Predator Three Zone Loop Application Data Sheet Features Cost effective controller for zone level control of up to three individual rooms or zones. Support up to three Staefa 10K Thermistor room sensor inputs with bypass and setpoint provides optimal control for multiple zones. Expansion platform for picking up remote I/O reduces total installed cost. Four PID loops enable customized control that responds to local sensors and network inputs.
Predator Three Zone Loop Application Data Sheet Sequence of Operation The Three Zone application has been expanded to accept inputs from up to three Talon 10K Thermistor room temperature sensors while continuing to perform general-purpose loop control and I/O expansion routines similar to the standard Four Loop controller. Due to the application flexibility, the sequences are dependant upon the configuration of the I/O and conversion components.
Conversions Conversion components include those components that accept inputs, perform a calculation, then output the result to a PID or output within the application. The Three Zone application includes the following conversion types: Bypass Function: Monitors up to three room temperature sensors and outputs a signal when any of the sensors go to bypass mode. Function: Calculates the minimum, maximum or average value of up to four inputs.
Three Zone Loop Default Configuration By default, the Three Zone controller comes configured to operate a three RTS to valve application.
Occupancy Sensor Use an occupancy sensor as a physical input to function as an “occupancy” or “system on” signal, coordinating the action of the other devices. Variable Frequency Drive Monitoring and control of any directly connected VFD can be accomplished via the Predator. Document No.
Sample Applications Multiple VAV Pressure Dependent System A common air handler cools two VAV rooms: an open plan area with two room temperature sensors (RTS 1 and RTS 2), and a private office with one sensor (RTS 3). Three-position damper actuators in the duct are modulated to provide cool air and maintain the space temperature at the readings on the setpoint sliders. Damper 1 operates in the open plan area, and damper 2 operates in the private office.
Multiple VAV-Pressure Dependent Wiring Diagram Document No.
Multiple Room Temperature Sensor (RTS) to Valve Sample Application System Description An office space contains three zones that are heated using three hot water radiators with floating motor valve actuators. The controller operates the radiator valves to control the space temperature in the zones to the current space temperature setpoint. Multiple VAV-Pressure Dependent Wiring Diagram Document No.
Document No.
Wiring Diagram Three Zone Predator Wiring Base. Note: Route wiring from either the bottom opening when using a J-box or from the base sides as shown in the picture when flat or din rail mounting. The image above is for illustrative purposes only Wiring Recommendations • • • • IN and AO: 20-22 AWG DO: 18-22 AWG Power: 16-18 AWG LON Network: 22 AWG Level 4 Transformer Requirements • Type: Class 2, 24 VAC, 50/60Hz Document No.
Hardware Map Factory Settings The Predator Three Zone Loop controller is only available on the full-point platform. For more information concerning the various Predator hardware platforms, see the Predator Owners Manual.
Predator and Accessories Bill of Material Multiple VAV Pressure Dependent BOM Equipment Diagram. Multiple RTS to Valve BOM Equipment Diagram. Document No.
Tag Description A Predator Three Zone 6IN, 8DO, 3AO, 1RTS Predator Full Point Wiring Base B Predator Room Sensors: Sensing Only Override Setpoint Temperature Display Setpoint and Override Override and Temperature Display Setpoint and Temperature Display Setpoint, Override, and Temperature Display Predator Room Sensors without Logo’s: No Logo Sensing Only No Logo Setpoint No Logo Setpoint and Override No Logo Setpoint, Override, and Temperature Display C Predator Room Sensor 6-Conductor Plenum Rated Cable
Predator Three Zone Loop Configuration Properties Configuration Property Element Factory Value Description Programmatic LanguageName dependent Name ao1DisSource Analog Output 1 Disable Source ao2DisSource Analog Output 2 Disable Source ao3DisSource Analog Output 3 Disable Source Sets the disable function for the analog output. If the value from the disable source is equal to the disable value, the output works as if overriden to 0%.
Configuration Property Element Factory Value Description Programmatic LanguageName dependent Name ao1Source Analog Output 1 Source ao2Source Analog Output 2 Source ao3Source Analog Output 3 Source Defines the source of the input for the analog output. sourceType PID Selects the source of the input signal for the analog output. Enumeration: srcCstA sourceNum Default values differ by CP: Selects the input variable number. NOTE: if nciPct is used as the sourceType, sourceNum must be set to "1".
Configuration Property Element Factory Value Description Programmatic LanguageName dependent Name do1Cfg Digital Output 1 Configuration do2Cfg Digital Output 2 Configuration do3Cfg Digital Output 3 Configuration do4Cfg Digital Output 4 Configuration Defines how the digital output responds to its input signal. type Deadband Selects the manner in which the digital output (DO) uses the input. Deadband or PWM pWMMinPct 0.00% Defines the input for 0% duty cycle.
Configuration Property Element Factory Value Description Disable Source type None Selects the disable input source. Enumeration: disDlyA value False Selects the disable value. If source is bypass 1-3 or bypass function, then False=none in bypass and True=bypass If source is occupancy 1-3, then False=occupied and True=unoccupied If source is DI or DO, then False=off and True=on enableDelay 0 seconds Selects the delay time to release the disable function. 0 to 6553.
Configuration Property Element Factory Value Description Programmatic LanguageName dependent Name fnc1Cfg Function 1 Configuration Selects the function to be performed and defines the number of inputs to that component. functionType Minimum Type of function the component performs. Minimum, Maximum, or Average numInputs 2 The number of inputs to the Function component.
Configuration Property Element Factory Value Description Programmatic LanguageName dependent Name map1BrkIn Map 1 Input Breakpoint Defines the input temperature pr percent breakpoints for the Map component. Breakpoints must be used in consecutive order. For example, if you are using 2 breakpoints, you must use A and B. If you are using 3 breakpoints, you must use A, B and C, etc. tempA 32°F (0°C) Temperature breakpoint. -459.706°F to 621.788°F (-273.17°C to 327.
Configuration Property Element Factory Value Description Programmatic LanguageName dependent Name map1BrkOut Map 1 Output Breakpoint map1Cfg Map 1 Configuration Defines the output percent or temperature breakpoints for the Map component. Breakpoints must be used in consecutive order. For example, if you are using 2 breakpoints, you must use A and B. If you are using 3 breakpoints, you must use A, B and C. tempA 32°F (0°C) Temperature breakpoint. -459.706°F to 621.788°F (-273.17°C to 327.
Configuration Property Element Factory Value Description Programmatic LanguageName dependent Name map1Source Map 1 Source Select Defines the source of the input for Map 1. sourceType spaceTemp Defines the source of the input variable. Enumeration: srcSelMap sourceNum 0 Defines the input variable number.
Configuration Property Element Factory Value Description Programmatic LanguageName dependent Name mtr1Source Motor 1 Source mtr2Source Motor 2 Source Selects the input source for the 3-position floating motor sourceType Selects the input variable type. Enumeration: srcCstA mtr1Sourcemtr3Source:PID mtr4Source: nciPercent mtr3Source Motor 3 Source mtr4Source Motor 4 Source Default values differ by CP: sourceNum Default values differ by CP: Selects the input variable number.
Configuration Property Element Factory Value Description unoccupied If the network occupancy input is NUL, this value is used in its place. Used in conjunction with byass to determine the occupancy state. Valid selections: Occupied or Unoccupied (occupT ) Unit: SNVT_occupancy Programmatic LanguageName dependent Name occ1Default Spc Occ 1 Default occ2Default Spc Occ 2 Default occ3Default Spc Occ 3 Default pid1Cfg PID1 Configuration Configures PID 1 and 2.
Configuration Property Element Factory Value Description Programmatic LanguageName dependent Name pid3Cfg PID3 Configuration Configures PID 3 and 4. reverse pid4Cfg PID4 Configuration Default values differ by CP: pid3Cfg: True pid4Cfg: False Establishes the reverse direction for the PID. false for direct acing loop true for reverse acting loop unit Temperature Selects the units for the PID proportional gain setpoint offset and deadband, if used. Temperature or Percent outMinPct 0.
Configuration Property Element Factory Value Description Programmatic LanguageName dependent Name pid3CtrB PID 3 Temp/Pct Controller Defines the PID controller gain for PID 3 and PID 4. pbTemp pid4CtrB PID 4 Temp/Pct Controller Default values differ by CP: pid3CtrB: 10°C pid4CtrB: 0°C pbMult 0 Proportional bad if configured for percent in multiples of 100%. For example if proportional band desired is 250%, enter 2.5. range 0 to 16.
Configuration Property Element Factory Value Description Programmatic LanguageName dependent Name pid1PVSource PID 1 Process Variable Source pid2PVSource PID 2 Process Variable Source Selects the source of the PID process variable. Must be the same units as PIDSPSource within each PID. sourceType spaceTemp Selects the input variable type. Enumeration: srcSelPVA sourceNum Default values differ by CP: Selects the input variable number.
Configuration Property Element Factory Value Description Programmatic LanguageName dependent Name pid3SPSource PID 3 Setpoint Source pid4SPSource PID 4 Setpoint Source Selects the source and properties for the PID setpoint. Must be the same units as PIDPVSource within each PID. sourceType spaceSetpt Selects the input variable type. Enumeration: srcSelSPb sourceNum Default values differ by CP: Selects the input variable number.
Configuration Property Element Factory Value Description Programmatic LanguageName dependent Name tempSP1Limits Spc Temp Stpt 1 Limits Sets up the limits for the value read from the space temperature setpoint slide.* minTemp 66.2°F (19.0°C) The minimum value that is accepted from the space temperature setpoint slide*. 50.0 to 95.0°F (10.00 to 35.00°C) Type: SNVT_temp_p maxTemp 77.0°F (25.0°C) The maximum value that is accepted from the space temperature setpoint slide*. 50.0 to 95.0°F (10.0 to 35.