CE Compliant Heat Pump Controller — Multi-Stage
Page 1 of 8
Product Description
These instructions explain how to field install or
replace a CE Compliant Heat Pump Controller —
Multi-Stage (for multiple compressor heat pump
applications).
Shipping carton includes a controller assembly
(controller board and cover), a mounting rail, and two
self-tapping screws.
For CE compliance, ferrite filter(s) and an alternate
room sensor cable must be used (see Product
Numbers).
NOTE: Keep the controller assembly in its static-proof
bag until installation.
Product Numbers
Product Description
550-505 Heat Pump Controller — Multi-Stage
588-100A 25-ft (7.6-m)
588-100B 50-ft (15.2-m)
588-100C
2-RJ11 room
temperature
sensor cable
100-ft (30.48-m)
550-705 clamp-on ferrite filter 10 pack
Caution Notation
CAUTION:
Equipment damage or loss of
data may occur if the user
does not follow procedure as
specified.
Prerequisites
Room temperature sensor installed (optional)
24 Vac Class 2 power source
Supply power to the unit is OFF
If required, controller enclosure installed
Required Tools
Electro-Static Discharge (ESD) wrist strap
Small flat-blade screwdriver
Medium flat-blade screwdriver
Medium-duty electric drill
1/4-inch (6.35 mm) hex nut bit
Portable Operator’s Terminal with Controller
Interface Software (CIS) Rev. 2.0 or higher
(controller replacement only)
Additional tools needed if not using self-tapping
option:
1/4-inch (6.35 mm) hex nut driver
1/8-inch (3 mm) bit
Expected Installation Time
New controller installation 10 min.
Replacement with removable terminal
blocks
6 min.
Replacement without removable
terminal blocks
16 min.
NOTE: You may require additional time for
database work at the field panel.
New Installation Instructions
1. Using the mounting rail as a template (Figure 1),
mark the screw holes where you will install the
controller assembly.
2. Do one of the following:
If using the self-tapping screws provided:
Using the drill and the hex nut bit, fasten the
mounting rail.
If not using the self-tapping screws: Drill
two 1/8-inch (3 mm) pilot holes, then fasten
the mounting rail with No. 6 or No. 8 screws.