BACnet PTEC Controller Dual Duct 2 AVS - Slave Mode Controller, Application 6693 Application Note 140-1118 2014-08-22 Building Technologies
Table of Contents Overview ............................................................................................................................. 4 BACnet .............................................................................................................................. 4 Hardware Inputs .................................................................................................................. 5 Hardware Outputs .......................................................................
Overview BACnet Overview Generic Controller I/O Layout. See Wiring Diagram for application specific details. Application 6693 is the slave mode application for the Siemens BACnet PTEC Dual Duct 2 AVS Controller (550-497PA). Slave mode is the default application that displays when power is first applied to the controller. Slave mode provides no control.
Overview Hardware Inputs Hardware Inputs Analog Air velocity sensor Room temperature sensor Room temperature setpoint dial Auxiliary temperature sensor Spare Analog Input (AI 3/AI 4) Digital Night mode override Wall switch (DI 2) Spare digital input (DI 6) Hardware Outputs Analog Analog output (three) 0-10Vdc Digital Floating control actuator 1 (DO 1/DO 2) Floating control actuator 2 (DO 3/DO 4) Floating control actuator (DO 5/DO 6) Digital Output (DO 1 through DO 8) Using Auxiliary Points It is possib
Overview Room Unit Operation NOTE: If using either a motor or DOs as auxiliary points, be sure to set MTR SETUP to the correct value. If using a pair of DOs to control a motor, the DOs cannot be unbundled or commanded separately. Motor Enable/Reverse Values for MTR SETUP MTR SETUP Value a) Disabled Enabled Enabled and Reversed Motor 1 0 1 3 Motor 2 0 4 12 Motor 3 0 16 48 a) The values in this table are additive and must be added per the requirements of the job.
Overview PPCL STATUS – CO2 enable and supervision (from the room unit) for fail communications with a value of 4. When the analog room unit (Series 1000/2000) is used, default temperature sensing (0) from an analog room unit is enabled (relative humidity and CO2 sensing are not available and should not be selected). Thermistor Inputs Default for input is 10K. To enable 100K thermistor on input, see the following table for additive values of 8.
Application 6693 Point Database Application 6693 Point Database Object Type 1) Object Instance (Point Number) Object Name (Descriptor) Factory Default (SI Units) 2) Eng Units (SI Units) Range Active Text Inactive Text AO 1 CTLR ADDRESS 255 -- 0-255 -- -- AO 2 APPLICATION 6693 -- 0-32767 -- -- AI {04} ROOM TEMP 74.0 (23.44888) DEG F (DEG C) 48-111.75 -- -- AI {13} RM STPT DIAL 74.0 (23.44888) DEG F (DEG C) 48-111.75 -- -- AI {15} AUX TEMP AI5 74.0 (23.
Application 6693 Point Database Object Type 1) Object Instance (Point Number) Object Name (Descriptor) Factory Default (SI Units) 2) Eng Units (SI Units) Range Active Text Inactive Text AO 56 DPR1 ROT ANG 90 -- 0-255 -- -- AO 57 DPR2 ROT ANG 90 -- 0-255 -- -- AO 58 MTR SETUP 0 -- 0-255 -- -- AO 59 DO DIR. REV 0 -- 0-255 -- -- AO 60 DUCT AREA 2 1.0 (0.09292) SQ. FT (SQ M) 0-6.