Data Sheet for Product

590 Series
Technical Instructions
Document No. 155-719
September 9, 2009
Differential Pressure Sensor
Sensor in Conduit Housing Sensor without
Conduit Housing
Siemens Industry, Inc.
Description
The 590 Series Differential Pressure Sensors obtain differential or gauge (static)
pressures and convert this pressure difference to a proportional electrical output. They
are offered with a 0 to 10 Vdc and 4 to 20 mA output.
Static accuracy is ±1% full scale in normal ambient temperature environments. The
units are temperature compensated to less than ±0.033% FS/°F of thermal error over
the temperature range of 0°F to 150°F (-19°C to 66°C).
Features
10 PSI proof pressure on all ranges
24 Vac excitation
0 to 10 Vdc analog input is compatible with all energy management systems
Fully protected against reverse wiring
1% accuracy improves variable air volume system performance
Optional accuracies as high as 0.25% FS
Meets
conformance standards
Applications
Heating, Ventilating and Air Conditioning (HVAC)
Energy management systems
Variable Air Volume (VAV) and fan control
Environmental pollution control
Static duct and clean room pressures
Oven pressurization and furnace draft controls