Data Sheet
Product data sheet
Characteristics
RM17TG20
phase control relay RM17-T - range 183..484 V
AC
Main
Range of product Zelio Control
Product or component-
type
Modular measurement and control relays
Relay type Control relay
Product specific applica-
tion
For 3-phase supply
Relay name RM17TG
Relay monitored para-
meters
Asymmetry
Phase sequence
Time delay type Without
Switching capacity in-
VA
1250 VA
Measurement range 208...480 V voltage AC
Complementary
Maximum switching voltage 250 V AC
250 V DC
Minimum switching current 10 mA at 5 V DC
Supply voltage limits 183...484 V AC
Control circuit voltage limits - 12 % + 10 % Un
Power consumption in VA 0...22 VA at 400 V AC 50 Hz
Voltage detection threshold < 100 V for phase failure AC
Control circuit frequency 50...60 Hz +/- 10 %
Output contacts 2 C/O
Nominal output current 5 A
Measurement voltage limits 183...528 V AC
Run-up delay at power-up <= 650 ms
Voltage range 183...484 V
Response time <= 130 ms in the event of a fault
Marking CE
Overvoltage category III conforming to IEC 60664-1
Insulation resistance > 500 MOhm at 500 V DC conforming to IEC 60255-5
> 500 MOhm at 500 V DC conforming to IEC 60664-1
[Ui] rated insulation voltage 400 V conforming to IEC 60664-1
Supply frequency 50/60 Hz +/- 10 %
Operating position Any position without
Connections - terminals Screw terminals 1 x 0.5...1 x 4 mm² - AWG 20...AWG 11, solid cable without ca-
ble end
Screw terminals 2 x 0.5...2 x 2.5 mm² - AWG 20...AWG 14, solid cable without-
cable end
Screw terminals 1 x 0.2...1 x 2.5 mm² - AWG 24...AWG 12, flexible cable with ca-
ble end
Screw terminals 2 x 0.2...2 x 1.5 mm² - AWG 24...AWG 16, flexible cable with ca-
ble end
Tightening torque 0.6...1 N.m conforming to IEC 60947-1
Housing material Self-extinguishing plastic
Local signalling LED yellow for relay ON
Mounting support 35 mm symmetrical DIN rail conforming to EN/IEC 60715
Electrical durability 10000 cycles
Mechanical durability <= 30000000 cycles
The information provided in this documentation contains general descriptions and/or technical characteristics of the performance of the products contained herein.
This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications.
It is the duty of any such user or integrator to perform the appropriate and complete risk analysis, evaluation and testing of the products with respect to the relevant specific application or use thereof.
Neither Schneider Electric Industries SAS nor any of its affiliates or subsidiaries shall be responsible or liable for misuse of the information contained herein.
Jun 15, 2018
1