TECHNICAL DATA & SERVICE MANUAL FILE NO. XH2672R / CH2672R, C2672R XH3672R / CH3672R, C3672R XH4272R / CH4272R, C4272R KH2672R / CH2672R, C2672R KH3072R / CH3072R, C3072R KH3672R / CH3672R, C3672R KHH2672R / CH2672R TH2672R / CH2672R, C2672R TH3672R / CH3672R, C3672R TH4272R / CH4272R, C4272R THH2672R / CH2672R THH3672R / CH3672R UH2672R / CH2672R, C2672R UH3672R / CH3672R, C3672R SPLIT SYSTEM AIR CONDITIONER Section INDOOR MODEL No. PRODUCT CODE No. OUTDOOR MODEL No. PRODUCT CODE No.
Important Please Read Before Starting When Installing ............................................................................................. This air conditioning system meets strict safety and operating standards. As the installer or service person, it is an important part of your job to install or service the system so it operates safely and efficiently. …In a Room Properly insulate any tubing run inside a room to prevent “sweating” that can cause dripping and water damage to walls and floors.
Contents Section 1: SPECIFICATIONS ................................................................................................. I-1 1-1 Unit Specifications .......................................................................................... I-2 1-2 Major Component Specifications .................................................................. I-27 1-3 Other Component Specifications .................................................................. I-47 1-4 Dimensional data .....................
1. Specifications 1. SPECIFICATIONS 1-1 1-2 1-3 1-4 1-5 1-6 1-7 1-8 1-9 1-10 1-11 1-12 1-13 Unit Specifications ......................................................................................................... I-2 Major Component Specifications ............................................................................... I-27 Other Component Specifications ............................................................................... I-47 Dimensional data .......................................
1. Specifications 1-1 Unit Specifications Wall-Mounted Type MODEL No. 1 2 3 4 5 Indoor Unit Outdoor Unit POWER SOURCE PERFORMANCE Capacity * [minimum~muximum] BTU / h (17˚F)** BTU / h Moisture removal (High) Pints / h Air circulation (H / M / L) 230 V CFM in. WG External Static Pressure S.E.E.R. / H.S.P.F. (Region 4) BTU / Wh ELECTRICAL RATINGS Voltage rating V Available voltage range V Max.
1. Specifications 1-1 Unit Specifications Wall-Mounted Type MODEL No. Indoor Unit Outdoor Unit POWER SOURCE PERFORMANCE Capacity * [minimum~muximum] BTU / h (17˚F)** BTU / h Moisture removal (High) Pints / h Air circulation (H / M / L) 230 V CFM in. WG External Static Pressure S.E.E.R. / H.S.P.F. (Region 4) BTU / Wh ELECTRICAL RATINGS Voltage rating V Available voltage range V Max.
1. Specifications 1-1 Unit Specifications Wall-Mounted Type MODEL No. 1 2 3 4 5 Indoor Unit Outdoor Unit POWER SOURCE PERFORMANCE Capacity * [minimum~muximum] BTU / h (17˚F)** BTU / h Moisture removal (High) Pints / h Air circulation (H / M / L) 230 V CFM in. WG External Static Pressure S.E.E.R. / H.S.P.F. (Region 4) BTU / Wh ELECTRICAL RATINGS Voltage rating V Available voltage range V Max.
1. Specifications 1-1 Unit Specifications Wall-Mounted Type MODEL No. Indoor Unit Outdoor Unit POWER SOURCE PERFORMANCE Capacity * [minimum~muximum] BTU / h (17˚F)** BTU / h Moisture removal (High) Pints / h Air circulation (H / M / L) 230 V CFM in. WG External Static Pressure S.E.E.R. / H.S.P.F. (Region 4) BTU / Wh ELECTRICAL RATINGS Voltage rating V Available voltage range V Max.
1. Specifications 1-1 Unit Specifications Wall-Mounted Type MODEL No. 1 2 3 4 5 Indoor Unit Outdoor Unit POWER SOURCE PERFORMANCE Capacity * [minimum~muximum] BTU / h (17˚F)** BTU / h Moisture removal (High) Pints / h Air circulation (H / M / L) 230 V CFM in. WG External Static Pressure S.E.E.R. / H.S.P.F. (Region 4) BTU / Wh ELECTRICAL RATINGS Voltage rating V Available voltage range V Max.
1. Specifications 1-1 Unit Specifications Wall-Mounted Type MODEL No. Indoor Unit Outdoor Unit POWER SOURCE PERFORMANCE Capacity * [minimum~muximum] BTU / h (17˚F)** BTU / h Moisture removal (High) Pints / h Air circulation (H / M / L) 230 V CFM in. WG External Static Pressure S.E.E.R. BTU / Wh ELECTRICAL RATINGS Voltage rating V Available voltage range V Max.
1. Specifications 1-1 Unit Specifications Wall-Mounted Type MODEL No. 1 2 3 4 5 Indoor Unit Outdoor Unit POWER SOURCE PERFORMANCE Capacity * [minimum~muximum] BTU / h (17˚F)** BTU / h Moisture removal (High) Pints / h Air circulation (H / M / L) 230 V CFM in. WG External Static Pressure S.E.E.R. BTU / Wh ELECTRICAL RATINGS Voltage rating V Available voltage range V Max.
1. Specifications 1-1 Unit Specifications 4-Way Air Discharge Semi-Concealed Type MODEL No. Indoor Unit XH2672R Outdoor Unit CH2672R 230 - 208 V / 1 Phase / 60 Hz POWER SOURCE Cooling Heating PERFORMANCE Capacity * [minimum~muximum] BTU / h 24,800 [9,500~24,800] 29,800 [8,000~29,800] (17˚F)** BTU / h 18,300 Moisture removal (High) Pints / h 8.1 Air circulation (H / M / L) 230 V CFM 710 / 530 / 450 in. WG External Static Pressure S.E.E.R. / H.S.P.F. (Region 4) BTU / Wh 14.1 10.
1. Specifications 1-1 Unit Specifications 4-Way Air Discharge Semi-Concealed Type MODEL No. 1 2 3 4 5 Indoor Unit XH3672R Outdoor Unit CH3672R 230 - 208 V / 1 Phase / 60 Hz POWER SOURCE Cooling Heating PERFORMANCE Capacity * [minimum~muximum] BTU / h 32,600 [9,500~32,600] 37,600 [8,000~37,600] (17˚F)** BTU / h 20,000 Moisture removal (High) Pints / h 10.6 Air circulation (H / M / L) 230 V CFM 1050 / 840 / 720 in. WG External Static Pressure S.E.E.R. / H.S.P.F. (Region 4) BTU / Wh 14.6 9.
1. Specifications 1-1 Unit Specifications 4-Way Air Discharge Semi-Concealed Type MODEL No. Indoor Unit XH4272R Outdoor Unit CH4272R 230 - 208 V / 1 Phase / 60 Hz POWER SOURCE Cooling Heating PERFORMANCE Capacity * [minimum~muximum] BTU / h 39,500 [9,500~39,500] 48,000 [8,000~48,000] (17˚F)** BTU / h 31,800 Moisture removal (High) Pints / h 12.6 Air circulation (H / M / L) 230 V CFM 1050 / 840 / 720 in. WG External Static Pressure S.E.E.R. / H.S.P.F. (Region 4) BTU / Wh 14.6 10.
1. Specifications 1-1 Unit Specifications 4-Way Air Discharge Semi-Concealed Type MODEL No. 1 2 3 4 5 Indoor Unit XH2672R Outdoor Unit C2672R 230 - 208 V / 1 Phase / 60 Hz POWER SOURCE Cooling PERFORMANCE Capacity * [minimum~muximum] BTU / h 24,800 [9,500~24,800] (17˚F)** BTU / h Moisture removal (High) Pints / h 8.1 Air circulation (H / M / L) 230 V CFM 710 / 530 / 450 in. WG External Static Pressure S.E.E.R. / H.S.P.F. (Region 4) BTU / Wh 14.
1. Specifications 1-1 Unit Specifications 4-Way Air Discharge Semi-Concealed Type MODEL No. Indoor Unit XH3672R Outdoor Unit C3672R 230 - 208 V / 1 Phase / 60 Hz POWER SOURCE Cooling PERFORMANCE Capacity * [minimum~muximum] BTU / h 32,600 [9,500~32,600] (17˚F)** BTU / h Moisture removal (High) Pints / h 10.6 Air circulation (H / M / L) 230 V CFM 1050 / 840 / 720 in. WG External Static Pressure S.E.E.R. / H.S.P.F. (Region 4) BTU / Wh 14.
1. Specifications 1-1 Unit Specifications 4-Way Air Discharge Semi-Concealed Type MODEL No. 1 2 3 4 5 Indoor Unit XH4272R Outdoor Unit C4272R 230 - 208 V / 1 Phase / 60 Hz POWER SOURCE Cooling PERFORMANCE Capacity * [minimum~muximum] BTU / h 39,500 [9,500~39,500] (17˚F)** BTU / h Moisture removal (High) Pints / h 12.6 Air circulation (H / M / L) 230 V CFM 1050 / 840 / 720 in. WG External Static Pressure S.E.E.R. / H.S.P.F. (Region 4) BTU / Wh 14.
1. Specifications 1-1 Unit Specifications Concealed-Duct Type MODEL No. Indoor Unit UH2672R Outdoor Unit CH2672R 230 - 208 V / 1 Phase / 60 Hz POWER SOURCE Cooling Heating PERFORMANCE Capacity * [minimum~muximum] BTU / h 24,000 [9,500~24,000] 28,600 [8,000~28,600] (17˚F)** BTU / h 17,100 Moisture removal (High) Pints / h 7.7 Air circulation (H / M / L) 230 V CFM 670 / 530 / 460 in.WG External Static Pressure 0.2:at shipment / 0.4:using jumper cable S.E.E.R. / H.S.P.F. (Region 4) BTU / Wh 14.0 9.
1. Specifications 1-1 Unit Specifications Concealed-Duct Type MODEL No. 1 2 3 4 5 Indoor Unit UH3672R Outdoor Unit CH3672R 230 - 208 V / 1 Phase / 60 Hz POWER SOURCE Cooling Heating PERFORMANCE Capacity * [minimum~muximum] BTU / h 31,200 [9,500~31,200] 36,200 [8,000~36,200] (17˚F)** BTU / h 20,200 Moisture removal (High) Pints / h 10.0 Air circulation (H / M / L) 230 V CFM 670 / 530 / 460 in. WG External Static Pressure 0.24:at shipment / 0.4:using jumper cable S.E.E.R. / H.S.P.F.
1. Specifications 1-1 Unit Specifications Concealed-Duct Type MODEL No. Indoor Unit UH2672R Outdoor Unit C2672R 230 - 208 V / 1 Phase / 60 Hz POWER SOURCE Cooling PERFORMANCE Capacity * [minimum~muximum] BTU / h 24,000 [9,500~24,000] — (17˚F)** BTU / h Moisture removal (High) Pints / h 7.7 Air circulation (H / M / L) 230 V CFM 670 / 530 / 460 in. WG External Static Pressure 0.2:at shipment / 0.4:using jumper cable S.E.E.R. / H.S.P.F. (Region 4) BTU / Wh 14.
1. Specifications 1-1 Unit Specifications Concealed-Duct Type MODEL No. 1 2 3 4 5 Indoor Unit UH3672R Outdoor Unit C3672R 230 - 208 V / 1 Phase / 60 Hz POWER SOURCE Cooling PERFORMANCE Capacity * [minimum~muximum] BTU / h 31,200 [9,500~31,200] — (17˚F)** BTU / h Moisture removal (High) Pints / h 10.0 Air circulation (H / M / L) 230 V CFM 670 / 530 / 460 in. WG External Static Pressure 0.24:at shipment / 0.4:using jumper cable S.E.E.R. / H.S.P.F. (Region 4) BTU / Wh 13.
1. Specifications 1-1 Unit Specifications Ceiling-Mounted Type MODEL No. Indoor Unit Outdoor Unit POWER SOURCE PERFORMANCE Capacity * [minimum~muximum] BTU / h (17˚F)** BTU / h Moisture removal (High) Pints / h Air circulation (H / M / L) 230 V CFM External Static Pressure in. WG S.E.E.R. / H.S.P.F. (Region 4) BTU / Wh ELECTRICAL RATINGS Voltage rating V Available voltage range V Max.
1. Specifications 1-1 Unit Specifications Ceiling-Mounted Type MODEL No. 1 2 3 4 5 Indoor Unit Outdoor Unit POWER SOURCE PERFORMANCE Capacity * [minimum~muximum] BTU / h (17˚F)** BTU / h Moisture removal (High) Pints / h Air circulation (H / M / L) 230 V CFM in. WG External Static Pressure S.E.E.R. / H.S.P.F. (Region 4) BTU / Wh ELECTRICAL RATINGS Voltage rating V Available voltage range V Max.
1. Specifications 1-1 Unit Specifications Ceiling-Mounted Type MODEL No. Indoor Unit Outdoor Unit POWER SOURCE PERFORMANCE Capacity * [minimum~muximum] BTU / h (17˚F)** BTU / h Moisture removal (High) Pints / h Air circulation (H / M / L) 230 V CFM in. WG External Static Pressure S.E.E.R. / H.S.P.F. (Region 4) BTU / Wh ELECTRICAL RATINGS Voltage rating V Available voltage range V Max.
1. Specifications 1-1 Unit Specifications Ceiling-Mounted Type MODEL No. 1 2 3 4 5 Indoor Unit Outdoor Unit POWER SOURCE PERFORMANCE Capacity * [minimum~muximum] BTU / h (17˚F)** BTU / h Moisture removal (High) Pints / h Air circulation (H / M / L) 230 V CFM in. WG External Static Pressure S.E.E.R. / H.S.P.F. (Region 4) BTU / Wh ELECTRICAL RATINGS Voltage rating V Available voltage range V Max.
1. Specifications 1-1 Unit Specifications Ceiling-Mounted Type MODEL No. Indoor Unit Outdoor Unit POWER SOURCE PERFORMANCE Capacity * [minimum~muximum] BTU / h (17˚F)** BTU / h Moisture removal (High) Pints / h Air circulation (H / M / L) 230 V CFM in. WG External Static Pressure S.E.E.R. / H.S.P.F. (Region 4) BTU / Wh ELECTRICAL RATINGS Voltage rating V Available voltage range V Max.
1. Specifications 1-1 Unit Specifications Ceiling-Mounted Type MODEL No. 1 2 3 4 5 Indoor Unit Outdoor Unit POWER SOURCE PERFORMANCE Capacity * [minimum~muximum] BTU / h (17˚F)** BTU / h Moisture removal (High) Pints / h Air circulation (H / M / L) 230 V CFM in. WG External Static Pressure S.E.E.R. / H.S.P.F. (Region 4) BTU / Wh ELECTRICAL RATINGS Voltage rating V Available voltage range V Max.
1. Specifications 1-1 Unit Specifications Ceiling-Mounted Type MODEL No. Indoor Unit Outdoor Unit POWER SOURCE PERFORMANCE Capacity * [minimum~muximum] BTU / h (17˚F)** BTU / h Moisture removal (High) Pints / h Air circulation (H / M / L) 230 V CFM in. WG External Static Pressure S.E.E.R. / H.S.P.F. (Region 4) BTU / Wh ELECTRICAL RATINGS Voltage rating V Available voltage range V Max.
1. Specifications 1-1 Unit Specifications Ceiling-Mounted Type MODEL No. 1 2 3 4 5 Indoor Unit Outdoor Unit POWER SOURCE PERFORMANCE Capacity * [minimum~muximum] BTU / h (17˚F)** BTU / h Moisture removal (High) Pints / h Air circulation (H / M / L) 230 V CFM in. WG External Static Pressure S.E.E.R. / H.S.P.F. (Region 4) BTU / Wh ELECTRICAL RATINGS Voltage rating V Available voltage range V Max.
1. Specifications 1-2 Major Component Specifications (A) Indoor Unit MODEL No. XH2672R Source 230 - 208 VAC / 1 phase / 60 Hz Remote controller (Option) Wired or Wireless (See Unit Specification) Controller P. C. B Ass'y CR - TH2672 Control circuit fuse Fan (Number … diameter) 250 VAC, 5 A in. (mm) Turbo (1…17-7/16 (443)) Fan motor Model SFG6X - 41D6P Source 230 - 208 V / 1 phase / 60 Hz No. of pole … r.p.m.
1. Specifications 1-2 Major Component Specifications (A) Indoor Unit MODEL No. XH3672R Source 230 - 208 VAC / 1 phase / 60 Hz Remote controller (Option) Wired or Wireless (See Unit Specification) Controller P. C. B Ass'y CR - TH2672 Control circuit fuse Fan (Number … diameter) 250 VAC, 5 A in. (mm) Turbo (1…17-7/16 (443)) Fan motor Model SFG6X - 81A6P Source 230 - 208 V / 1 phase / 60 Hz No. of pole … r.p.m.
1. Specifications 1-2 Major Component Specifications (A) Indoor Unit MODEL No. XH4272R Source 230 - 208 VAC / 1 phase / 60 Hz Remote controller (Option) Wired or Wireless (See Unit Specification) Controller P. C. B Ass'y CR - TH2672 Control circuit fuse Fan (Number … diameter) 250 VAC, 5 A in. (mm) Turbo (1…17-7/16 (443)) Fan motor Model SFG6X - 81A6P Source 230 - 208 V / 1 phase / 60 Hz No. of pole … r.p.m.
1. Specifications 1-2 Major Component Specifications (A) Indoor Unit MODEL No. TH2672R Source 230 - 208 V / 1 phase / 60 Hz Remote controller (Option) Wired or Wireless (See Unit Specification) Controller P. C. B Ass'y CR - TH2672 Control circuit fuse Fan (Number … diameter) 250 V, 5 A in. (mm) Centrifugal (4 ... 5-1/8(130)) Fan motor Model SR4X - 51A6P Source 230 - 208 V / 1 phase / 60 Hz No. of pole … r.p.m.
1. Specifications 1-2 Major Component Specifications (A) Indoor Unit MODEL No. TH3672R Source 230 - 208 V / 1 phase / 60 Hz Remote controller (Option) Wired or Wireless (See Unit Specification) Controller P. C. B Ass'y CR - TH2672 Control circuit fuse Fan (Number … diameter) 250 V, 5 A in. (mm) Centrifugal (4 ... 5-29/32(150)) Fan motor Model KFG4X - 101C6P Source 230 - 208 V / 1 phase / 60 Hz No. of pole … r.p.m. (230 V, High) rpm Nominal output W Coil resistance Ω 4 ...
1. Specifications 1-2 Major Component Specifications (A) Indoor Unit MODEL No. TH4272R Source 230 - 208 V / 1 phase / 60 Hz Remote controller (Option) Wired or Wireless (See Unit Specification) Controller P. C. B Ass'y CR - TH2672 Control circuit fuse Fan (Number … diameter) 250 V, 5 A in. (mm) Centrifugal (4 ... 5-29/32(150)) Fan motor Model KFG4X - 101C6P Source 230 - 208 V / 1 phase / 60 Hz No. of pole … r.p.m. (230 V, High) rpm Nominal output W Coil resistance Ω 4 ...
1. Specifications 1-2 Major Component Specifications (A) Indoor Unit MODEL No. THH2672R Source 230 - 208 V / 1 phase / 60 Hz Remote controller (Option) Wired or Wireless (See Unit Specification) Controller P. C. B Ass'y CR - TH2672 Control circuit fuse Fan (Number ... diameter) 250 V, 5 A in. Centrifugal (4 ... 5-1/8(130)) (mm) Fan motor SR4X - 51A6P Model 230 - 208 V / 1 phase / 60 Hz Source No. of pole ... r.p.m.
1. Specifications 1-2 Major Component Specifications (A) Indoor Unit MODEL No. THH3672R Source 230 - 208 V / 1 phase / 60 Hz Remote controller (Option) Wired or Wireless (See Unit Specification) Controller P. C. B Ass'y CR - TH2672 Control circuit fuse Fan (Number ... diameter) 250 V, 5 A in. Centrifugal (4 ... 5-29/32(150)) (mm) Fan motor KFG4X - 101C6P Model 230 - 208 V / 1 phase / 60 Hz Source No. of pole ... r.p.m. (230 V, High) rpm Nominal output W Coil resistance Ω 4 ...
1. Specifications 1-2 Major Component Specifications (A) Indoor Unit MODEL No. UH2672R Source 230 - 208 V / 1 phase / 60 Hz Remote controller (Option) Wired or Wireless (See Unit Specification) Controller P. C. B Ass'y CR - TH2672 Control circuit fuse Fan (Number … diameter) 250 V, 5 A in. (mm) Centrifugal (4 ... 5-29/32(150)) Fan motor Model KFG4X - 71B6P Source 230 - 208 V / 1 phase / 60 Hz No. of pole … r.p.m. (230 V, High) rpm Nominal output W Coil resistance Ω 4 ...
1. Specifications 1-2 Major Component Specifications (A) Indoor Unit MODEL No. UH3672R Source 230 - 208 V / 1 phase / 60 Hz Remote controller (Option) Wired or Wireless (See Unit Specification) Controller P. C. B Ass'y CR - TH2672 Control circuit fuse Fan (Number … diameter) 250 V, 5 A in. (mm) Centrifugal (4 ... 5-29/32(150)) Fan motor Model KFG4X - 141A6P Source 230 - 208 V / 1 phase / 60 Hz No. of pole ... r.p.m. (230 V, High) rpm Nominal output W Coil resistance Ω 4 ...
1. Specifications 1-2 Major Component Specifications (A) Indoor Unit MODEL No. KH2672R Source 230 - 208 V / 1 phase / 60 Hz Remote controller (Option) Wired or Wireless (See Unit Specification) Controller P. C. B Ass'y CB - KR24GXH56A Control circuit fuse 250 V, 5 A Fan Cross-flow Number ... Dia. and length in. (mm) 1 ... O.D. 4-1/3 (110), L39 (990) Fan motor Model KFT4Q - 31A6P - C Source 230 - 208 V / 1 phase / 60 Hz No. of pole ... r.p.m.
1. Specifications 1-2 Major Component Specifications (A) Indoor Unit MODEL No. KH3072R Source 230 - 208 V / 1 phase / 60 Hz Remote controller (Option) Wired or Wireless (See Unit Specification) Controller P. C. B Ass'y CR - TH2672 Control circuit fuse 250 V, 5 A Fan Cross-flow Number ... Dia. and length in. (mm) 1 ... O.D. 4-13/18 (120), L46 (1,170) Fan motor Model SGF4Q - 41D6P Source 230 - 208 V / 1 phase / 60 Hz No. of pole ... r.p.m.
1. Specifications 1-2 Major Component Specifications (A) Indoor Unit MODEL No. KH3672R Source 230 - 208 V / 1 phase / 60 Hz Remote controller (Option) Wired or Wireless (See Unit Specification) Controller P. C. B Ass'y CR - TH2672 Control circuit fuse 250 V, 5 A Fan Cross-flow Number ... Dia. and length in. (mm) 1 ... O.D. 4-13/18 (120), L46 (1,170) Fan motor Model SFG4Q - 41B6P Source 230 - 208 V / 1 phase / 60 Hz No. of pole ... r.p.m.
1. Specifications 1-2 Major Component Specifications (A) Indoor Unit MODEL No. KHH2672R Source 230 - 208 V / 1 phase / 60 Hz Remote controller (Option) Wired or Wireless (See Unit Specification) Controller P. C. B Ass'y CR - TH2672 Control circuit fuse 250 V, 5 A Fan Cross-flow Number ... Dia. and length in. (mm) 1 ... O.D. 4-1/3 (110), L39 (990) Fan motor Model UF4Q - 31A6P Source 230 - 208 V / 1 phase / 60 Hz No. of pole ... r.p.m.
1. Specifications 1-2 Major Component Specifications (B) Outdoor Unit CH2672R MODEL No. 208 - 230 V / 1 phase / 60 Hz Source CR-CH4872R (Microprocessor) Controller P.C.B. Ass'y 280 V, 25 A Control circuit fuse (on the P.C.B.“FIL-CH4872R”) Compressor Model....number C-7RVN153H0V Nominal output W Compressor oil cc Coil resistance Ω 1,500 650 C – R : 0.665 (Ambient temperature 25 °C) R – S : 0.665 C – S : 0.
1. Specifications 1-2 Major Component Specifications (B) Outdoor Unit CH3072R / CH3672R MODEL No. 208 - 230 V / 1 phase / 60 Hz Source CR-CH4872R (Microprocessor) Controller P.C.B. Ass'y 280 V, 25 A Control circuit fuse (on the P.C.B.“FIL-CH4872R”) Compressor Model....number C-7RVN153H0V Nominal output W Compressor oil cc Coil resistance Ω 1,500 650 C – R : 0.665 (Ambient temperature 25 °C) R – S : 0.665 C – S : 0.
1. Specifications 1-2 Major Component Specifications (B) Outdoor Unit CH4272R MODEL No. 208 - 230 V / 1 phase / 60 Hz Source CR-CH4872R (Microprocessor) Controller P.C.B. Ass'y 280 V, 25 A Control circuit fuse (on the P.C.B.“FIL-CH4872R”) Compressor Model....number C-9RVN273H0W Nominal output W Compressor oil cc Coil resistance Ω 2,700 1,900 C – R : 0.169 (Ambient temperature 25 °C) R – S :0.169 C – S :0.
1. Specifications 1-2 Major Component Specifications (B) Outdoor Unit C2672R MODEL No. 208 - 230 V / 1 phase / 60 Hz Source CR-CH4872R (Microprocessor) Controller P.C.B. Ass'y 280 V, 25 A Control circuit fuse (on the P.C.B.“FIL-CH4872R”) Compressor Model....number C-7RVN153H0V Nominal output W Compressor oil cc Coil resistance Ω 1,500 650 C – R : 0.665 (Ambient temperature 25 °C) R – S : 0.665 C – S : 0.
1. Specifications 1-2 Major Component Specifications (B) Outdoor Unit C3072R / C3672R MODEL No. 208 - 230 V / 1 phase / 60 Hz Source CR-CH4872R (Microprocessor) Controller P.C.B. Ass'y 280 V, 25 A Control circuit fuse (on the P.C.B.“FIL-CH4872R”) Compressor Model....number C-7RVN153H0V Nominal output W Compressor oil cc Coil resistance Ω 1,500 650 C – R : 0.665 (Ambient temperature 25 °C) R – S : 0.665 C – S : 0.
1. Specifications 1-2 Major Component Specifications (B) Outdoor Unit C4272R MODEL No. 208 - 230 V / 1 phase / 60 Hz Source CR-CH4872R (Microprocessor) Controller P.C.B. Ass'y 280 V, 25 A Control circuit fuse (on the P.C.B.“FIL-CH4872R”) Compressor Model....number C-9RVN273H0W Nominal output W Compressor oil cc Coil resistance Ω 2,700 1,900 C – R : 0.169 (Ambient temperature 25 °C) R – S :0.169 C – S :0.
1. Specifications 1-3 Other Component Specifications (A) Indoor Unit MODEL No. XH2672R Power Transformer Rated ATR – IIK224A Primary 220 VAC, 60 Hz Secondary BRN - BRN : 14 V, 0.45 A, RED - RED : 14 V, 0.3 A Capacity — Coil resistance (Ambient temprature 77 °F) Ω Thermistor cut off temperature °F WHT - WHT BRN - BRN RED - RED ORG - ORG : : 1.37 3.16 PBC - 41E - S14 kΩ 14 °F : 23.7 23 °F : 18.8 32 °F : 15.0 Thermistor (Room sensor) : TH1 Coil resistance 61.0 , 0.
1. Specifications 1-3 Other Component Specifications (A) Indoor Unit MODEL No. XH3672R Power Transformer Rated ATR – IIK224A Primary 220 VAC, 60 Hz Secondary BRN - BRN : 14 V, 0.45 A, RED - RED : 14 V, 0.3 A — Capacity Coil resistance (Ambient temprature 77 °F) Ω Thermistor cut off temperature °F WHT - WHT BRN - BRN 1 RED - RED ORG - ORG : : 1.37 3.16 PBC - 41E - S14 kΩ 14 °F : 23.7 23 °F : 18.8 32 °F : 15.0 Thermistor (Room sensor) : TH1 Coil resistance 61.0 , 0.
1. Specifications 1-3 Other Component Specifications (A) Indoor Unit MODEL No. XH4272R Power Transformer Rated ATR – IIK224A Primary 220 VAC, 60 Hz Secondary BRN - BRN : 14 V, 0.45 A, RED - RED : 14 V, 0.3 A — Capacity Coil resistance (Ambient temprature 77 °F) Ω Thermistor cut off temperature °F WHT - WHT BRN - BRN RED - RED ORG - ORG : : 1.37 3.16 PBC - 41E - S14 kΩ 14 °F : 23.7 23 °F : 18.8 32 °F : 15.
1. Specifications 1-3 Other Component Specifications (A) Indoor Unit MODEL No. TH2672R Power Transformer Rated ATR – IIK244B Primary AC 220 V, 60 Hz Secondary BRN - BRN : 14 V / 0.55 A, RED - RED : 14 V / 0.3 A — Capacity Coil resistance (Ambient temprature 77 °F) Ω Thermistor cut off temperature °F WHT - WHT BRN - BRN 1 RED - RED ORG - ORG : : 0.89 2.05 PBC - 41E - S14 kΩ 14 °F 23 °F 32 °F 41 °F 50 °F : : : : : 23.7 18.8 15.0 12.1 9.7 kΩ 32 °F 41 °F 50 °F 68 °F 86 °F : : : : : 16.
1. Specifications 1-3 Other Component Specifications (A) Indoor Unit MODEL No. TH3672R Power Transformer Rated ATR – IIK244B Primary AC 220 V, 60 Hz Secondary BRN - BRN : 14 V / 0.55 A, RED - RED : 14 V / 0.55 A Capacity — Coil resistance (Ambient temprature 77 °F) Ω Thermistor cut off temperature °F WHT - WHT BRN - BRN RED - RED ORG - ORG : : 0.89 2.05 PBC - 41E - S14 kΩ 14 °F 23 °F 32 °F 41 °F 50 °F : : : : : 23.7 18.8 15.0 12.1 9.
1. Specifications 1-3 Other Component Specifications (A) Indoor Unit MODEL No. TH4272R Power Transformer Rated ATR – IIK244B Primary AC 220 V, 60 Hz Secondary BRN - BRN : 14 V / 0.55 A, RED - RED : 14 V / 0.3 A — Capacity Coil resistance (Ambient temprature 77 °F) Ω Thermistor cut off temperature °F WHT - WHT BRN - BRN 1 RED - RED ORG - ORG : : 0.89 2.05 PBC - 41E - S14 kΩ 14 °F 23 °F 32 °F 41 °F 50 °F : : : : : 23.7 18.8 15.0 12.1 9.
1. Specifications 1-3 Other Component Specifications (A) Indoor Unit MODEL No. THH2672R Power Transformer Rated ATR – IIK244B Primary AC 220 V, 60 Hz Secondary BRN - BRN : 14 V / 0.55 A, RED - RED : 14 V / 0.3 A — Capacity Coil resistance (Ambient temprature 77 °F) Ω Thermistor cut off temperature °F WHT - WHT BRN - BRN RED - RED ORG - ORG : : 0.89 2.05 PBC - 41E - S14 kΩ 14 °F 23 °F 32 °F 41 °F 50 °F : : : : : 23.7 18.8 15.0 12.1 9.7 kΩ 32 °F 41 °F 50 °F 68 °F 86 °F : : : : : 16.
1. Specifications 1-3 Other Component Specifications (A) Indoor Unit MODEL No. THH3672R Power Transformer Rated ATR – IIK244B Primary AC 220 V, 60 Hz Secondary BRN - BRN : 14 V / 0.55 A, RED - RED : 14 V / 0.55 A — Capacity Coil resistance (Ambient temprature 77 °F) Ω Thermistor cut off temperature °F WHT - WHT BRN - BRN 1 RED - RED ORG - ORG : : 0.89 2.05 PBC - 41E - S14 kΩ 14 °F 23 °F 32 °F 41 °F 50 °F : : : : : 23.7 18.8 15.0 12.1 9.
1. Specifications 1-3 Other Component Specifications (A) Indoor Unit MODEL No. UH2672R Power Transformer Rated ATR – IIK244B Primary AC 220 V, 60 Hz Secondary BRN - BRN : 14 V / 0.55 A, RED - RED : 14 V / 0.3 A — Capacity Coil resistance (Ambient temprature 77 °F) Ω Thermistor cut off temperature °F WHT - WHT BRN - BRN RED - RED ORG - ORG : : 0.89 2.05 PBC - 41E - S36 kΩ 14 °F 23 °F 32 °F 41 °F 50 °F : : : : : 23.7 18.8 15.0 12.1 9.7 Thermistor (Room or coil sensor) Coil resistance 48.
1. Specifications 1-3 Other Component Specifications (A) Indoor Unit MODEL No. UH3672R Power Transformer Rated ATR – IIK244B Primary AC 220 V, 60 Hz Secondary BRN - BRN : 14 V / 0.55 A, RED - RED : 14 V / 0.3 A — Capacity Coil resistance (Ambient temprature 77 °F) Ω Thermistor cut off temperature °F WHT - WHT BRN - BRN RED - RED ORG - ORG : : 0.89 2.05 PBC - 41E - S36 kΩ 14 °F 23 °F 32 °F 41 °F 50 °F : : : : : 23.7 18.8 15.0 12.1 9.
1. Specifications 1-3 Other Component Specifications (A) Indoor Unit MODEL No. KH2672R Power Transformer Rated ATR – IIK244D – R Primary AC 230 V, 60 Hz Secondary BRN - BRN : 11 V / 1.25 A, RED - RED : 14 V / 0.45 A — Capacity Coil resistance (Ambient temprature 77 °F) Ω Thermistor cut off temperature °F WHT - WHT BRN - BRN RED - RED ORG - ORG : : 1.95 6.11 PBC - 41E - S4 kΩ 14 °F 23 °F 32 °F 41 °F 50 °F : : : : : 23.7 18.8 15.0 12.1 9.
1. Specifications 1-3 Other Component Specifications (A) Indoor Unit MODEL No. KH3072R Power Transformer Rated ATR – IIK244B Primary AC 220 V, 60 Hz Secondary BRN - BRN : 14 V / 0.55 A, RED - RED : 14 V / 0.3 A — Capacity Coil resistance (Ambient temprature 77 °F) Ω Thermistor cut off temperature °F WHT - WHT BRN - BRN 1 RED - RED ORG - ORG : : 0.89 2.05 PBC - 41E - S4 kΩ 14 °F 23 °F 32 °F 41 °F 50 °F : : : : : 23.7 18.8 15.0 12.1 9.
1. Specifications 1-3 Other Component Specifications (A) Indoor Unit MODEL No. KHH2672R Power Transformer Rated ATR – IIK244B Primary AC 220 V, 60 Hz Secondary BRN - BRN : 14 V / 0.55 A, RED - RED : 14 V / 0.3 A — Capacity Coil resistance (Ambient temprature 77 °F) Ω Thermistor cut off temperature °F WHT - WHT BRN - BRN RED - RED ORG - ORG : : 0.89 2.05 PBC - 41E - S4 kΩ 14 °F 23 °F 32 °F 41 °F 50 °F : : : : : 23.7 18.8 15.0 12.1 9.7 Thermistor (Room or coil sensor) Coil resistance 48.
1. Specifications 1-3 Other Component Specifications (B) Outdoor Unit MODEL No. CH2672R, C2672R Thermistor (Coil sensor) : TH2 to 5 Coil resistance kΩ 14 °F 23 °F 32 °F 41 °F : : : : 23.7 18.8 15.0 12.1 , , , , 50 °F 68 °F 86 °F 104 °F 113 °F : : : : : 9.7 6.5 4.4 3.1 2.6 140 °F 158 °F 167 °F 176 °F 185 °F : : : : : 13.8 9.7 8.2 7.0 5.9 , , , , , 194 °F 212 °F 230 °F 248 °F 266 °F : : : : : 5.1 3.8 2.8 2.2 1.7 Thermistor (Comp.
1. Specifications 1-3 Other Component Specifications (B) Outdoor Unit MODEL No. CH3072R, C3072R, CH3672R, C3672R Thermistor (Coil sensor) : TH2 to 5 Coil resistance kΩ 14 °F 23 °F 32 °F 41 °F : : : : 23.7 18.8 15.0 12.1 , , , , 50 °F 68 °F 86 °F 104 °F 113 °F : : : : : 9.7 6.5 4.4 3.1 2.6 140 °F 158 °F 167 °F 176 °F 185 °F : : : : : 13.8 9.7 8.2 7.0 5.9 , , , , , 194 °F 212 °F 230 °F 248 °F 266 °F : : : : : 5.1 3.8 2.8 2.2 1.7 Thermistor (Comp.
1. Specifications MODEL No. CH4272R, C4272R Thermistor (Coil sensor) : TH2 to 5 Coil resistance kΩ 14 °F 23 °F 32 °F 41 °F : : : : 23.7 18.8 15.0 12.1 , , , , 50 °F 68 °F 86 °F 104 °F 113 °F : : : : : 9.7 6.5 4.4 3.1 2.6 140 °F 158 °F 167 °F 176 °F 185 °F : : : : : 13.8 9.7 8.2 7.0 5.9 , , , , , 194 °F 212 °F 230 °F 248 °F 266 °F : : : : : 5.1 3.8 2.8 2.2 1.7 Thermistor (Comp.
1. Specifications 1-4 Dimensional data Indoor unit : 4-Way Air Discharge Semi-concealed Type 26 Type 10-9/32 8-11/16 4-7/8 Min. 2-15/32 3 11-1/2 9-1/8 X-view 13-11/32 3-15/16 Min.
1. Specifications 1-4 Dimensional data Indoor unit : 4-Way Air Discharge Semi-concealed Type 36, 42Type 11-15/32 9-19/32 13-11/32 3-15/16 4-7/8 Min. 2-15/32 X-view Min.
1.
1.
1.
1.
1. Specifications 1-4 Dimensional data Indoor unit : Concealed Duct Type 13/32 Thickness more than T1/16 inch 8-9/32 31/32 2-ø1/8 (Hole) Flange for the air intake duct (Field supply) : For Concealed Duct Type 31/32 12-1/32 31/32 10-1/4 (O.D.) 29/32 23/32 F 1-7/32 1/4 (Hole) 13/32 G C-ø1/8 (Hole) D 1 E A H B (O.D.
1.
1.
1.
1.
1.
1.
1.
1. Specifications 1-8 Noise Criterion Curves 4-Way Air Discharge Semi-concealed Type MODEL : XH2672R SOUND LEVEL : HIGH 38 dB(A), NC 31 LOW 31 dB(A), NC 23 CONDITION : Center, Under the unit 4.9 ft. SOURCE : 208 - 230 V, 1 Phase, 60 Hz OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.
1. Specifications 1-8 Noise Criterion Curves Ceiling Mounted Type MODEL : TH2672R, THH2672R MODEL SOUND LEVEL : HIGH 40 dB(A), NC 34 LOW SOUND LEVEL : HIGH 46 dB(A), NC 39 36 dB(A), NC 26 LOW : Distance 3.3 ft., Under the unit 3.3 ft. CONDITION : Distance 3.3 ft., Under the unit 3.3 ft.
1. Specifications 1-8 Noise Criterion Curves Concealed Duct Type MODEL MODEL : UH2672R : UH3672R CONDITION : Under the unit 4.9 ft. CONDITION : Under the unit 4.9 ft. SOURCE : 208 - 230 V, 1 Phase, 60 Hz SOURCE : 208 - 230 V, 1 Phase, 60 Hz OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 bar) SOUND LEVEL : HIGH 38 dB(A), NC 30 / LOW 31 dB(A), NC 21 OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.
1. Specifications 1-8 Noise Criterion Curves Wall Mounted Type MODEL : KHH2672R SOUND LEVEL : HIGH 45 dB(A), LOW CONDITION : Distance 3.3 ft., Under the unit 3.3 ft. SOURCE : 208 - 230 V, NC 38 40 dB(A), NC 33 CONDITION : Distance 3.3 ft., Under the unit 3.3 ft. SOURCE : 208 - 230 V, 1 Phase, 60 Hz 1 Phase, 60 Hz OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.
1. Specifications 1-8 Noise Criterion Curves Outdoor Units 1 2 3 4 REMARKS: 1. Value obtained in the actual place where the unit is installed may be slightly higher than the values shown in this graph because of the conditions of operation, the structure of the building, the background noise and other factors. 2. The test results were obtained from an nechoic room. NOTE To evaluate “Noise level” the maximum number of the measured OCTAVE BAND SOUND PRESSURE LEVEL is used.
1. Specifications 1-9 Increasing the Fan Speed Electrical component box If external static pressure is too great (due to long extension of ducts, for example), the air flow volume may drop too low at each air outlet. This problem may be solved by increasing the fan speed using the following procedure: Jumper cable Fan motor Jumper cable Fan motor socket (At shipment) (1) Remove 4 screws on the electrical component box and remove the cover plate.
1. Specifications 1-10 Air throw distance chart 4-Way Air Discharge Semi-concealed Type Model: 26 Type HORIZONTAL DISTANCE (ft.) 0 3 7 10 13 17 20 AXIS AIR VELOCITY (ft./sec) VERTICAL DISTANCE (ft.) 0 AXIS AIR VELOCITY 3 7 10 13 2111_X_I Model: 36, 42 Type 1 HORIZONTAL DISTANCE (ft.) 0 3 7 10 13 17 20 AXIS AIR VELOCITY (ft./sec) VERTICAL DISTANCE (ft.
1. Specifications 1-10 Air throw distance chart Ceiling Mounted Type Model: 26 Type HORIZONTAL DISTANCE (ft.) AXIS AIR VELOCITY (ft./sec) VERTICAL DISTANCE (ft.) 0 3 7 10 13 17 20 23 26 29 33 0 3 AXIS AIR VELOCITY 7 10 13 17 2115_T_I Model: 36 Type HORIZONTAL DISTANCE (ft.) 1 AXIS AIR VELOCITY (ft./sec) VERTICAL DISTANCE (ft.) 0 3 7 10 13 17 20 23 26 29 33 0 3 AXIS AIR VELOCITY 7 10 13 17 2116_T_I 2 Model: 42 Type HORIZONTAL DISTANCE (ft.) 3 4 AXIS AIR VELOCITY (ft.
1. Specifications 1-10 Air throw distance chart Wall Mounted Type Model: KHH2672R Horizontal distance (ft.) 5 0 10 15 20 25 30 ty xis air veloci Axis air velocity (ft./sec.) Vertical distance (ft.) A 45˚ 5 0˚ 67.5˚ 22.5˚ 10 45˚ 15 2121_K_S Model: KH2672R Horizontal distance (ft.) Axis air velocity (ft./sec.) Vertical distance (ft.) 0 1 5 10 13 2 Model: KH3072R KH3672R Horizontal distance (ft.) 5 Axis air velocity (ft./sec.) Vertical distance (ft.
1. Specifications 1-11 Installation Instructions Single Tubing Length Single type Maximum length Refrigerant tubing between the indoor and outdoor units should be kept as short as possible. H1 The length of the refrigerant tubes between the indoor and outdoor units are limited by the elevation difference between the 2 units. During tubing work, try to make both the tubing length (L) and the difference in elevation (H1) as short as possible. Refer to Table 1-2.
1. Specifications Table 1-2 Tubing Data for Models Models Tubing Data Tubing size outer diameter Liquid tube Gas tube in. (mm) in. (mm) Limit of tubing length (ft.) Outdoor unit is placed Limit of elevation higher (ft.) difference between Outdoor unit is placed the 2 units lower (ft.) Max. allowable tubing length at shipment (ft.) Required additional refrigerant *1 (oz./ft.) Refrigerant charged at shipment (lbs.) C(H)2672R C(H)3072R C(H)3672R C(H)4272R 3/8 (9.52) 5/8 (15.88) 165 3/8 (9.52) 5/8 (15.
1. Specifications SELECTING THE INSTALLATION SITE Indoor Unit Ceiling-Mounted Type AVOID: Ceiling areas where leakage of flammable gas may be expected. places where large amounts of oil mist exist. Wall direct sunlight. locations near inverter lamps which may affect performance of the unit. Min.10 inch NOTE locations near heat sources which may affect performance of the unit. The rear of the indoor unit can be installed flush against the wall.
1. Specifications Outdoor Unit AVOID: Exhaust fan heat sources, exhaust fans, etc. (Fig. 1-1) Hot air damp, humid or uneven locations Heat source DO: Outdoor unit choose a place as cool as possible. choose a place that is well ventilated and outside air temperature does not exceed maximum 115°F constantly. Fig. 1-1 allow enough room around the unit for air intake/ exhaust and possible maintenance. (Fig. 1-2) use lug bolts or equal to bolt down unit, reducing vibration and noise.
1. Specifications Air-Discharge Chamber for Top Discharge Be sure to install an air discharge chamber in the field when: it is difficult to keep a space of min. 20" between the air discharge outlet and an obstacle. the air discharge outlet is facing a sidewalk and discharged hot air may bother passers-by. Refer to Fig. 1-5.
1.
1.
1. Specifications Reference diagram for air-discharge chamber (field supply) For outdoor unit C(H)2672R / 3072R / 3672R / 4272R Required space around outdoor unit If the air discharge chamber is used, the space shown below must be secured around the outdoor unit. If the unit is used without the required space, a protective device may activate, preventing the unit from operating. Min. 7-7/8 Min. 39-3/8 (1) Single-unit installation Unit: inch CAUTION The top and both sides must remain open.
1.
1.
1. Specifications Reference diagram for snow-proof vents - 1 Space requirements for setting - (1) C(H)2672R / 3072R / 3672R / 4272R with STK-BDRE80A & STK-BDR140U [Obstacle to the front of unit] [Obstacle to the rear of unit] Top is open: Top is open: (1) Single-unit installation Min. D Min. A Min. H (1) Single-unit installation (2) Obstacles on both sides Min. B Min. C (2) Multiple-unit installation (2 or more units) Min. I Min. G Min. I Min.
1. Specifications Reference diagram for snow-proof vents - 2 Space requirements for setting - (2) C(H)2672R / 3072R / 3672R / 4272R with STK-BDRE80A & STK-BDR140U [Obstacles to the front and rear of unit] The top and both sides must remain open. Either the obstacle to the front or the obstacle to the rear must be no taller than the height of the outdoor unit. Q Min. O Min.
1. Specifications 1-12 Electrical Wiring General Precautions on Wiring 1) Before wiring, confirm the rated voltage of the unit as shown on its nameplate, then carry out the wiring closely following the wiring diagram. 2) Provide a power outlet to be used exclusively for each unit, and a power supply disconnect and circuit breaker for overcurrent protection should be provided in the exclusive line. 7) To prevent possible hazards from insulation failure, the unit must be grounded.
1. Specifications Indoor Unit MOP (B) Power Supply Trade Size (Fuse or HACR AWG #14 of Conduit type circuit breaker) Type X, K, T, U Max. length 67 ft. 3/4 in. 15 A Control Wiring (C) Inter-Unit Control Wiring (D) Remote Control Wiring AWG #18 Use high voltage wire (300 V)*1 AWG #18*2 (0.75 mm2) Max. 3,300 ft. Max. 1,650 ft. (E) Control Wiring For Group Control AWG #18*2 – (0.75 mm2) Max. 1,650 – ft. (Total) *1 *2 With ring-type wire terminal. Wire joint connection.
1. Specifications Stranded wire Strip 3/8 in. WARNING Loose wiring may cause the terminal to overheat or result in unit malfunction. A fire hazard may also exist. Therefore, ensure that all wiring is tightly connected. When connecting each power wire to the corresponding terminal, follow the instructions on “How to connect wiring to the terminal” and fasten the wire securely with the fixing screw of the terminal plate. Fig.
1. Specifications CAUTION (1) When linking outdoor units in a network (S-net link system), disconnect the terminal extended from the short plug (CN003, 2P Black, location: right bottom on the outdoor main control PCB) from all outdoor units except any one of the outdoor units. (When shipping: In shorted condition.) Otherwise the communication of S-net link system is not performed. For a system without link (no connection wiring between outdoor units), do not remove the short plug.
1. Specifications 1-13 Using Wireless Remote Controller with Wall-mounted Indoor Unit When the wireless remote controller is to be used, slide the switch on the indoor unit control PCB. If this setting is not made, an alarm will occur.(The operation lamp on the display blinks.) This setting is not necessary if both the wired remote controller and wireless remote controller are used. KH3072R KH3672R KHH2672R 1 2 3 KH2672R Setting at time of factory shipment 4 Slide No. 3 on SW101 from ON OFF.
2. Processes and functions 2. PROCESSES AND FUNCTIONS 2-1 2-2 2-3 2-4 2-5 2-6 Room Temperature Control .......................................................................................... II-2 Cold Draft Prevention (Heating Cycle) ........................................................................ II-4 Automatic Fan Speed (Indoor Unit) ............................................................................. II-5 Control Functions ............................................................
2. Processes and functions 2-1 Room Temperature Control The unit adjusts room temperature by turning the outdoor unit’s compressor ON and OFF. This process is controlled by the thermostat located in the remote control unit. The figures on this and the next pages show how each part of the system performs when the room temperature changes and the thermostat activates the compressor to start (thermo ON) or stop (thermo OFF). Fig. 1 shows about the cooling cycle, and Fig. 2 shows about the heating cycle.
2. Processes and functions (B) Heating THERMO. ON REMOTE CONTROL SENSOR (Only for wireless remote controller) SET. +2 °F SETTING TEMP. SET. –2 °F THERMO. ON THERMO. OFF THERMO. OFF THERMO. ON THERMO. OFF BODY SENSOR THERMO. ON THERMO. OFF THERMO. ON THERMO. ON +2°F SET TEMP.+7 °F SHIFT –2°F SET TEMP.
2. Processes and functions 2-2 Cold Draft Prevention (Heating Cycle) The cold draft prevention function controls indoor fan speed so a strong draft of cold air will not blow out before the indoor heat exchange coils have warmed up. ❑ STANDBY shows on the remote controller when the indoor fan speed is LL (very low) or OFF. This condition occurs in the following 3 cases: • During Thermo OFF (refer to 2-1 B.
2. Processes and functions 2-3 Automatic Fan Speed (Indoor Unit) By pressing the FAN SPEED button on the remote controller, the fan speed can be set at one of four steps: AUTO., HI., MED., or LO. When set at AUTO. the indoor unit fan speed will be automatically adjusted to the room temperature as the two charts shown below. (A) Cooling ROOM TEMP. (deg) +3 +2 +1 SET TEMP. INDOOR FAN SPEED H M M L H 1 H : High L : Low M : Middle 1923_M_S Fig.
2. Processes and functions 2-4 Control Functions Electronic control valve control Opening of the electronic control valve is controlled so that the appropriate operating conditions are maintained, based on the signal from each sensor (discharge temperature [TD], intake temperature [TS], outdoor heat exchanger temperature [C1], and indoor heat exchanger temperature [E1, E2]).
2. Processes and functions Overcurrent protection control (1) If the overcurrent protection circuit detects abnormal current, the compressor is stopped. (Error count = 1.) The compressor then restarts after 3 minutes. (2) If compressor start/stop is repeated 4 times (error count = 4), alarm "P26", "P29" or "H01" (count = 2 in this case only) occurs. Operation stops and does not restart.
2. Processes and functions Defrost control Defrost control Defrost sequence Heating operation (25-minute mask) 1 Frost detection Defrost start (reverse cycle defrost) • Defrost in progress • • • • 2 Defrost cancel 1 Operating frequency: 61.8 Hz Outdoor unit fan: OFF Electronic control valve: step 300 4-way valve: OFF Indoor unit fan: OFF 3 Start-up operation (1) Frost detection 1. Outdoor heat exchanger temperature (C1) method (15-minute mask after operation start) 2 3 4 5 2.
2.
2. Processes and functions 2-6 Outdoor Unit Control PCB (CR-CH4272R) (1) Explanation of Functions S001 Push-button switch (black): Automatic address setting switch • If the system address switch (S002: set to 0 at time of shipment) setting is other than "0" (central control), press this switch once to automatically set the addresses at all indoor units which are in the same system, and are connected to that outdoor unit.
2. Processes and functions Terminal plug (CN015) 3P plug (black): Terminal plug for the communications line • At the time of shipment from the factory, the short-circuiting socket (2P, black) is installed between pins 1 and 2 on the terminal plug (terminal = yes). • When central control is used for multiple systems, leave the short-circuiting socket in place only on the outdoor unit with a system address of 1. At all other outdoor units (other than unit No.
3. Electrical data 3. ELECTRICAL DATA 3-1 Indoor Units .................................................................................................................... III-2 3-2 Outdoor Units ...............................................................................................................
3.
3.
3.
3.
3.
3.
3.
3.
3.
3.
3.
3.
3.
3.
3.
3.
3.
3.
3.
3.
3.
3.
3.
3.
3.
3.
4. Service procedures 4. SERVICE PROCEDURES 4-1. Meaning of Alarm Messages......................................................................................... IV-2 4-2. Symptoms and Parts to Inspect ................................................................................... IV-5 4-3. Details of Alarm Messages ...........................................................................................IV-8 4-4. Table of Thermistor Characteristics ..................................................
4. Service procedures 4-1.
4.
4. Service procedures (2) LED Indicator Messages on Outdoor Control PCB LED 1 LED 2 Power ON sequence 1. No communication from indoor units in system Remarks If it is not possible to advance to 3, repeats 1 → 2. At 3, changes to normal control. 2. Communication received from 1 or more indoor units in system 3. Regular communication OK (Capacity and unit quantity match) Normal operation Displayed during automatic address setting 1 and initial communication.
4. Service procedures 4-2. Symptoms and Parts to Inspect Remote controller alarm display Alarm contents Judgment condition Clear condition Judgment and correction Abnormal discharge temperature • Discharge temp. detected at or above the specified value. High pressure switch is activated. Compressor motor thermal protector is activated. Stops when temp. exceeds 232 ˚F. Recovery at restart Stops when pressure exceeds 600 psi. Stops when temp. exceeds 230 ˚F. Recovery at restart 1.
4. Service procedures Remote controller alarm display Alarm contents P29 Current detection circuit trouble • AC current value is high even when compressor is stopped. Compressor motor output trouble, Inverter compressor trouble, MDC trouble Clear condition Judgment and correction Inverter stops after alarm is detected. Alarm is output when inverter stops (pre-trip) consecutively 4 times. Recovery at restart 1. Stops immediately when restarted. • Layer short in the compressor 2.
4. Service procedures Remote controller alarm display Alarm contents Judgment condition Clear condition Judgment and correction Recovery at power reset 1. Check EEPROM (IC007). 2. Check outdoor unit control PCB. F31 EEPROM trouble L02 Indoor unit judges that type Mismatch of indoor and outdoor unit types does not match outdoor unit type. (Espacio, Multi ) Recovery at power reset 1. Check indoor unit EEPROM. 2. Check indoor unit control PCB.
4. Service procedures 4-3. Details of Alarm Messages (1) [Alarm “P29”] (MDC trouble) Input power detection circuit trouble Compressor does not run. Breakdown Motor current detection circuit trouble Is power OK? No Correct power line. Yes Is current detection circuit wiring OK? Are wiring and connector connections OK? No Check and correct wiring. No Check and correct wiring.
4. Service procedures (2) [Alarm “P26”] HIC PCB trouble) IGBT short-circuit protection on inverter control (IPDU) PCB Is power OK? No Correct power line. Yes Are circuit wiring, connector connections, and reactor connections OK? No Correct. Yes Has filter PCB RY001 or RY002 relay activated? Yes Disconnect U.V.W. output terminal on HIC PCB and start operation. Does alarm “P26” occur? 1 No Has filter PCB AC fuse blown? Yes Replace filter PCB. 2 No No Replace HIC PCB.
4. Service procedures HIC-CH2672R (26, 30, 36 Type) HIC-CH4872R (42 Type) 1 Resistance Between terminals 2 Resistance HIC + HIC – 200 kΩ or more HIC + U 300 kΩ or more HIC + V 300 kΩ or more HIC + W 300 kΩ or more HIC – U 200 kΩ or more HIC – V 200 kΩ or more HIC – W 200 kΩ or more 3 (3) [Alarm “E31”] (communications trouble within unit) 4 5 IGBT short-circuit protection Is “E31” displayed even after the power voltage is reset? No Normal Yes Replace outdoor unit control PCB.
4. Service procedures (4) [Alarm "P22"] Outdoor unit fan motor drive circuit trouble Are connectors CN003 and CN004 connected correctly to the outdoor unit control PCB? No Correct the connector connections. Yes Disconnect connectors CN003 and CN004 from outdoor unit control PCB, and rotate fan by hand. Does it rotate easily? No Yes Outdoor unit fan motor coil resistance is OK if it is as shown below. * Disconnect connector CN004 and measure on the plug side.
4. Service procedures Sensor trouble (5) [Alarms “F04,” “F06,” “F07,” “F08,” “F12”] Are connectors CN020, 021, 022, 023, and 024 (TD, TO, C1, C2, and TS sensors) connected correctly to the outdoor unit control PCB? No Correct the connector connections. Yes Are the TD, TO, C1, C2, and TS sensor resistance* characteristics OK? No Replace the TD, TO, C1, C2, or TS sensor. 1 * Refer to “4-4. Table of Thermistor Characteristics.” Yes 2 Check the outdoor unit control PCB. Replace if PCB has failed.
4. Service procedures Sensor Temperature Display Function (Displayed both when operating and stopped) The below check procedure can be used to display all remote controller, indoor unit, and outdoor unit sensor temperatures. (1) Press and hold the button and button simultaneously for 4 seconds or longer. (2) Unit No. X-X (main unit No.), item code XX (sensor address), and service monitor 00XX (sensor temperature) appear on the remote controller LCD. (See figure.
4. Service procedures Check Pin Short-circuit the cooling check pin (or heating check pin) on the outdoor unit control PCB to perform the control described below. 1. Thermistor checks The checks listed below are performed for 1 second each, in order from the top down. The results are displayed by LED 1 and 2. Check results Thermistor Normal Discharge temp. (TD) LED 1 lit Outdoor air temp. (TO) LED 2 lit Heat exchanger temp. (C1) LED 1 lit Abnormal LED 1 and 2 OFF Heat exchanger temp.
5. Outdoor unit maintenance remote control 5. OUTDOOR UNIT MAINTENANCE REMOTE CONTROL 5-1. Overview ......................................................................................................................... 5-2. Functions ....................................................................................................................... 5-3. Normal Display Operations and Functions ................................................................. 5-4.
5. Outdoor unit maintenance remote control 5-1. Overview What is the outdoor unit maintenance remote controller? Beginning with the DC-INV series of outdoor units, nonvolatile memory (EEPROM) is used in the outdoor unit PCB. In this way, the setting switches that were located on earlier PCBs have been converted to EEPROM data. This remote controller is an outdoor unit maintenance tool that is used to make and change the EEPROM settings.
5. Outdoor unit maintenance remote control 5-3. Normal Display Operations and Functions Normal display functions • Connect the special service checker wiring to the outdoor unit PCB. The connection is shown in the figure below.
5. Outdoor unit maintenance remote control Display (functions) • Use the temperature setting and Item code buttons to change the item code. Display contents Remarks 00 (1) Outdoor unit alarm contents (code): OFF when normal Blinking 8-alarm code display at pre-trip, LED (2) At initial status 01 No. of indoor units connected in that refrigerant system 02 Unit. Nos.
5. Outdoor unit maintenance remote control *2: 7-segment, 4-digit display for remote controller timer display The connected unit Nos. are displayed as shown below, using the 7-segment 4-digit ( colon. ) display and the Display for unit Nos. 1 – 20 Not lit Not lit 1 Not lit 6 3 8 4 2 18 14 12 5 19 17 10 15 Lit Meaning of display colon 16 13 9 7 Lit Not lit 11 20 Lit — Lit — — — is not displayed. Display for unit Nos.
5. Outdoor unit maintenance remote control 5-4. Monitoring Operations: Display of Indoor Unit and Outdoor Unit Sensor Temperatures (1) Press and hold the button and button simultaneously for 4 seconds or longer to switch to temperature monitor mode. During temperature monitoring, “Service Monitor” is lit. (The display and operations are the same as when monitor mode is started from the unit remote controller.) (2) Press the button and select the indoor unit to monitor.
5. Outdoor unit maintenance remote control 5-5. Monitoring the Outdoor Unit Alarm History: Display of Outdoor Unit Alarm History * * Displays outdoor unit alarms only. Does not display indoor unit alarms. Check the indoor unit alarm histories separately using the indoor unit remote controllers or other control device. (1) Press and hold the button and button simultaneously for 4 seconds or longer to change to outdoor unit alarm history mode.
5.
5. Outdoor unit maintenance remote control Setting mode 2 (1) Press and hold the seconds or longer. button, button, and button simultaneously for 4 (2) Use the temperature setting and buttons to change the item code. The item codes and setting data are shown in the table below. (3) Use the timer time and buttons to change the setting data. To confirm the changed setting data, press the button. (At this time, “Setting” stops blinking and remains lit.
5.
6. Test run 6. TEST RUN 6-1. Preparing for Test Run ............................................................................................... VI-2 6-2. Caution........................................................................................................................ VI-3 6-3. Test Run Procedure .................................................................................................... VI-3 6-4. Items to Check Before the Test Run ..................................................
6. Test run 6. TEST RUN 6-1. Preparing for Test Run Before attempting to start the air conditioner, check the following: (1) All loose matter is removed from the cabinet especially steel filings, bits of wire, and clips. ON (Power must be turned ON at least 5 hours before attempting test run) (2) The control wiring is correctly connected and all electrical connections are tight. (3) The protective spacers for the compressor used for transportation have been removed. If not, remove them now.
6. Test run X, T, U, K Type 6-2. Caution This unit may be used in a single-type refrigerant system where 1 outdoor unit is connected to 1 indoor unit. The indoor and outdoor unit control PCBs utilize a semiconductor memory element (EEPROM). The settings required for operation were made at the time of shipment. Only the correct combination of indoor and outdoor units can be used. This test run manual describes primarily the procedure when using the wired remote controller. 6-3.
6. Test run 6-4. Items to Check Before the Test Run (1) Turn the breaker ON at least 12 hours in advance in order to energize the crank case heater. (2) Fully open the closed valves on the liquid tube and gas tube sides. 6-5. Test Run Using the Remote Controller (1) Press and hold the remote controller button for 4 seconds or longer. Then press the button. • “TEST” appears in the LCD display during the test run. • Temperature control is not possible when test run mode is engaged.
VI-5 P 0 9 displayed L 0 7 displayed L 0 2 displayed L 1 3 displayed P 0 5 displayed E 2 0 displayed E 1 6 displayed E 1 5 displayed E 0 6 displayed E 0 4 displayed E 1 4 displayed E 0 9 displayed Indoor-outdoor unit type mismatch The indoor unit ceiling panel connector is not connected correctly. ● ● Both the Operation lamp and Standby lamp are blinking together. Timer lamp and Standby lamp are blinking alternately. No serial signal is being received at all from the indoor units.
6. Test run 6-8. Examples of Wiring Diagrams Basic wiring diagram 1 Single-type system Be careful to avoid miswiring when connecting the wires. (Miswiring will damage the units.) System address rotary switch (Set to “0” at the time of shipment.) 0 Outdoor unit L1 L2 2 G U1 U2 Inter-unit power line 230 / 208 V, 60 Hz 1 Ground Power supply Single-phase 230 / 208 V 1 Indoor unit 1 2 U1 U2 RC WHT 2 Remote controller wiring (Field supply) BLK 12 (Optional) Wired remote controller Fig.
6. Test run Basic wiring diagram 2 Group control (when a central control device is not used) Simultaneous-operation multi system A maximum of 8 indoor units can be connected to 1 remote controller. Set the system address (refrigerant tubing system address) before turning on the remote power switch. (Refer to “Setting the system addresses” on next page.) (Set using the system address rotary switch on the outdoor unit control PCB.
6. Test run Setting the outdoor unit system addresses For basic wiring diagram 2 (Set the system addresses: 1, 2, 3...) Outdoor unit control PCB 3 – 5HP System address rotary switch (Set to “0” at time of shipment) System address rotary switch System address 10s digit and 20s digit DIP switch System address rotary switch 0 Automatic address button (black) System address 10s 20s DIP switch ON ON 1 2 Terminal plug (black) OFF Fig. 6-7 System address No.
6. Test run Indicating (marking) the indoor and outdoor unit combination number Indicate (mark) the number after automatic address setting is completed.