User manual
Siemens AG Österreich 4/8 PS 307
ENGLISH
Installation and assembly:
To ensure adequate cooling, the device must be installed vertically, with the input and output terminals at the bottom.
Be sure to leave a minimum clearance of 40 mm (1.5 in.) above and below the device. The supply voltage (120/230 V
AC) must be connected in accordance with IEC 60364 and EN 50178. A protective device (fuse) and an isolating device
for disconnecting the power supply must be provided. For operation in hazardous applications it must be ensured that
the equipment is installed in a suitable enclosure in accordance with EN60079-15 (taking into account the ambient
operating conditions) and that precautions are taken against transient overvoltages that are 40% greater than the
rated value.
!
Danger:
The mains switch has to be switched off and prevented from being switched on again before installation or
maintenance. If this warning is ignored, contact with live parts or improper use can result in death or serious personal
injury.
Description and design:
The PS 307 24 V/2 A, 5 A, and 10 A power supplies are rail-mounted, built-in units. The relevant DIN/VDE regulations or
equivalent local regulations must be observed during installation.
Primary switched-mode power supply for mounting on an S7-300 rail. For hardwired connection to a 120 or 230 V,
50/60 Hz single-phase AC system.
Output voltage +24 V DC, potential-free, protected against short-circuit and open-circuit conditions.
Parallel connection of two similar devices to increase the power is permitted (provided the line impedances are equal to
the load).
Technical specifications:
Specifications valid for 230 V AC input voltage and +25°C ambient temperature, unless otherwise stated. Subject to
change without prior notice.
Type: 24 V / 2 A 24 V / 5 A 24 V / 10 A
Order no.: 6ES7307-1BA01-0AA0 6ES7307-1EA01-0AA0 6ES7307-1KA02-0AA0
Input:
Rated voltage V
in
: AC 120 / 230 V
Voltage range: AC 85…132 / 170…264 V, automatic range switching
Line frequency range: 47...63 Hz
Mains buffering: > 20 ms (@U
in
93 V / 187 V)
Rated current I
in
(at AC 120 / 230 V): 0.9 / 0.5 A 2.3 / 1.2 A 4.2 / 1.9 A
Recommended fuse in mains
supply line:
3 A Char. C
6 A Char. C
10 A Char. C
Output:
Rated voltage V
out
: DC 24 V
Residual ripple/spikes: < 40 / <100 mV
pp
Rated current I
out
: 2 A 5 A 10 A
Current limitation: Typ. 2.5 A Typ. 6.5 A Typ. 13 A
Efficiency at full load: Typ. 84% Typ. 86% Typ. 90%
Environmental conditions:
Transportation and storage
temperature: -40°C...+85°C
Ambient temperature during
operation: 0°C...+60°C
Degree of protection: IP20
Pollution degree: 2
Humidity rating: Climate category 3K3 acc. to EN 60721, relative humidity 5...95 %, non-
condensing
EMC interference emission: EN 61000-6-3
Limit acc. to EN 55022: Class B
EMC interference immunity: EN 61000-6-2, EN 61000-4-2/-3/-4/-5/-6/-11
Safety:
Protection class: I
Electrical isolation,
primary/secondary:
SELV output voltage acc. to EN 60950 and EN 50178, transformer acc. to EN
61558-2-17, protection against overvoltage in case of internal fault: V
out
< 33 V
Certificates:
CE CE marking acc. to 2004/108/EC and 2006/95/EC
UL cULus (UL508, CSA C22.2, No.142 - Listed, File E143289),
cULus (UL 1604, Class1, Div2 – Listed, File E330455)
FM FM (Class I, Zone 2, Group IIC, temperature class T4)
Approval for hazardous areas
(Directive 94/9/EC)
Conformity statement EN 60079-15: ATEX94/9/EC Cat.3; Eex, nA, II, T4 U
C-Tick AS/NZS 2064:1997