Siemens Energy Manager / Heating Conroller RVP540 / RVP550 CE1N2488en
Building Technologies 04.11.2009
Norms and standards conformity to
EMC directive 2004/108/EC
Immunity and emissions EN 60730-1 (for use in industrial and
domestic environments)
Low voltage directive 2006/95/EC
Safety EN 60730-1 / EN 60730-2-9
Degree of protection IP40 to EN 60529 (when correctly
installed)
Safety class II to EN 60730
Output relays Rated voltage AC 24…230 V
Rated current range Q101 AC 0.02…2 (2) A
Rated current range Q102…Q110 AC 0.02…1 (1) A
Rated current ignition transformer max. 1 A for max. 30 s
Switch-on current ignition transformer max. 10 A for max. 10 ms
Perm. cable lengths To the sensors and to external contacts
Copper cable 0.6 mm
2
Copper cable 1.0 mm
2
Copper cable 1.5 mm
2
20 m
80 m
120 m
To the room unit (PPS)
Copper cable 0.25 mm
2
Copper cable 0.5 mm
2
25 m
50 m
Cable lengths for LPB copper cable
1.5 mm
2
, 2-wire, non-exchangeable
With controller bus power supply (per
controller)
With central bus power supply
Bus loading number
250 m
460 m
E = 3
Inputs Sensor input B101 NTC 575 (QAC32) or
Ni 1000 (QAC22)
Sensor inputs B102…B109
LG-Ni 1000 (QAE22) or
LG-Ni 1000 (QAP21.2) or
Pt 1000 (FGT-PT1000)
H1 as contact input
with safety extra low-voltage (SELV)
U
H1
= 12…24 V (contact open)
I
H1
= 2…5 mA (contact closed)
H1 as an analog input with
safety extra low-voltage (SELV)
U
in
= (DC 0…10) V
R
in
= 100 kΩ
max. rating DC 20 V; 20 mA
AC 230 V mains input (E1)
input signal range
AC 0…230 V (+10 %)
detection of passive input:
U
ein
AC 10 V or
input dead
detection of active input:
U
ein
AC 100 V
input resistance R
ein
> 100 kOhm
galvanic separation (optocoupler)
Outputs PWM output P1
signal frequency f = 2.4 kHz
output voltage
V
out_high
= +11.5 V…+13 V (no load)
V
out_low
< +0.5 V
output resistance R
out
= 1300 Ohm
degree of modulation g = 3 %…97 %
output is short-circuit-proof