Data Sheet

Interface types
RS 485
● Transmission rate, max.
12Mbit/s
● Cable length, max.
100m
Protocols
PROFIBUS DP master
Services
— PG/OP communication
Yes
— S7 routing
Yes
— Data record routing
Yes
— Isochronous mode
No
— Equidistance
No
— Number of DP slaves
125
— Activation/deactivation of DP slaves
Yes
PROFIBUS DP slave
● Transmission rate, max.
12Mbit/s
● automatic baud rate search
Yes
● Address area, max.
120
● User data per address area, max.
128byte
Services
— PG/OP communication
Yes; Only with active interface
— Routing
Yes; Only with active interface
— S7 communication
Yes; Only with active interface
— Direct data exchange (slave-to-slave
communication)
Yes; No subscriber possible - only passive publisher
— DPV1
Yes
Transfer memory
— Inputs
244byte
— Outputs
244byte
Interrupts/diagnostics/status information
Diagnostics function Yes
Diagnostics indication LED
● for module diagnostics
Yes; green/red DIAG LED
Potential separation
between backplane bus and interface Yes
Ambient conditions
Ambient temperature during operation
● horizontal installation, min.
-40°C; = Tmin (incl. condensation/frost); start-up @ -25 °C
● horizontal installation, max.
60°C; = Tmax
● vertical installation, min.
-40°C; = Tmin; Startup @ -25 °C
6AG1545-5DA00-2AB0 Subject to change without notice
Page 2/
4
09/16/2019 © Copyright Siemens