Installation manual

16 R
EFERENCE
& I
NSTALLATION
M
ANUAL
All detection devices connected to the control panel, keypads and zone expansion modules must be assigned to a zone and that zone must be defined as
described in this section.
Figure 5-1: Zone Programming
5.1 Z
ONE
N
UMBERING
The Zone Numbering feature is used to individually assign each detection
device to any zone in the DigiplexNE system (see Figure 5-1). The Zone
Parameters define the type of zone, the zone's partition assignment and
how the control panel will react when an alarm occurs on that zone (see
section 5.3 to section 5.5).
To assign an addressable PIR or door contact with GuardWall
technology connected to the communication network, program the
modules serial number into the section corresponding to the desired
zone (i.e. program zone 34 in section [0034]).
To assign a detection device connected to a module or control panel's
hardwired input terminal, program the module's or control panel's serial
number and the input number where the device is connected into the
section corresponding to the desired zone. See the Module
Programming Guide for details of its input numbers (input numbers not
required for keypad zones).
If PGM1 is defined as a smoke detector input (see section
11.6), the control panel will recognize it as input # 255.
Figure 5-2: Zone Numbering
Press & hold the
[0]
key
Zone Definition
First Digit
Zone Partition
Assignment
Second Digit
Zone Options
Feature Select
Enter the 8-digit
[
SERIAL
NUMBER
]
of the
addressable detection device
or module that has a hardwire
device connected to it.
Enter the module's 3-digit
[
INPUT
NUMBER
]
where the
hardwire device is connected.
NOTE:
For addressable PIRs, door
contacts and keypads, no input # is
required
Key in the
[
INSTALLER
CODE
]
Zone Definitions
0- Disabled (Default)
8- 24Hr Gas
1- Entry Delay 1 9- 24Hr Heat
2- Entry Delay 2 A- 24Hr Water
3- Follow B- 24Hr Freeze
4- Instant C- Delayed 24Hr Fire
5- 24Hr Buzzer D- Standard 24Hr Fire
6- 24Hr Burglary E- Stay Delay 1
7- 24Hr Hold-up F- Stay Delay 2
Zone Partition Assignment
1- Zone Assigned to Partition 1 (Default)
2- Zone Assigned to Partition 2
3- Zone Assigned to Partition 3
4- Zone Assigned to Partition 4
5- Zone Assigned to Partition 5
6- Zone Assigned to Partition 6
7- Zone Assigned to Partition 7
8- Zone Assigned to Partition 8
Zone Options
[1] Auto Zone Shutdown
[2] Bypass Zone (Default)
[3] Stay Zone
[4] Force Zone
[5] [6] Zone Alarm Type
off off Audible Alarm (steady)
off on Audible Alarm (pulsed)
on off Silent Alarm
on on Generates only a report
[7] Intellizone
[8] Delay before transmission
Press
[
ENTER
]
Key in 4-digit
[
SECTION
]
Select
one only
Zone Parameters
Sections
[0101]
to
[0196]
represent
zones 1 to 96 respectively
Select
one only
Zone Numbering
Sections
[0001]
to
[0096]
represent
zones 1 to 96 respectively
Select one
or more
Input 2
Hardwired
Device B
Control Panel
SN#:020000A2
APR3-ZX8 Module
SN#: 34000041
Input 5
Detector A
SN#: 21000033
C
OMMUNICATION
N
ETWORK
Input Terminals
1 2 3 4 5 6 7 8
Detector A:
Hardwired Device A:
Hardwired Device B:
Hardwired Device C:
Zone#
1 =
2 =
3 =
4 =
Section#
[0001]
[0002]
[0003]
[0004]
Serial#
21000033
1A000252
020000A2
34000041
Input#
N/A
N/A
002
005
Keypad
SN#: 1A000252
Keypad Zone
Hardwired
Device C
Hardwired
Device A
Input Terminals
1 2 3 4 5 6 7 8