Heat & Glo • SL-550 / 750 / 950TR-E • 2118-900 Rev. K • 9/0816
Figure 5.4
E. Vent Diagrams
Top Vent - Horizontal Termination
Venting with 1 elbow
H
1
V
1
V Minimum
H
1
Maximum
SL-550TR-E SL-750TR-E SL-950TR-E
90 Elbow 2 ft. 610 mm 2 ft. 610 mm 1 ft. 305 mm
1/2 ft. 152 mm 2 ft. 610 mm 2 ft. 610 mm 2 ft. 610 mm
1-1/2 ft. 457 mm 3 ft. 914 mm 3 ft. 914 mm 3 ft. 914 mm
2-1/2 ft. 762 mm 5 ft. 1.5 m 5 ft. 1.5 m 5 ft. 1.5 m
3-1/2 ft. 1.1 m 7 ft. 2.1 m 7 ft. 2.1 m 7 ft. 2.1 m
4-1/2 ft. 1.4 m 14 ft. 4.3 m 14 ft. 4.3 m 14 ft. 4.3 m
H MAX. =14 ft. (4.3 m)
V + H MAX. = 40 ft. (12.2 m)
Fire Risk. Explosion Risk.
Do NOT pack insulation or other combustibles between ceiling restops.
ALWAYS maintain speci ed clearances around venting and restop systems.
Install wall shield and ceiling restops as speci ed.
Failure to keep insulation or other material away from vent pipe may cause re.
WARNING
Note: Use SLP Series
components only.
Note: There MUST be a 25%
reduction in total H when using
ex vent except when using the
simple up and out installation
(see Figure 5.3).
Fire Risk.
• When using SLP-HRC-SS and SLP-HRC-ZC-SS
termination caps on top vented replaces, a one
foot minimum vertical vent section is required before
installing rst elbow.
WARNING
When using DVP-TB1 termination cap on top vented replaces,
a three foot minimum vertical vent section is required before
installing rst elbow.