Data Sheet

Data sheet 3RK1105-1AG04-2CA0
ASIsafe extended Safety monitor 1 F-RO 1 enabling
circuit IP20, with spring-type terminal removable
terminals Safe output relay Response time maximum 40
ms Monitor type 3, Version 3 Can be used up to
Category 4 (EN954-1) up to PL E (EN ISO 13849-1) up
to SIL 3 (IEC 61508)
General technical data:
Design of the product safety monitor, with expanded functionality
Protocol is supported AS-interface protocol Yes
Type 1 enabling circuit
Number of release circuits 1
Response time max. ms 40
Type of electrical connection of the inputs and
outputs
spring-loaded terminals
Rated operational current Ie
● AC-12, 50/60 Hz 250 V
A 3
● AC-15, 50/60 Hz
— 115 V
A 3
— 230 V
A 3
● DC-12 (DC-1) 24 V
A 3
● DC-13 (DC-11)
— 24 V
A 1
— 115 V
A 0.1
— 230 V
A 0.05
3RK1105-1AG04-2CA0 Subject to change without notice
Page 1/
3
09/13/2019 © Copyright Siemens

Summary of content (3 pages)