User Manual
IO-Link
10.1 Configuring the IO-Link
SIRIUS ACT 3SU1 pushbuttons and signaling devices
System Manual, 02/2015, A5E03457306020A/RS-AB/002
209
10.1.3.3
Configuration
Configuring the IO-Link device with the S7-PCT port configuration tool
1. Start the
S7-PCT
port configuration tool.
2. Create a new project or open an existing project as described in the online help.
3. Select a bus category (PROFIBUS DP/PROFINET IO).
4. Select an IO-Link master.
5. Select the IO-Link device in the component catalog of the
S7-PCT
port configuration tool.
6. Drag the IO-Link device out of the component catalog to the required port of the IO-Link
master.
7. Load the configuration into the IO-Link master before parameterizing the IO-Link device.
8. Start by parameterizing the IO-Link device.
Additional information is available in the
S7-PCT
online help.
Note
To be able to access the IO-Link master or an IO-Link device online, communication
between the ET 200 and the higher-level controller must be active (BF LED on ET 200
interface module is off).
10.1.4
Acyclic data exchange with the IOL_CALL function block
For acyclic data exchange, the "IOL_Call" function block is available as a download for
controllers of the S7 families.
The block supports you in the following tasks:
● Parameterization of an IO-Link device during operation
● Executing IO-Link port functions
● Backing up/restoring IO-Link device parameters
● Backing up/restoring IO-Link master parameters
Requirements
● Install the "IOL_Call" function block.
You can download the IOL_Call function block and the description from the Internet
(https://support.industry.siemens.com/cs/ww/en/view/82981502).