Commissioning
6.1 Operating via the handheld programmer
SITRANS LR250 (FOUNDATION FIELDBUS)
50 Operating Instructions, 01/2014, A5E32221411-AB
Units
Sensor measurement units.
Options
m, cm, mm, ft, in
Default: m
Operation
Operation
Description
NO SERVICE Measurement and associated loop current are not updated, and the device
defaults to Fail-safe mode
a)
.
LEVEL
*
Distance to material surface referenced from Low calibration point
SPACE
Distance to material surface referenced from High calibration point
DISTANCE
Distance to material surface referenced from Sensor reference point
a)
See Material Level (2.3.5.) for more detail.