Green Mode
: An illuminated icon indicates that the unit is working in Green mode. The
connected equipment is receiving the utility input directly as long as the input voltage and
frequency are within the configured limits.
Alarm or notification:
The UPS has detected an error or the UPS is in configuration mode.
See β€œAlarms and Notifications” on page 11 in this manual.
Event:
The icon is illuminated when the user is viewing the event log.
Alarms and System Errors
Status Indicators
Continuous beeps, every half second
Low Battery State
- The battery is nearing its complete discharge state.
The UPS is about to shut down.
Overload condition
- The equipment connected to the UPS is drawing
more power than rated.
4 beeps every 30 sec
(first beep starts after 4 sec on battery)
On Battery State
- The UPS is supplying battery backup power to the
connected equipment.
Beeper continuously on
Alarm State
- UPS has detected an error. See β€œAlarms and Notifications”
in this manual.
Short beep every 2.5 sec
Battery disconnected.
Continuous short beeps for every
half second for 1 minute, repeats
every 5 hours.
Bad battery (replace)
Two short beeps every 5 sec
Event Bypass State
- UPS has detected an error. Connected equipment
receives utility input power through the bypass relay.
Alarms
Display code
Description
Solution
UPS has experienced a short circuit
at the output. Unit will try to auto-
recover from this condition.
Check if there is any short circuit at the UPS
output. Remove the short circuit wait the unit
auto-recover or Press button to start
the UPS.
Note:
The power supplied to the connected
equipment is dropped when the UPS is in this
condition.
UPS is experiencing an overload
condition.
Disconnect nonessential equipment from the UPS
to eliminate the overload condition.
The UPS has detected a DC voltage
error. Unit will try to auto-recover
from this condition.
If the UPS does not recover automatically,
contact Schneider Electric.
Temperature of the unit is rising
above the set limits.
Disconnect nonessential equipment from the UPS
to reduce the UPS load.
Ensure that ambient temperature is within limits.
Ensure that adequate clearance is maintained.
UPS has detected a charger error.
Verify if there is any short circuit at the UPS
battery terminal.
Press button to start the UPS.
Contact Schneider Electric for all other alarm codes.