User's Guide

Use
HeatTag Wireless Sensor for Early Detection of Overheating
Cables
Filling the Tester
WARNING
UNINTENDED EQUIPMENT OPERATION
To test the HeatTag sensor, fill the HeatTag tester only with the HeatTag
Tester liquid provided by Schneider Electric.
Before using the HeatTag Tester liquid, check the validity date printed on the
bottle.
Failure to follow these instructions can result in death, serious injury, or
equipment damage.
To fill the tester with the HeatTag Tester liquid, proceed as follows:
1. Remove the tester cap by pulling it from the tester body with reasonable
force.
2. Pull out the top waterproof plug.
3. Fill the tank with the liquid to the maximum limit indicated.
4. Put the top waterproof plug on.
5. Put the tester cap back into place.
For more information about the HeatTag Tester liquid, see the data sheet, page
25.
Testing the HeatTag Sensor
NOTICE
INOPERATIVE EQUIPMENT
When testing the HeatTag sensor:
Position the HeatTag tester with the spray nozzle 10 centimeters (3.93 in)
away from the air inlet of the HeatTag sensor.
Spray the liquid for 30 s (minimum) to 45 s (maximum) towards the air inlet of
the HeatTag sensor.
Failure to follow these instructions can result in equipment damage.
To test a HeatTag sensor, proceed as follows:
1. Before testing a HeatTag sensor, turn off all power supplying the equipment
except the HeatTag sensor and the gateway paired to it.
2. Check that the tester is charged and filled with HeatTag Tester liquid.
3. Position the tester with the spray nozzle 10 centimeters (3.93 in) away from
the air inlet of the HeatTag sensor to be tested.
4. Slide the tester cap to the limit. The tester immediately emits fine particles of
the liquid.
5. Hold the tester in position and spray the liquid for 30 s (minimum) to 45 s
(maximum) towards the air inlet of the HeatTag sensor.
DOCA0171EN-00 19