-Z3 ● I/O card (programmable) FCI2008-A1 ● I/O card (horn/monitored) FCI2009A1 ● I/O card (remote transmission) FCI2007-A1 Features: ● Operating unit ● Operating add-on (empty) ● Card cage (2 slots) ● 150 W power supply ● Max.
FC724 You will find information on the integrated extinguishing system and the individual extinguishing components that are available in a separate data sheet with the document ID 'A6V11480005'. FC724-ZA Housing (Comfort) Detector line (C-NET) ● 504 addresses ● 4 loops/8 stubs Properties ● Operating unit ● Operating add-on (empty) ● 150 W power supply ● Max.
FC726 FC726-ZA Housing (Large) C-NET detector line: ● Max. 1512 addresses ● 4 loops/8 stubs ● Can be extended up to 28 loops/56 stubs Extra module bus cards (option): ● Line card (FDnet/C-NET) FCL2001-A1 or Line card (FDnet/C-NET, P) FCL2008-A1 ● Line card (SynoLOOP) FCL7201-Z3 ● I/O card (programmable) FCI2008-A1 ● I/O card (horn/monitored) FCI2009A1 ● I/O card (remote transmission) FCI2007-A1 Features: ● Operating unit ● Operating add-on (empty) ● Card cage (5 slots) ● 150 W power supply ● Max.
FT724 ● ● ● ● ● ● FT724-ZZ Person Machine Interface that is used remotely from the control panel, which can be optionally provided with its own power supply Up to five fire terminals can be configured with system-wide visibility. The fire terminal has spaces for installing optional interfaces such as an RS232 or RS485, network modules (SAFEDLINK), and a key switch. Each fire terminal has an Ethernet connection.
Station application FC722 For smaller-scale applications, e.g., workshops or hotels. Also suitable for more comprehensive systems thanks to flexible networking options. Single-sector extinguishing applications can also be achieved with this station type. FC723 For medium-sized applications, e.g., for industrial plants, regional banks, or office complexes. As part of a modernization process, for a gradual and seamless transition from older systems to Cerberus PRO. FC724 For medium-sized applications, e.g.
Application matrix Use FC722 FC723 FC724 FC726 FT724 Smaller applications, such as workshops or hotels ● ○ ● ○ ‒ Medium-sized applications, such as medium-sized industrial plants, regional banks, or medium-sized office blocks ○ ● ● ○ ‒ Large applications, such as industrial plants, large office blocks, or production halls ○ ○ ○ ● ‒ Large applications with high redundancy requirements, such as airports, power generation facilities, and shopping malls ‒ ‒ ‒ ○ ‒ Integrable extingu
Type Overview Fire control panels You will find detailed information on the available control panel types and the available variants in the separate data sheet for the respective control panel type and in the system documentation. You will find information on the document ID of the documents in section 'Product documentation [▶ 24]'. FC722 FC722 FC723 FC724 FC726 Standard Comfort Comfort Comfort Large Power supply 70 W 150 W 150 W 150 W 150 W Max.
FC722 FC722 FC723 FC724 FC726 Integrated outputs for alarm and control: ● RT alarm relay 1 1 1 1 ● RT fault relay 1 1 1 1 ● Monitored alarm output 1 1 1 1 ● Monitored fault output 1 1 1 1 1/4 1/8 2/8 2/8 8 8 12 12 Horn output, monitored (with sounder module) Configurable inputs/outputs 24 V Dimensions With cover cap/door 430 x 398 x 103 mm 430 x 796 x 188 mm 430 x 796 x 188 mm 430 x 796 x 188 mm 430 x 796 x 288 mm Without cover cap 430 x 398 x 80 m 430 x 796 x 160
Fire terminals You will find detailed information on the available terminal types and the available variants in the separate data sheet for the respective terminal type and in the system documentation. You will find information on the document ID of the documents in section 'Product documentation [▶ 24]'.
FT724 Time functions Freely configurable, time-dependent controls with optional weekly switching programs. In the event of site testing or if detector zones are isolated, timeout functions ensure that these detector zones get reactivated. Event memory Up to 13000 events can be called up for each station based on various criteria. Ground fault monitoring All the outgoing detector lines running out from the control panels are monitored for ground faults.
Device combinations Hardware extensions You will find detailed information on the hardware extensions and compatibilities in the separate data sheet for the respective control panel or terminal type and in the system documentation. You will find information on the document ID of the documents in section 'Product documentation [▶ 24]'.
● Extension possible ‒ Extension not possible 1) Only possible with a periphery board (2 loops) FCI2002-A1 or a periphery board (4 loops) FCI2004-A1. 2) Only possible with a periphery board (2 loops, P) FCI2023-A1 or a periphery board (4 loops, P) FCI2024-A1. 3) Installation is only possible if there is sufficient space in the housing. Line devices Fire detector ● ● ● ● Fire detectors with the latest generation of evaluation algorithms. Signals are processed using ASAtechnologyTM.
Sounders and sounder bases (sounders, sounder beacons, voice sounders) ● ● ● ● ● ● ● Operation of the sounders and sounder bases on the C-NET detector line. Supply and communication via C-NET No costly additional cabling required Meets the requirements of the EN 54-3 standard Max.
Floor repeater terminal and floor repeater display ● ● ● ● ● The floor repeater terminal FT2010 and the floor repeater display FT2011 are operated directly on the C-NET detector line. The floor repeater display FT2011 displays messages and events from selected areas of the fire detection system. The floor repeater terminal FT2010 displays messages and events from selected areas of the fire detection system and also enables operation. The responsible customer personnel (e.g.
Product documentation Title Document ID System documentation System description A6V10210355 Product data A6V10210368 Planning A6V10210362 Mounting/Installation A6V10210390 Data sheets FC721 - fire control panel A6V10203220 FC722 - fire control panel A6V10206525 FC723 - fire control panel for modernization A6V10379246 FC724 - fire control panel A6V10207176 FC726 - fire control panel (modular) A6V10263277 FT724 - fire terminal A6V10207898 Fire detection system with integrated single-sect
Notes Safety CAUTION National safety regulations Failure to comply with national safety regulations may result in personal injury and property damage. ● Observe national provisions and comply with the appropriate safety regulations. Disposal The device is considered an electronic device for disposal in accordance with European Directive and may not be disposed of as domestic waste. ● Use only designated channels for disposing the devices.
Issued by Siemens Switzerland Ltd Smart Infrastructure Global Headquarters Theilerstrasse 1a CH-6300 Zug +41 58 724 2424 www.siemens.com/buildingtechnologies Document ID A6V10227649_g_en_-- Edition 2021-10-22 © Siemens Switzerland Ltd, 2007 Technical specifications and availability subject to change without notice.