Datasheet

5
3-Phase AC Filters / DC Filters
FMAD
https://www.schurter.com /PG80
EMC Products
Derating Curves
Permissible Working Current as a Function of Ambient Temperature
Admissible operating current in %
of In
100
80
60
40
20
0
0 20 40 60 75 100
UL Listed
Ambient air temperature Ta °C
Attenuation Loss
- - - - 50 differential mode _____ 50 common mode
Industrial version
6A (FMAD-0924-0610) 8A (FMAD-0931-0810) 16A (FMAD-0931-1610)
16A (FMAD-0932-1610)
25A (FMAD-0932-2510)
36A (FMAD-0934-3610) 50A (FMAD-0934-5010) 64A (FMAD-0953-6410) 80A (FMAD-0937-8010)
110A (FMAD-0954-H110) 180A (FMAD-0955-H210) 250A FMAD-0956-H310 550A FMAD-09KQ-H650
All Variants
Bemessungsstrom @ Tu
40°C (75°C) [A]
Leakage Current [mA]
@ 440V, 60Hz 1)
Tripped Power Dissi-
pation [W]
Contact Resi
-
stance [m]
Weight
[kg]
Clamps [mm2] Housings Order Number
6 (4.8) 1.3 3.9 27 0.95 kg 4 24-4 FMAD-0924-0610
8 (5) 1.3 9 35 1.9 kg 4 31-4 FMAD-0931-0810
16 (9.5) 1.3 15.4 15 2.1 kg 4 31-4 FMAD-0931-1610
16 (9.5) 1.3 15.4 15 3.1 kg 4 32-4 FMAD-0932-1610
25 (13) 8.4 11.5 4.6 3.35 kg 6 32-8 FMAD-0932-2510
36 (19) 8.4 21 4 3.4 kg 10 34-4 FMAD-0934-3610
50 (32) 9.0 20 2 3.4 kg 10 34-4 FMAD-0934-5010
64 (34) 9.0 27 1.6 4.3 kg 25 53-4 FMAD-0953-6410
80 (43) 9.7 39 1.5 7.35 kg 25 37-4 FMAD-0937-8010
110 (66) 9.7 58 1.2 7.25 kg 50 54-4 FMAD-0954-H110
180 (95) 9.7 51 0.39 22 kg 95 55-4 FMAD-0955-H210
250 (120) 10.4 62.5 0.25 24.5 kg 240 56-4 FMAD-0956-H310