Data Sheet
Data sheet 6AG1431-0HH00-4AB0
SIPLUS S7-400 SM 431 16AI for medial exposure based on
6ES7431-0HH00-0AB0
Supply voltage
Load voltage L+
● Rated value (DC)
24V; Only required for supplying 2-wire transmitters
● Reverse polarity protection
Yes
Input current
from load voltage L+ (without load), max. 400mA; for 16 connected, fully controlled 2-wire transmitters
from backplane bus 5 V DC, max. 100mA
Power loss
Power loss, typ. 2W
Analog inputs
Number of analog inputs 16
● For voltage/current measurement
16
permissible input voltage for voltage input
(destruction limit), max.
20V; 20 V DC permanent, 75 V DC for max. 1 s (duty factor 1:20)
permissible input current for current input (destruction
limit), max.
40mA
6AG1431-0HH00-4AB0 Subject to change without notice