Datasheet

5
Power Entry Modules with Line Filter
DD12
https://www.schurter.com /PG06
EMC Products
Technical Data of Filter-Components
Rated Current [A] Filter-Type Inductance L1/
L2 [mH]
Inductance L3
[mH]
Capacitance CX
[nF]
Capacitance CY
[nF]
R [M]
1 Standard Version 2 x 10 - 100 2.2 1
2 Standard Version 2 x 4 - 100 2.2 1
4 Standard Version 2 x 1.5 - 100 2.2 1
6 Standard Version 2 x 0.8 - 100 2.2 1
8 Standard Version 2 x 0.6 - 100 2.2 1
10 Standard Version 2 x 0.3 - 100 2.2 1
6 Standard Version with Ground Line Choke 2 x 0.8 - 100 2.2 1
10 Standard Version with Ground Line Choke 2 x 0.3 - 100 2.2 1
1 Medical Version (M5) 2 x 10 - 100 - 1
2 Medical Version (M5) 2 x 4 - 100 - 1
4 Medical Version (M5) 2 x 1.5 - 100 - 1
6 Medical Version (M5) 2 x 0.8 - 100 - 1
8 Medical Version (M5) 2 x 0.6 - 100 - 1
10 Medical Version (M5) 2 x 0.3 - 100 - 1
1 Medical Version (M80) 2 x 10 - 100 0.47 1
Diagrams
Standard Version, medical Version M80
non-illuminated
L
PE
N
Cx
L1
L2
Cy
Cy
L’
PE’
N’
R
1) 2)
F1
F2
S
1) Line
2) Load
Medical version M5
non-illuminated
L
PE
N
Cx
L1
L2
Cy
L’
PE’
N’
RS
1) 2)
F1
F2
1) Line
2) Load
Standard Version, medical Version M80
with PE-choke
L
PE
N
Cx
L1
L2
Cy
Cy
L’
PE’
N’
R
1) 2)
F1
F2
S
L3
1) Line
2) Load
Medical version M5
with PE-choke
L
PE
N
Cx
L1
L2
L’
PE’
N’
RS
1) 2)
F1
F2
L3
1) Line
2) Load
Derating Curves
1-pole
Admissible power
acceptance in Watt
020406080 100
I = << I
n
I = 0.7 I
n
I = 1.0 I
n
2.0
1.5
1.0
0.5
0.0
Ambient air temperature Ta °C
2-pole
Admissible power
acceptance in Watt
020406080 100
0.2
0.0
I = << I
n
I = 0.7 I
n
I = 1.0 I
n
1.6
0.6
0.4
0.8
1.2
1.0
1.4
Ambient air temperature Ta °C