Datasheet

Stabilized Power Supplies
SITOP 6EP Power Supplies
DC-UPS uninterruptible power supplies
11/61
Siemens IC 10 · 2011
* You can order this quantity or a multiple thereof.
Illustrations are approximate
11
Overview
To combat prolonged mains failures the 24 V SITOP
power supply units can be upgraded into a DC-UPS
uninterruptible power supply.
SITOP offers two systems for this purpose:
Battery modules as energy stores which provide a buffer in the
hours range
Capacitors for 24 V buffering in the minutes range
The combination is used for example in machine-tool building, in
the textile industry, on all types of production lines and filling
plants, and in conjunction with 24 V industrial PCs. They prevent
the negative consequences which often result from mains
failures.
For the SIMATIC IPC this means that all running applications, in-
cluding the operating system, can be shut down under stabi-
lized conditions.
The DC-UPS 24 V uninterruptible power supply with battery
modules is comprised of DC-UPS modules with 6 A, 15 A or
40 A output current and the battery modules 1.2 Ah, 3.2 Ah, 7 Ah
and 12 Ah (containing lead rechargeable batteries with corro-
sion-resistant lead-calcium high-performance grid plates and
glass fiber fleece) and 2.5 Ah (containing "high-temperature
rechargeable batteries" type Reinblei).
Selection and ordering data
Battery modules as energy stores
For capacitors as energy stores see page 11/62.
Version Inputs Output Dimensions
(W × H × D)
DT Order No. Price
per PU
PU
(UNIT,
SET, M)
PS* PG
Rated
voltage
U
e Rated
Rated voltage
U
a Rated
Rated
current
I
a Rated
mm
DC UPS modules
6EP1 931-2
.C..
6EP1 931-2FC..
6 A 24 V DC
(22 ... 29 V)
24 V DC
(mains operation:
21.5 ... 28.5 V,
battery operation:
27.0 ... 18.5 V)
6 A 50 × 125 × 125 }
6EP1 931-2DC21 1 1 unit 585
With serial
interface
50 × 125 × 125 }
6EP1 931-2DC31 1 1 unit 585
With USB
interface
50 × 125 × 125 }
6EP1 931-2DC42 1 1 unit 585
15 A 24 V DC
(22 ... 29 V)
24 V DC
(mains operation:
21.5 ... 28.5 V,
battery operation:
27.0 V ... 18.5 V)
15 A 50 × 125 × 125 }
6EP1 931-2EC21 1 1 unit 585
With serial
interface
50 × 125 × 125 }
6EP1 931-2EC31 1 1 unit 585
With USB
interface
50 × 125 × 125 }
6EP1 931-2EC42 1 1 unit 585
40 A 24 V DC
(22 ... 29 V)
24 V DC
(mains operation:
21.5 ... 28.5 V,
battery operation:
27.0 ... 18.5 V)
40 A 102 x 125 x 125 }
6EP1 931-2FC21 1 1 unit 585
With USB
interface
102 x 125 x 125 }
6EP1 931-2FC42 1 1 unit 585
Version Charging
voltage at +25 °C
U
Charge
Output
Rated voltage
U
a Rated
Dimensions
(W × H × D)
DT Order No. Price
per PU
PU
(UNIT,
SET, M)
PS* PG
mm
Battery modules
For DC-UPS modules 6 A and 15 A
6EP1 935-6MC01
6EP1 935-6ME21
1.2 Ah 27.0 V DC 24 V DC
(end of charge
voltage: 27.0 V,
exhaustive discharge
protection: 18.5 V)
96 × 106 × 108 }
6EP1 935-6MC01 1 1 unit 585
2.5 Ah/
high tem-
perature
recharge-
able
battery
27.7 V DC 24 V DC
(end of charge
voltage: 27.7 V,
exhaustive discharge
protection: 18.5 V)
265 × 151 × 91 }
6EP1 935-6MD31 1 1 unit 585
3.2 Ah 27.0 V DC 24 V DC
(end of charge
voltage: 27.0 V,
exhaustive discharge
protection: 18.5 V)
190 × 151 × 82 }
6EP1 935-6MD11 1 1 unit 585
For DC-UPS modules 6 A to 40 A
7 Ah 27.0 V DC 24 V DC
(end of charge
voltage: 27.0 V,
exhaustive discharge
protection: 18.5 V)
186 x 168 x
121
}
6EP1 935-6ME21 1 1 unit 585
12 Ah 27.0 V DC 253 x 168 x
121
}
6EP1 935-6MF01 1 1 unit 585
IC10_11.book Seite 61 Donnerstag, 16. Dezember 2010 7:53 07
© Siemens AG 2010

Summary of content (1 pages)