SB Encased Systems Breakers, Trip Units and Accessories Selection and Application Guide October 1, 1999
Table of Contents General Information 2-3 Description Stationary and Moveable Drawout Elements 4 How to Order SB Encased Systems Breakers 5 Frames 6 SB Circuit Breaker Frames 6 SBA Alternate Interrupting Rating 6 SBS Standard Interrupting Rating 6 SBH High Interrupting Rating 6 Drawout Breaker Elements 6 Non-Automatic Switches 6 SBN Standard Withstand Rating 6 Drawout Switch Elements 6 Ratings, Stationary Drawouts and Power Connectors 7-8 UL 489 Ratings 7 EC 947-2 Ratings 7 Stationary Drawout Element (SBA,
General Information NOTE: For more information on other standard and optional trip unit features, see Siemens Electronic Trip Units for SB Encased Systems Breakers Information and Instruction Guide Bulletin IPIM-2203B and the Sentron Systems Breaker Energy Communicating Trip Unit Information and Instruction Guide Bulletin IPIM-2208A. This patented construction provides a higher interrupting capacity within a smaller housing than can be achieved by more conventional construction.
General Information Compact Size For space-limited installations, the 1200A and 2000A frames offer a common width of 15 1/2 inches, a common depth of only 12 1/8 inches, a common mounting footprint, and common bus center lines. This compact, shallow depth (even with drawout breakers) permits stacking of six 800A or 1200A breakers or four 2000A breakers in a standard switchboard. This packaging is made possible by the insulated-encased construction and thermal performance of the SB breaker.
Description Stationary and Moveable Drawout Elements Simplified Minimum Depth Drawout Mechanism The two elements of a drawout constructed SB Encased Systems Breaker are the stationary drawout element and the moveable drawout element. The stationary drawout element mounts from the front or bottom into a standard switchboard. Bottom mounting flanges are provided for optional mounting arrangements. The moveable drawout element mounts onto the stationary drawout element’s two extension rails.
How to Order SB Encased Systems Breakers Description 1. Frames Select basic breaker frame catalog number from Table A. 2. Drawout Mechanisms Select the proper stationary drawout element (cradle) for use with breaker frame selected in Step 1. Stationary drawout mechanism is not required if fixed mounted breaker was selected in Step 1. Select from Table B. Example Catalog Number SBS2016DV SBS20DFV 3.
Frames Table A: Circuit Breaker Frames SBA Alternate Interrupting Rating 1 Breaker Frame Frame 4 Max Ampere 5 Size (A) Rating (A) 1200 400 1200 800 1200 1200 2000 1200 2000 1600 2000 2000 Fixed Mounted Breaker Catalog Number SBA0804F SBA0808F SBA1212F SBA2012F SBA2016F SBA2020F Drawout Breaker Element 2 Vertical Bus 3 Catalog Number SBA0804DV SBA0808DV SBA1212DV SBA2012DV SBA2016DV SBA2020DV Horizontal Bus 3 Catalog Number SBA0804DH SBA0808DH SBA1212DH SBA2012DH SBA2016DH SBA2020DH SBS0804F SBS0808F SBS
Ratings, Stationary Drawouts and Power Connectors UL Symmetrical RMS Amperes Interrupting Ratings (kA) Optional Ratings and Application Voltages Alternate A. I. R. (kA): Blue Label “SBA” @ 240V AC @ 480V AC @ 600V AC Standard A. I. R. (kA): Black Label “SBS” @ 240V AC @ 480V AC @ 600V AC High A. I. R. (kA): Red Label “SBH” @ 240V AC @ 480V AC @ 600V AC Short Time Rating 1 (kA), T = 0.5 Sec.
Ratings, Stationary Drawouts and Power Connectors Table C: Bus Connectors and Pressure Wire Connectors T-Connectors 1 For rear bus connected fixed mounted breakers, two connectors are required per pole for connecting bus bars to breaker stabs. T-connectors are rotatable 90 degrees for flexibility of bus connection on 1200 and 2000 ampere frames only.
SB-EC Trip Units Two types of interchangeable trip units for the SB Encased Systems Breakers are available. The basic type “TL” Trip Unit features a full range of industry standard protective settings.
10 Front Panel Menu Structure Alarms Settings ALARMS ➡ OVER CURRENT GND OVER CURRENT OVER AMP DEMAND TOTAL HARMONICS OVER KW OVER KW DEMAND OVER KVAR OVER KVA UNDER PF LAGGING OVER PF LEADING Configuration Settings SYSTEM CONFIG ➡ VIEW CONFIG FREQUENCY WIRING PT RATING SHORT CIRCUIT PROT EXT NEUTRAL SENSOR TIME AND DATE LCD CONTRAST BREAKER S/N Relays Settings Demand Data Metering Data METERING MENU ➡ METERED DATA DEMAND CONFIG RESET METER DATA PROTECTIVE RELAYS ➡ NEUT.
SB-EC Trip Unit Accessories Required SB-EC Trip Unit Accessories Table F: SB-EC External Power Supply Catalog Number SBEPS SBEPS24 Input Voltage 120 VAC 24 VDC and 48 VDC Note: One power supply can power up to three trip units. Max wire length between trip unit and power supply is 50 feet.
Type “TL”Trip Units Table L: Type “TL” Trip Units Trip Unit Function Adjustable Continuous Current Adjustable Long Time Delay Adjustable Short Time Pickup Adjustable Short Time Delay (l 2t) Adjustable Short Time Delay (Fixed) Adjustable Instantaneous Pickup Adjustable Ground Fault Pickup 3 Adjustable Ground Fault Time Delay (l 2t) 3 Adjustable Ground Fault Time Delay (Fixed) 3 Fixed Instantaneous Override Internal Watchdog Integral Testing Functions Local Trip Indication: Overload Short Time Short Circuit G
Type“TL”Trip Unit Accessories Plug-in Display Module The Plug-in Display Module can be added to the type “TL” electronic trip unit only to provide digital current readout of each phase in amperes. The module also provides load monitor set points at 60, 70, 80, 90 and 100% of the continuous ampere setting. Also provided are two ampere demand functions. May be used in conjunction with the Alarm Relay on page 16 or the Bell Alarm and Alarm Relay Combination Module on page 15 for remote alarming.
Internal and External Accessories Table N: Electrical Operators Electric Operators function to automatically charge the SB breaker’s stored energy mechanism. Each operator includes a Remote Closing Solenoid for closing the breaker from a remote location and an electronic controller which provides anti-pump protection and remote charging capability and indication.
Internal and External Accessories Shunt Trips Allows the breaker to be opened from a remote location. Included is an auxiliary switch for remote indication of breaker “open” or “closed” status. UL listed for field installation.
Internal and External Accessories Alarm Relays The Alarm Relay provides 1 NO and NC (Form C) contact. When used with the “TL” Trip Unit Display Module or Ground Fault Monitor, the relay changes state when the current set-point is exceeded. When used with the SB-EC Trip Unit, the relay changes state whenever an alarm is active. If the current falls below the set point or the alarm is no longer active, the contact returns to its normal state.
Internal and External Accessories Breaker Closing Blocking Devices Covers the Close pushbutton on the breaker escutcheon to prevent closing breaker manually without special tool. UL listed for field installation. Description Breaker Closing Blocking Device Catalog Number SBBD Key is installed in the central escutcheon.
Internal and External Accessories Mechanical Interlocks For Fixed Mounted Breaker Frame Sizes 1200 2000 3200 5000 Catalog Number SBMIF08 1 SBMIF20 1 SBMIF32 1 SBMIF40 1 1 Add “LI2” suffix for extended cable length. Mechanical Interlocks For Drawout Mounted Breaker Frame Size 1200 2000 3200 5000 Catalog Number SBMID08 2 SBMID20 2 SBMID32 2 SBMID40 2 2 Add “LI2” suffix for extended cable length.
External Accessories and ACCESS™ Communications Type “TL” Trip Unit Auxiliary Power Module A device used to bring power into the SB breaker type “TL” electronic trip unit only so that the trip unit can be tested via the integral testing functions when the breaker is withdrawn from the Stationery Drawout Element. It is required to trip the breaker’s shunt trip when no primary power is applied to the breaker or when “bench testing” the electronic trip unit.
External Accessories and ACCESS™ Communications System DANGER Hazardous voltage. Will cause death or serious injury. Turn off and lock out all power supplying the device prior to cover(s) removal or while cover(s) are removed and when installing any internal or external accessory. Replace the cover(s) and shield(s) before power supplying this device is turned on.
External Accessories ACCESS™ Communications System The MTCSB cable is used to connect an MTA or MTZ to an EPSB expansion plug via the SB breaker secondary terminal block or sliding disconnect. A. SB Breaker Zone Selective Interlocking (only) 1. All SB Breaker Trip Units Installation: 1. When the factory-installed ZSI option is present, the EPSB expansion plug is already wired to the breaker and secondary control terminals.
Outline Dimension Drawing 1200A Stationary Drawout Element 21.82 9.56 5.82 2.75 2.94 2.38 .75 8.75 20.50 17.38 5.00 19.00 Front Cover 1.25 Lifting Points. Do Not Lift By Other Points 17.50 C L 18.50 Inside Cradle 5.00 .50 2X .54 4X Top Ø.228 Holes 4X Bottom 4X Top Ø.438 Optional Mounting Holes 4X Bottom Preferred Mounting Surface 26.46 See Detail A 15.86 15.37 Wire Path For Secondary Contacts 1.75 .85 2X 2.00 2X 1.00 2X 3.50 1.36 C L 2X 5.00 2X 3.62 4X Ø.
Outline Dimension Drawing 1200A Stationary Drawout Element 1.30 .44 3/8 -16 Bus Support Bolts Optional Rear Mounting Surface Detail A Scale 1/1 See Note 1 20.00 10.00 8.75 4X 1.00 12X Ø.281 Front Mtg. Holes Of Bus C L Stab 8.562 C L Of Bus Stab 2X 6.88 4X 5.50 2X .375 13.75 2X 1.00 4X 2.50 C L Provide Clearance Holes For #8 - 32 Screws When Using Rear Flange Mounting Surface.
Outline Dimension Drawing 1200A Moveable Drawout Element C L C L 2.87 2.84 2.87 2.84 4X .59 2X .44 4.59 4.56 1.74 C L C L 2.13 .20 4.59 4.56 3X Ø 1.25 .94 .94 Front View Front Panel Cutout Minimum Clearance (Escutcheon Dimensions) 20.50 Overall 10.25 6.88 13.
Outline Dimension Drawing 1200A Moveable Drawout Element 15.75 Breaker Fully Withdrawn 16.00 .75 1.45 Breaker Test Position Front Cover Location Shown Provides Minimum Clearance With Breaker 7.75 15.50 C L Top View 21.82 10.31 7.82 Minimum Clearance Required For Breaker Rotation R 11.52 10.54 58° C L 36° .
Outline Dimension Drawing 1200A Fixed-Mounted 15.50 C L Ø.34 Holes Typ. 5.00 5.00 1.00 Typ. See Detail A 3.37 1.13 11.13 11.38 11.63 12.13 Top View .09 2.50 2.
Outline Dimension Drawing 1200A Fixed-Mounted 5.00 5.00 R .125 Typ. C L 6X 1.32 .50 .66 1.13 Front View 2X 5.50 C L 9.75 C L 12.00 .37 .75 14.00 .87 7.375 .375 C L 14.75 4X Ø .44 Mounting Holes For 3/8 - 16x23/4 (Min.) screws, use 2 flat washers, 1 lock washer and nut. Torque to 15 ft. lbs. max. C L 2X 2.84 4X .59 2X .44 12X .38 X .43 Slot C L 4.56 1.74 C L 2.87 2.13 2.87 .20 4.56 3X Ø 1.25 2X .94 4.59 Front View (Escutcheon Dimensions) 1.75 Typ. C L .50 Typ. 4.59 90° Max. 11.
Outline Dimension Drawing 2000A Stationary Drawout Element 1.30 .44 3/8 -16 Bus Support Bolts Optional Rear Mounting Surface Detail A Scale 1/1 20.00 See Note 1 10.00 C L Of Bus Stab 8.75 8.562 Typically 16 places Ø .281 Front Mtg. Holes Of Bus C L Stab 4X 1.00 4X 8.50 4X 5.50 2X .375 2X 1.00 19.75 2X 2.50 2X 9.75 C L 28 Provide Clearance Holes For #8-32 Screws When Using Rear Flange Mounting Surface.
Outline Dimension Drawing 2000A Stationary Drawout Element 21.82 9.56 5.82 2.75 2.94 Front Cover .75 2.38 1.25 8.75 17.50 19.00 5.00 Lifting Points. Do Not Lift By Other Points. C L 17.38 18.50 Inside Cradle 20.50 5.00 .50 2X .54 4X Top Ø .228 Holes 4X Bottom 4X Top 4X Bottom Ø .438 Optional Mounting Holes Top View Preferred Mounting Surface 26.46 See Detail A (Next Page) 15.86 15.37 1.75 Wire Path For Secondary Contacts. .85 2X 4.00 2X .88 2X 7.50 8X Ø .438 C L 2X 3.62 1.36 2X 7.
Outline Dimension Drawing 2000A Moveable Drawout Element 15.75 Breaker Fully Withdrawn 16.00 .75 1.45 Breaker Test Position Front Cover Location Shown Provides Minimum Clearance With Breaker 7.75 15.50 C L Top View 21.82 10.31 Minimum clearance required for breaker rotation 7.82 R 13.50 12.14 58° C L .
Outline Dimension Drawing 2000A Moveable Drawout Element 31
Outline Dimension Drawing 2000A Fixed-Mounted 15.50 C L 7.75 5.00 .09 5.00 .75 Typ. See Detail A 2.76 2.375 3.37 1.13 Detail A 11.13 C L 11.38 2X 2.84 11.63 12.13 4X .59 2X .44 C L 2.13 C L 4.56 1.74 .20 4.56 2.87 2.87 3X Ø 1.25 2X .94 24 Ø .39 Holes 1.75 Typ. 4.59 1.75 C L .88 2X 7 .12 4.59 90° Max. C L Front Panel Cutout Minimum Clearance 2X 2.50 7.82 Handle Clearance Rotation 2.
Outline Dimension Drawing 3200A, 4000A, and 5000A Stationary Drawout Element C B A 16X Ø .281 Front Mtg. Holes 4X 15.00 35.00 4X 8.75 2X 17.50 4X 5.00 4X 4.00 4X 7.50 Rear View Stationary Drawout Element Rear View Dimensions Frame Size Location 3200 4000/5000 A B C 2X 8.75 2X 10.25 20.50 2X 12.75 2X 14.25 28.
Outline Dimension Drawing 3200A, 4000A, and 5000A Moveable Drawout Element 16.00 .75 14.73 Breaker Fully Withdrawn 1.61 Breaker Test Position A B .50 3200 Ampere Bus Configuration Top View Moveable Drawout Element Top View Dimensions Frame Size 23.28 Location 3200 4000/5000 A B 7.50 15.00 11.50 23.00 15.15 7.76 2X 3.
Outline Dimension Drawing 3200A, 4000A, and 5000A Moveable Drawout Element Of Breaker Of Breaker 8.28 2.87 8.28 2.87 5.71 5.71 Of Breaker 3.45 Of Breaker 3.45 Front Panel Cutout Minimum Clearance Optional Panel Cutout (For Trip Unit and Label Information) A Overall 2.84 2.84 4X .59 B 2X .44 4.56 1.74 2.13 17.50 .20 4.56 3X Ø 1.25 .94 35.00 Overall .94 Front View (Escutcheon Dimensions) Moveable Drawout Element Front View Dimensions Frame Size Location 3200A 4000/5000A A B 21.50 10.
Outline Dimension Drawing 3200A Fixed-Mounted 4.91 5.69 3.98 4.54 10.25 9.13 R .12 Typ. R .12 Typ. .75 14.00 Front View (Escutcheon Dimensions) 15.12 .25 1.00 Typ. 1.25 Typ. 1.12 .75 1.75 4.00 Typ. 1.87 16.75 8X Ø.56 .75 .75 1.75 5.00 Typ.
Outline Dimension Drawing 3200A Fixed-Mounted 15.50 5.00 5.00 .75 .63 11.13 11.38 11.63 12.13 12.75 Top View 14.12 10.00 5.00 2.75 Typ. 30X Ø .41 Holes 2.00 3.50 1.25 Typ. 27.50 1.75 20.50 22.10 15.25 1.75 2.00 6X Ø Mounting Holes For /8 -16 X 2.75 (Min.) Bolts. Use 2 Flat Washers, 1 Lockwasher and Nut. Torque to 15 ft-lbs Max. 3 .70 .37 3.75 Typ. 14.
Outline Dimension Drawing 4000A and 5000A Fixed-Mounted 8.91 5.68 R .12 Typ. 3.98 4.54 10.25 9.13 R .12 Typ. 3.50 16.50 Front View (Escutcheon Dimensions) 1.25 Typ. 5.00 26.00 2.75 22.50 3.50 1.75 1.00 3.25 Side View 38 .
Outline Dimension Drawing 4000A and 5000A Fixed-Mounted 23.50 20.00 12.50 5.00 .50 Typ. 1.50 Typ. .87 .63 11.13 11.38 11.63 12.13 12.75 Top View 21.25 15.00 7.50 4.00 30X Ø .41 Holes 2.00 2.75 1.75 3.50 3.00 11.00 20.50 22.50 27.50 3.00 4.75 5.00 .38 22.75 Front View 8X Ø .44 Mounting Holes For 3/8 -16 x 2 3/4 (Min.) Bolts. Use 2 Flat Washers, 1 Lockwasher and Nut. Torque to 15 lb. Max.
Internal Accessories Electric Motor Operator and Local Electric Close Remote Close + Control Power + NO – NC LEC (Local Electric Close) Switch COM Local Electric Close NO COM For 48VDC and 125VDC Only LOCAL ELECTRIC CLOSE Available As Factory Installed Option Only. Switch "B" NC NO COM Resistor NC REM. Close + Elec. Oper. + Relay Com Relay No Common Local Elec.
Electrical Schematics RT= Right Top Secondary Terminals on Breaker. Alarm Reset Switch Customer Supplied Electronic Bell Alarm Types SBBA and SB4BA + – Control Power TRIP ALARM 60VA Max. 1.25A Max. 150VDC/2000VAC Max. or + Control Power TRIP 4 12 16 20 24 32 36 3 7 11 15 19 23 27 31 35 2 8 6 10 14 18 22 26 28 30 34 1 5 9 13 17 21 25 29 33 – ALARM Customer Supplied 60VA Max. 1.25A Max.
Electrical Schematics Undervoltage Release Connection Monitored Source + – UVR+ UVR Coil UVR– DC Undervoltage Release External Connections Internal Breaker Connections DC Undervoltage Release Solenoid Schematic Monitored Source AC Undervoltage Release Schematic UVR Resistor If Needed UVR Internal Breaker Connections External Breaker Connections AC Undervoltage Release Solenoid Schematic 42 UVR Coil
Electrical Schematics Supplied by Customer Coil+ Shunt Trip Coil “B” Type Clearing Switch NC Coil - (Common) COM NO Supplied by Customer Remote Open-Closed Indication Shunt Trip Shunt Trip Schematic Auxiliary Switch 4 Auxiliary Switch 5 Note: Auxiliary Switch 6 must be omitted if either Electronic Alarm Switch or Local Load Monitor Relay is installed. Auxiliary Switch 6 Auxiliary Switch 1 Auxiliary Switch 2 Auxiliary Switch 3 Aux. 4 A Aux. 4 A Aux.
Electrical Schematics "A" "B" Phase Phase “N” Phase X1 + X2 – "C" Phase Trip Unit Neutral Sensor "N" Phase Voltage + Note: Trip Unit Plug Shown As Viewed From Front Of Breaker. Left Pole + Note: Electronic Alarm Switch, Local Load Monitor Relay, And Remote Indicator Panel Are Mutually Exclusive. No Combination Of These Devices Is Permitted. See Sheet 5 For Connection Of Electronic Alarm Switch And Local Load Monitor Relay.
SB Solenoid Coil Resistances SHUNT TRIP SOLENOID: SHUNT TRIP PLUNGER O.D. = 0.310 INCH +/- 5% @ 20 degrees C 12 VDC - 3.6 ohms 120 VAC - 79.6 ohms 24 VCD - 14.2 ohms 240 VAC - 380 ohms 48 VDC - 55 ohms 480 VAC - 1163 ohms 125 VDC - 370 ohms SHUNT TRIP PLUNGER O.D. = 0.437 INCH +/- 10% @ 20 degrees C 12 VDC - 4.
Insulated Case Circuit Breakers Guide Form Specification SPECIFICATIONS: 1.01 STANDARDS A. The insulated case circuit breakers and all components shall be designed, manufactured and tested in accordance with the latest applicable standards, including the following: 1. Underwriters Laboratory 2. Canadian Standards Association 3. IEC947-2 Interrupting Ratings 4. NEMA 1.02 MANUFACTURERS A. Siemens Energy & Automation, Inc. B. _________________________ C. _________________________ 1.
Insulated Case Circuit Breakers Guide Form Specification H. The continuous ampere rating of the breaker shall be determined by a rating plug, which shall be inserted into the front panel of the trip unit. The trip units’ adjustable continuous ampere setting shall default to the trip unit’s minimum valve when the rating plug is removed. A rejection scheme shall prevent the installation of a rating plug into a trip unit for which it is not intended. I.
Insulated Case Circuit Breakers Guide Form Specification Z. When current harmonic analysis is specified, the trip unit shall be equipped to provide digital harmonic sampling capability up to the 19th harmonic. This data shall be capable of being viewed on the trip unit display or transmitted via communications. 1.04 INTERNAL ACCESSORIES A. Provide shunt trips, bell alarms, auxiliary switches, electric motor operator, undervoltage release, remote close solenoids, as shown on the contract drawings. B.
Siemens Energy & Automation, Inc. Distribution Products Division 3333 Old Milton Parkway Alpharetta, GA 30005 © Siemens Energy & Automation, Inc. Siemens is a registered trademark of Siemens AG. Specifications are subject to change without notice. For Nearest Sales Office TEL: 1.800.964.4114 WEB: www.sea.siemens.com/ sales/salesoffices.html For Product Information 1.800.964.4114 www.sea.siemens.com/dpd Order No. IPSA-2202C New 2M0100CP Printed in U.S.A.