07-115 SSHP_II 5/7/07 3:59 PM Page a INSTALLATION INSTRUCTIONS – Split System Heat Pump Air Conditioner – X Model Combinations K Combine indoor and outdoor units only as listed below.
07-115 SSHP_II 5/7/07 3:59 PM Page 2 IMPORTANT! Please Read Before Starting When Installing… This air conditioning system meets strict safety and operating standards. As the installer or service person, it is an important part of your job to install or service the system so it operates safely and efficiently. …In a Room Properly insulate any tubing run inside a room to prevent “sweating” that can cause dripping and water damage to walls and floors.
07-115 SSHP_II 5/7/07 3:59 PM Page 3 Check of Density Limit 2. The standards for minimum room volume are as follows. The room in which the air conditioner is to be installed requires a design that in the event of refrigerant gas leaking out, its density will not exceed a set limit. The refrigerant (R410A), which is used in the air conditioner, is safe, without the toxicity or combustibility of ammonia, and is not restricted by laws imposed to protect the ozone layer.
07-115 SSHP_II 5/7/07 3:59 PM Page 4 Precautions for Installation Using New Refrigerant 1. Care regarding tubing 1-1. Process tubing Material: Use C1220 phosphorous deoxidized copper specified in JIS H3300 “Copper and Copper Alloy Seamless Pipes and Tubes.” Tubing size: Be sure to use the sizes indicated in the table below. Use a tube cutter when cutting the tubing, and be sure to remove any flash. This also applies to distribution joints (optional).
07-115 SSHP_II 5/7/07 3:59 PM Page 5 3-2. Use R410A exclusive cylinder only. Configuration and characteristics of cylinders When charging with a refrigerant cylinder, use an electronic scale for charging refrigerant. In this case, if the volume of refrigerant in the cylinder becomes less than 20% of the fully-charged amount, the composition of the refrigerant starts to change. Thus, do not use the refrigerant if the amount in the charging cylinder is less than 20%.
07-115 SSHP_II 5/7/07 3:59 PM Page 6 CONTENTS Page Page IMPORTANT! . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 Please Read Before Starting Check of Density Limit Precautions for Installation Using New Refrigerant 1. GENERAL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 1-1. Tools Required for Installation (not supplied) 1-2. Accessories Supplied with Outdoor Unit 1-3. Type of Copper Tube and Insulation Material 1-4.
07-115 SSHP_II 5/7/07 3:59 PM Page 7 Page 7-12. Separate Type Signal Receiving Unit Installation 7-13. Electrical Wiring 7-14. Test Run Switch 7-15. Misoperation Alarm Indicators 7-16. Basic Wiring Diagram 7-17. Wiring System Diagram for Group Control 7-18. Wiring System Diagram for Multiple Remote Controllers 7-19. Test Run Procedure 7-20. Check Items Before the Test Run 7-21. Preparing for the Test Run 7-22. Precautions 7-23.
07-115 SSHP_II 5/7/07 3:59 PM Page 8 1. GENERAL 1-3. Type of Copper Tube and Insulation Material This booklet briefly outlines where and how to install the air conditioning system. Please read over the entire set of instructions for the indoor and outdoor units and make sure all accessory parts listed are with the system before beginning. Copper tubing for connecting the outdoor unit to the indoor unit is available in kits which contain the liquid and gas tubing, fittings and insulation.
07-115 SSHP_II 5/7/07 3:59 PM Page 9 Table 1-1 XH / XHW (4-Way Air Discharge Semi-Concealed) Part Name Figure Q’ty Remarks Full-scale installation diagram 1 For determining suspension bolt pitch Flare insulator 2 For gas and liquid tubes 8 For suspending indoor unit from ceiling 1 For gas tube flare nuts Hose band 2 For securing drain hose Packing 1 For drain joint Drain insulator 1 For drain joint Drain hose 1 Washer (White) Insulating tape Drain hose adaptor 1 For drain ou
07-115 SSHP_II 5/7/07 3:59 PM Page 10 Table 1-3 TH / THW (Ceiling-Mounted) Part Name Figure ‘Q’ty Special washer Drain insulator Flare insulator T3 T5 Drain hose adaptor Remarks 4 For temporarily suspending indoor unit from ceiling 1 For drain hose joint 1 Set For gas tube joints 1 Drain hose clamp 4 Black 2 For gas tube and drain hose joint White (heat-resisting) 1 For gas flare joints Vinyl clamp 2 For ends of flare insulator Full-scale installation diagram 1 For determining s
07-115 SSHP_II 5/7/07 Table 1-5 3:59 PM Page 11 (Accessories for the Wired Remote Controller) Part Name Figure ‘Q’ty Part Name Figure ‘Q’ty Wired remote controller (comes with 7-7/8 in. wire) 1 Spacers 2 Machine screws M4 × 1 in. 2 Wire joints 4 Wood screws 2 Table 1-6 (Accessories for the Wireless Remote Controller) Part Name Figure Operation controller ‘Q’ty Part Name Figure ‘Q’ty 1 Spacers 2 1 Pan-head tapping screws 4 × 13/32 in.
07-115 SSHP_II 5/7/07 3:59 PM Page 12 Part Name Figure ‘Q’ty Part Name Figure ‘Q’ty Separate type signal receiving unit (comes with 7-7/8 in. wire) 1 Small screws M4 × 1-9/16 in. 2 Carrier for ceiling installation 1 Wood screws 2 Wireless remote controller 1 Spacers 4 Wireless remote controller mounting cradle 1 Wire joints 4 Batteries 2 Clamp 1 Machine screws M4 × 1 in. 2 Ceiling installation paper pattern (3-3/4 × 2-1/32 in.
5/7/07 3:59 PM Page 13 1-5. Tubing Size Single Single type Refrigerant tubing between the indoor and outdoor units should be kept as short as possible. The length of the refrigerant tubes between the indoor and outdoor units are limited by the elevation difference between the 2 units. During tubing work, try to make both the tubing length (L) and the difference in elevation (H1) as short as possible. Refer to Table 1-10.
07-115 SSHP_II 5/7/07 3:59 PM Page 14 Table 1-10 Tubing Data for Models Models Tubing Data Tubing size outer diameter Liquid tube Gas tube in. (mm) in. (mm) Limit of tubing length (ft.) Outdoor unit is placed Limit of elevation higher (ft.) difference between Outdoor unit is placed the 2 units lower (ft.) Max. allowable tubing length at shipment (ft.) Required additional refrigerant *1 (oz./ft.) Refrigerant charged at shipment (lbs.) C(H)2672R C(H)3072R C(H)3672R C(H)4272R 3/8 (9.52) 5/8 (15.
07-115 SSHP_II 5/7/07 3:59 PM CAUTION Page 15 1. This unit requires no additional refrigerant charge up to 100 ft. tubing length. In case of more than 100 ft., additional refrigerant charge is required. Refer to Table 1-11. 2. In case of multi type installation, indoor units should be installed within the same room.
07-115 SSHP_II 5/7/07 3:59 PM Page 16 2. SELECTING THE INSTALLATION SITE Ceiling-Mounted Type 2-1. Indoor Unit Ceiling AVOID: areas where leakage of flammable gas may be expected. places where large amounts of oil mist exist. direct sunlight. locations near inverter lamps which may affect the performance of the unit. locations near heat sources which may affect the performance of the unit. Wall Min.
07-115 SSHP_II 5/7/07 3:59 PM Page 17 2-2. Outdoor Unit AVOID: Exhaust fan heat sources, exhaust fans, etc. (Fig. 2-1) damp, humid or uneven locations Hot air Heat source DO: Outdoor unit choose a place as cool as possible. choose a place that is well ventilated and outside air temperature does not exceed maximum 115°F constantly. allow enough room around the unit for air intake/ exhaust and possible maintenance. (Fig.
07-115 SSHP_II 5/7/07 3:59 PM Page 18 2-3. Air-Discharge Chamber for Top Discharge Be sure to install an air discharge chamber in the field when: Air discharge it is difficult to keep a space of min. 20" between the air discharge outlet and an obstacle. Air discharge the air discharge outlet is facing a sidewalk and discharged hot air may bother passers-by. Refer to Fig. 2-5. 2-4.
07-115 SSHP_II 5/7/07 3:59 PM Page 19 2-6.
07-115 SSHP_II 5/7/07 3:59 PM Page 20 Dimensions of Outdoor Unit with air-discharge chamber (field supply) 2672R / 3072R / 3672R unit with STK-DRV80U 13/32 Win d dire ctio n 1/2 2-17/32 15-15/16 14-31/32 19/32 1/2 25/32 Wind direction 1/2 13-3/8 4-5/16 25-31/32 25/32 6-11/16 21-13/16 37 4-1/16 9-27/32 Wind direction 5-3/16 21-5/8 23/32 Wind direction Wind direction 30-23/32 Wind direction Unit: inch 25/32 13/32 14-31/32 1/2 25/32 4-5/16 Win dire d ctio n 1/2 11-13/16 13
07-115 SSHP_II 5/7/07 3:59 PM Page 21 Reference diagram for air-discharge chamber (field supply) C(H)2672R / 3072R / 3672R / 4272R with STK-DRV80U & DRE140A Required space around outdoor unit If the air discharge chamber is used, the space shown below must be secured around the outdoor unit. If the unit is used without the required space, a protective device may activate, preventing the unit from operating. Min. 39-3/8 Min.
07-115 SSHP_II 5/7/07 3:59 PM Page 22 2-7.
07-115 SSHP_II 5/7/07 3:59 PM Page 23 Dimensions of outdoor unit with snow-proof vents (field supply) 2672R / 3072R / 3672R unit with STK-BDRE80A 13/32 15-15/16 14-31/32 19/32 11-29/32 37 Wind direction 16-3/4 Wind direction 25/32 Wind direction 7-1/16 3/4 30-3/32 Wind direction 25-13/32 Wind direction 30-23/32 Wind direction Unit: inch 4272R unit with STK-BDR140U Wind direction Wind direction 15-15/16 25/32 13/32 19/32 14-31/32 25/32 25-13/32 30-3/32 7-1/16 Wind direction Wind
07-115 SSHP_II 5/7/07 3:59 PM Page 24 Reference diagram for snow-proof vents – 1 Space requirements for setting – (1) C(H)2672R / 3072R / 3672R / 4272R with STK-BDRE80A & STK-BDR140U [Obstacle to the front of unit] [Obstacle to the rear of unit] Top is open: Top is open: (1) Single-unit installation Min. D Min. A Min. H (1) Single-unit installation (2) Obstacles on both sides Min. B (2) Multiple-unit installation (2 or more units) Min. C Min. I Min. G Min. I Min.
07-115 SSHP_II 5/7/07 3:59 PM Page 25 Reference diagram for snow-proof vents – 2 Space requirements for setting – (2) C(H)2672R / 3072R / 3672R / 4272R with STK-BDRE80A & STK-BDR140U [Obstacles to the front and rear of unit] The top and both sides must remain open. Either the obstacle to the front or the obstacle to the rear must be no taller than the height of the outdoor unit. Q Min. O Min.
07-115 SSHP_II 5/7/07 3:59 PM Page 26 3. HOW TO INSTALL THE INDOOR UNIT 4-Way Air Discharge Semi-Concealed Type (X Type) 3-1. Suspending the Indoor Unit Hole-in-anchor Hole-in-plug This unit uses a drain pump. Use a carpenter’s level to check that the unit is level. Concrete Insert 3-2. Preparation for Suspending (1) Fix the suspension bolts securely in the ceiling using the method shown in the diagrams (Figs.
3:59 PM Page 27 3-3. Placing the Unit Inside the Ceiling (1) When placing the unit inside the ceiling, determine the pitch of the suspension bolts using the supplied full-scale installation diagram. (Fig. 3-4) The size of the opening for the indoor unit can be confirmed by attaching the full-scale installation diagram beneath the unit. (Fig. 3-4) Tubing and wiring must be laid inside the ceiling when suspending the unit.
07-115 SSHP_II 5/7/07 3:59 PM Page 28 3-4. Installing the Drain Piping X Transparent part for checking drainage (1) Prepare standard hard PVC pipe for the drain and use the supplied drain hose and hose band to prevent water leaks. The PVC pipe must be purchased separately. The transparent part allows you to check drainage. (Fig. 3-6) CAUTION Packing (supplied) Tighten the hose clamps so their locking nuts face upward. (Fig.
07-115 SSHP_II 5/7/07 3:59 PM Page 29 3-5. Checking the Drainage After wiring and piping are completed, use the following procedure to check that the water will drain smoothly. For this, prepare a bucket and wiping cloth to catch and wipe up spilled water. WARNING X Do not supply power to the unit until the tubing and wiring to the outdoor unit are completed. (1) Take off the tube cover and through the opening, slowly pour about 43 oz. of water into the drain pan to check drainage.
07-115 SSHP_II 5/7/07 3:59 PM Page 30 Ceiling Panel CAUTION X Latch Screw Never touch or attempt to move the air direction louver by hand or you may damage the unit. Instead, use the remote control unit if you want to change the direction or air flow. Air-intake grille 3-6. Before Installing the Ceiling Panel (1) Remove the air-intake grille and air filter from the ceiling panel. (Figs. 3-13 and 3-14) Ceiling panel (a) Remove the 2 screws on the latch of the airintake grille. (Fig. 3-13) Fig.
07-115 SSHP_II 5/7/07 3:59 PM Page 31 3-7. Installing the Ceiling Panel (1) Lift the ceiling panel and position it to align the panel hook with the panel catch of the indoor unit. NOTE X The ceiling panel must be mounted in the correct direction. Note that the 2 catches of the panel differ in size. Confirm that the catches are correctly matched between the ceiling panel and the indoor unit body. (2) Next, check to see that the ceiling panel is properly aligned with the seamline of the ceiling.
07-115 SSHP_II 5/7/07 3:59 PM Page 32 3-9. Duct for Fresh Air For fresh air intake There is a duct connection part on side of the indoor unit. (Fig. 3-16) An optional air-intake plenum (including duct connection CMB-GSJ80U CMB-GSJ140U ø1 /8 Type PNR-XH2442 (XH(W)2672R) PNR-XH3642 (XH(W)3672R, XH(W)4272R) 4- Air-intake plenum ho le box and flange) can be attached to the indoor unit.
07-115 SSHP_II 5/7/07 3:59 PM Page 33 (d) Installing the ceiling panel Duct connection flange Attach the ceiling panel to the chamber. Drawing the panel downwards sets the panel in position temporarily with the panel catch (at 2 locations). Duct connection box Installation screws (M4 × 1/2 in.) Remove the socket cover of the air-intake plenum and X pass the 8P sockets through it. (Fix the panel lead wire with the chamber side clamp.) (Fig.
07-115 SSHP_II 5/7/07 3:59 PM Page 34 Wall-Mounted Type (K Type) 3-10. Removing the Wall Fixture from the Unit KH(S)2672R Remove and discard the set screws and take off the rear panel. (Fig. 3-19) Set screws for transportation only NOTE Fig. 3-19 K Tubing can be extended in 3 directions as shown in Fig. 3-20. Select the direction that provides the shortest run to the outside unit. Right-rear tubing (recommended) Left-rear tubling 3-11.
07-115 SSHP_II 5/7/07 3:59 PM Page 35 KH(S)3072R, KH(S)3672R One hole is required for the air conditioner tubing, and may be either on the left or right side. (Also see section 3-14. Preparing the Indoor Side Tubing.) Tape Full-scale installation diagram (1) Tape the full-scale installation diagram on the wall at the location selected. Make sure the unit is horizontal using a level or tape measure to measure down from the ceiling. (Fig. 3-25) Fig.
07-115 SSHP_II 5/7/07 3:59 PM Page 36 KHH(S)2672R Remove and discard the set screws and take off the wall fixture. (Fig. 3-29) Wall fixture KHH(S)2672R K (1) Tape the full-scale installation diagram on the wall at the location selected. Make sure the unit is horizontal using a level or tape measure to measure down from the ceiling. (Fig. 3-30) Set screws only for transportation Fig.
07-115 SSHP_II 5/7/07 3:59 PM Page 37 3-12. Installing the Rear Panel on the Wall KH(S)2672R Be sure to confirm that the wall is strong enough to suspend the unit. See either Item a) or b) below depending on the wall type. a) If Wooden Wall Fig. 3-34 (1) Attach the rear panel to the wall with the 10 screws provided. (Fig. 3-34) If you are not able to line up the holes in the rear panel with the beam locations marked on the wall, use toggle bolts to go through the holes on the panel or drill 3/16 in.
07-115 SSHP_II 5/7/07 3:59 PM Page 38 KHH(S)2672R wall fixture Confirm that the wall is strong enough to support the unit. a) If Wooden Wall K (1) Attach the wall fixture to the wall with the 9 screws provided. (Fig. 3-38) If you are not able to line up the holes in the wall fixture with the beam locations marked on the wall, use rawl plugs or toggle bolts to go through the holes on the panel or drill 13/64 in. dia. holes in the panel over the stud locations and then mount the wall fixture. Fig.
07-115 SSHP_II 5/7/07 3:59 PM Page 39 3-13. Remove the Grille to Install the Indoor Unit Grille Air-intake grille KH(S)2672R Basically, these models can be installed and wired without removing the grille. If access to any internal part is needed, follow the steps given below: How to remove the grille K (1) Set the 2 flaps in the horizontal position. Fig. 3-40a (2) Unscrew the 3 screws. (Fig. 3-40a) Air-intake grille (3) Remove the grille.
07-115 SSHP_II 5/7/07 4:00 PM Page 40 KH(S)3072R, KH(S)3672R How to Remove the Grille (1) Remove the plastic cover. (Fig. 3-42) (2) Remove the clamp for the wiring connector. (Fig. 3-43) Plastic cover (3) Disconnect the 2 wiring connectors. (Fig. 3-44) Screw K (4) Set the flap in the horizontal position. (Fig. 3-45) Fig. 3-42 (5) Remove the 3 screws. (Fig. 3-45) (6) Remove the grille. (Fig.
07-115 SSHP_II 5/7/07 4:00 PM Page 41 Frame 3-14. Preparing the Indoor Side Tubing KH(S)2672R Right tubing outlet Arrangement of tubing by directions (a) Right tubing The corner of the right frame needs to be cut by a hacksaw or the like. (Fig. 3-46) Fig. 3-46 Tab Mounting slot K (b) Right-rear or left-rear tubing In this case, the corner of the frame need not be cut. To mount the indoor unit on the rear panel: (a) Hang the 3 mounting slots of the unit on the upper tabs of the rear panel. (Fig.
07-115 SSHP_II 5/7/07 4:00 PM Page 42 KHH(S)2672R Tubing can be extended in 4 directions as shown in Fig. 3-54. Left tubing Right-rear tubing (Recommended) Left-rear tubing Arrangement for Left Tubing (a) Cut out the left tubing outlet. (Fig. 3-55) Right tubing Arrangement for Right Tubing K Fig. 3-54 (a) Cut out the right tubing outlet using a hacksaw. (Fig. 3-56) Arrangement for Left-rear and Right-rear Tubing Right tubing outlet (a) It is not necessary to cut a hole.
07-115 SSHP_II 5/7/07 4:00 PM Page 43 3-16. Wiring Instructions for Inter-Unit Connections Rear panel KH(S)2672R (1) Insert the inter-unit wiring (according to local electrical codes) into the through-the-wall PVC pipe. Run the wiring toward the indoor side allowing approx. 10 inches to extend from the wall face. (Fig. 3-57) Wall Plastic cover Wiring (2) Route the inter-unit wiring from the back of the indoor unit and pull it toward the front for connection. (Figs. 3-58a and 3-58b) K 10 in. Fig.
07-115 SSHP_II 5/7/07 4:00 PM Page 44 (1) Insert the inter-unit wiring (according to local codes) into the through-the-wall PVC pipe. Run the wiring toward the indoor side allowing approx. 5" to extend from the wall face. (Figs. 3-59a and 3-59b) CAUTION K KHH(S)2672R Rear panel Wall Plastic cover Never fix the wiring by any means before the indoor unit is fully seated on the rear panel. Wiring (2) Remove the side cover and the metallic cover. (Fig. 3-60 or 3-61, depending on model.
07-115 SSHP_II 5/7/07 4:00 PM Page 45 KHH(S)2672R Cover (1) Shape the refrigerant tubing so that it can easily go into the wall hole. (Fig. 3-62) CAUTION Refrigerant tubing If using a stepladder, be careful to keep your balance and not fall off. To prevent the unit from damage and avoid personal injury, ask for someone’s help when feeding the tubing through the hole because the unit is heavy and difficult to hold in place. Inter-unit wiring Drain hose K Fig.
07-115 SSHP_II 5/7/07 4:00 PM Page 46 Cover 3-17. Shaping the Tubing KHH(S)2672R Refrigerant tubing (1) Shape the refrigerant tubing so that it can easily go into the hole. (Fig. 3-69) K Inter-unit wiring (2) Push the wiring, refrigerant tubing and drain hose through the hole in the wall. Adjust the indoor unit so it is securely seated on the wall fixture. Drain hose Fig.
07-115 SSHP_II 5/7/07 4:00 PM Page 47 Ceiling-Mounted Type (T Type) Front face 3-19. Suspending the Indoor Unit (1) Place the full-scale diagram (supplied) on the ceiling at the spot where you want to install the indoor unit. Use a pencil to mark the drill holes. (Fig. 3-74). Rear Full-scale diagram Fig. 3-74 NOTE Since the diagram is made of paper, it may shrink or stretch slightly because of high temperature or humidity.
07-115 SSHP_II 5/7/07 4:00 PM Page 48 (5) Before suspending the indoor unit, remove the 2 screws on the latch of the air-intake grilles, open the grilles, and remove them by pushing the claws of the hinges as shown in Fig. 3-78. Then remove both side panels sliding them along the unit toward the front after removing the two screws which fix them. (Fig. 3-79) Pull out the air-Intake grille pushing claws of the hinges Screw Hinge Latch de Sli (6) Preparation for suspending the indoor unit.
07-115 SSHP_II 5/7/07 4:00 PM Page 49 Approx. 1 inch (7) Suspend the indoor unit as follows. (a) Mount a washer and two hexagonal nuts on each suspension bolt as shown in Fig. 3-82. (b) Lift the indoor unit, and place it on the washers through the notches, to fix it in place. (Fig. 3-83) (c) Tighten the two hexagonal nuts on each suspension bolt to suspend the indoor unit as shown in Fig. 3-84. Ceiling surface Washer (supplied) Nut (field supply) Suspension bolt Fig.
07-115 SSHP_II 5/7/07 4:00 PM Page 50 3-20. Duct for Fresh Air Duct connection port (Knock-out hole) There is a duct connection port (knock-out hole) at the right-rear on the panel top of the indoor unit for drawing in fresh air. If it is necessary to draw in fresh air, remove the cover by knocking it out and connect the duct to the indoor unit through the connection port. (Fig.
07-115 SSHP_II 5/7/07 4:00 PM Page 51 3-22. Required Minimum Space for Installation and Service A (Suspension bolt pitch) ceiling so that the indoor unit and ducts are not visible. Only the air intake and air outlet ports are visible from below. min. 9-27/32 The minimum space for installation and service is 22-27/32 This air conditioner is usually installed above the min.
07-115 SSHP_II 5/7/07 4:00 PM Page 52 3-23. Suspending the Indoor Unit Hole-in-anchor Hole-in-plug Concrete Depending on the ceiling type: Insert • Insert suspension bolts as shown in Fig. 3-93 or • Use existing ceiling supports or construct a suitable support as shown in Fig. 3-94. Suspension bolt (M10 or 3/8") (field supply) WARNING U It is important that you use extreme care in supporting the indoor unit inside the ceiling.
07-115 SSHP_II 5/7/07 4:00 PM Page 53 Fig. 3-97 shows an example of installation. Bolt anchor Air outlet duct Suspension bolt Air-intake duct Air-outlet grille Ceiling material Indoor unit Air-intake grille U Fig. 3-97 3-24. Installing the Drain Piping (1) Prepare standard hard PVC pipe for the drain and use the supplied hose band to prevent water leaks. The PVC pipe must be purchased separately.
07-115 SSHP_II 5/7/07 4:00 PM Page 54 Air bleeder CAUTION U Do not install an air bleeder tube as this may cause water to spray from the drain pipe outlet. (Fig. 3-100) If it is necessary to increase the height of the drain pipe, the section directly after the connection port can be raised a maximum of 19-11/16 in. Do not raise it any higher than 19-11/16 in., as this could result in water leaks. (Fig. 3-101) Not good Fig. 3-100 11-13/16 in.
07-115 SSHP_II 5/7/07 4:00 PM Page 55 3-26. Increasing the Fan Speed Electrical component box If external static pressure is too great (due to long extension of ducts, for example), the air flow volume may drop too low at each air outlet. This problem may be solved by increasing the fan speed using the following procedure: Booster cable Fan motor Booster cable Fan motor socket (At shipment) (Booster cable installed) Fig.
07-115 SSHP_II 5/7/07 4:00 PM Page 56 4. HOW TO INSTALL THE OUTDOOR UNIT 4-1. Installing the Outdoor Unit Refer to the Fig. 4-1 for the anchor bolt dimensions. Be sure to anchor the feet with the anchor bolts (M10). In addition, use anchoring washers on the top side. (Use large square 32 × 32 SUS washers with diameters of 10.) (Field supply) 6-47/64 33/64 33/64 33/64 4-2. Drainage Work For the drain port dimensions, refer to the figure at right. Ensure a base height of 6 in.
07-115 SSHP_II 5/7/07 4:00 PM Page 57 5. ELECTRICAL WIRING 5-1. General Precautions on Wiring (1) Before wiring, confirm the rated voltage of the unit as shown on its nameplate, then carry out the wiring closely following the wiring diagram. (2) Provide a power outlet to be used exclusively for each unit, and a power supply disconnect and circuit breaker for overcurrent protection should be provided in the exclusive line.
07-115 SSHP_II 5/7/07 4:00 PM Page 58 Indoor Unit Type X, K, T, U (B) Power Supply Trade Size of Conduit AWG #14 Max. length 67 ft. MOP (Fuse or HACR type circuit breaker) 3/4 in. 15 A Control Wiring (C) Inter-Unit Control Wiring (D) Remote Control Wiring AWG #18 Use high voltage wire (300 V)*1 AWG #18 (0.75 mm ) Max. 3,300 ft. Max. 1,650 ft. *2 (E) Control Wiring For Group Control 2 AWG #18 *2 – (0.75 2 mm ) Max. 1,650 – ft. (Total) *1 *2 With ring-type wire terminal.
5/7/07 4:00 PM Page 59 WARNING Stranded wire Loose wiring may cause the terminal to overheat or result in unit malfunction. A fire hazard may also exist. Therefore, ensure that all Strip 3/8 in. 07-115 SSHP_II Ring pressure terminal wiring is tightly connected. When connecting each power wire to the corresponding terminal, follow the instructions on “How to connect wiring to the terminal” and fasten the wire securely with the fixing screw of the terminal plate. Fig.
07-115 SSHP_II 5/7/07 4:00 PM Page 60 6. HOW TO INSTALL THE WIRED REMOTE CONTROLLER (OPTIONAL PART) 6-1. Installation Site Selection Install the remote controller at a height of between 3–5 ft. above the floor. Do not install the remote controller in a place where it will be exposed to direct sunlight or near a window or other place where it will be exposed to the outside air. Be sure to install the remote controller vertically, such as on a wall.
07-115 SSHP_II 5/7/07 4:00 PM Page 61 6-2. Wired Remote Controller Installation Do not supply power to the unit or try to operate it until the tubing and wiring to the outdoor unit are completed. Do not twist the control wiring with the power wiring or run it in the same metal conduit, because this may cause malfunction. Install the remote controller away from sources of electrical noise.
07-115 SSHP_II 5/7/07 4:00 PM Page 62 6-3. Basic Wiring Diagram Carry out wiring correctly (incorrect wiring will damage the equipment). Shielded wire Ground Ground Use shielded wires for inter-unit control wiring and ground the shield on both sides. (Fig. 6-5) Otherwise misoperation because of noise may occur. Fig. 6-5 Diagram of outer dimensions Wiring procedure 5/32 RC (WD) Address setting is automatically executed after turning on the system.
07-115 SSHP_II 5/7/07 4:00 PM Page 63 6-4. Wiring System Diagram for Group Control This diagram shows when several units (maximum of 8) are controlled by a remote controller (main unit). In this case, a remote controller can be connected at any indoor unit. Wiring procedure Remote controller Wire according to the diagram at right: 1 2 Address setting is executed automatically when the outdoor unit is turned on. Wire joint 1 2 Indoor unit No.
07-115 SSHP_II 5/7/07 4:00 PM Page 64 6-5. Wiring System Diagram for Multiple Remote Controllers When Installing Multiple Remote Controllers Remote controller This multiple remote controller system is used for operating the unit(s) at different positions. (A maximum of 2 remote controllers can be installed.) Remote controller address connector Main RCU check Sub Setting method To execute this control, make the setting according to the following procedure. RCU.
07-115 SSHP_II 5/7/07 4:00 PM Page 65 6-7.
4:00 PM Page 66 Wired remote control display Operation Possible cause of malfunction Ceiling panel connection failure Activation of protective device Indoor protection Outdoor protection Thermistor fault RC (WD) Thermistor open circuit • Short circuit (indoor) Thermistor open circuit • Short circuit (outdoor) Wireless remote controller receiver display P09 Fan protective thermostat P01 Float switch P10 Discharge temperature trouble P03 High pressure switch or compressor motor thermal prot
07-115 SSHP_II 5/7/07 4:00 PM Page 67 (2) LED Indicator Messages on Outdoor Control PCB LED 1 LED 2 Power ON sequence 1. No communication from indoor units in system Remarks If it is not possible to advance to 3, repeats 1 → 2. At 3, changes to normal control. 2. Communication received from 1 or more indoor units in system 3. Regular communication OK (Capacity and unit quantity match) Normal operation Displayed during automatic address setting 1 and initial communication.
07-115 SSHP_II 5/7/07 4:00 PM Page 68 7. HOW TO INSTALL THE WIRELESS REMOTE CONTROLLER (ACCESSORY PART / OPTIONAL PART) IMPORTANT When using this air conditioner with the wireless remote controller it may sometimes be impossible to change the operation modes while other indoor unit is running. When this happens, a double beep tone sounds, the (operation lamp) lights up, and the (Timer lamp) and (Standby lamp) blink alternately.
07-115 SSHP_II 5/7/07 4:00 PM Page 69 7-2. Room Temperature Sensor Setting The room temperature sensors are built into the indoor unit and the wireless remote controller. Either of these room temperature sensors can operate. The system is shipped from the factory set to the indoor unit sensor. To switch to the remote controller sensor, press the sensor switching button located inside the remote controller cover and check that A/C SENSOR on the LCD display panel goes out.
07-115 SSHP_II 5/7/07 4:00 PM Page 70 4-Way Air Discharge Semi-concealed Type (X Type) Air intake grille Mark section (indicator section) 7-5. Indicator Section Installation X Remove the ceiling panel and indicator cover and install the indicator section. (1) (2) (3) (4) (5) (6) Remove the ceiling panel. Remove the corner cover behind the mark section. (3 screws) Remove the mark section inside the ceiling panel.
07-115 SSHP_II 5/7/07 4:00 PM Page 71 Ceiling-Mounted Type (T Type) 7-7. Indicator Section Installation Remove the side panel to install the indicator section. (Fig. 7-8) (1) (2) (3) (4) (5) (6) (7) Remove the side panel. Open the air intake grille, remove the screw at one place and then remove the side panel by sliding it toward the front (arrow direction). Remove cover A and cover B. Insert a standard screwdriver into the recess of cover A to remove cover A and cover B.
07-115 SSHP_II 5/7/07 4:00 PM Page 72 7-9. Electrical Wiring Signal receiving unit Indoor PCB 1 WL 2 Operating controller W2 CN2 (0.7 ft.) CN1 BLU W1 (4.3 ft.) YEL PNK WHT RED BLK GRY BLK W3 Indicator section (4.3 ft.) CN1 BLU YEL PNK RED GRY BLK Relay connector Connection method (1) Connect W1 to the indoor PCB WL connector. (2) Connect W3 from the indicator section with W2 from the operating controller using the relay connector. Fig. 7-10 7-10.
07-115 SSHP_II 5/7/07 4:00 PM Page 73 7-11. Misoperation Alarm Indicators Alarm indicator lamps on the indoor unit indicate the error cause if the air conditioner fails to operate upon being switched on. The possible alarm indications are given in Table 7-1. Fig. 7-12 shows the location of the alarm lamps on the indoor unit. (See Table 7-1 and Fig. 7-12.) Table 7-1 Alarm (OPERATION lamp) (TIMER lamp) Cause of Trouble (STANDBY lamp) S.C.
07-115 SSHP_II 5/7/07 4:00 PM Page 74 CAUTION If the signal receiving unit is installed near a rapidstart or inverter type fluorescent lamp (neither one uses glow lamps), it may be impossible to receive signals from the wireless remote controller. To avoid signal interference from fluorescent lamps, install the receiving unit at least 6.6 ft. away from the lamps and install at a location where wireless remote controller signals can be received when the fluorescent lamps are on. 7-12.
07-115 SSHP_II 5/7/07 4:00 PM Page 75 When using the signal receiving unit on a wall with Clamp (Supplied) the front exposed, choose a wall surface that the Run the remote control About 3/32-1/8 in. signal receiving unit can be mounted on. cable through a notch in the upper case. (1) Insert a standard (minus) screwdriver into the slot on the lower side of the signal receiving unit and pry off the back case as shown in Fig. 7-14.
07-115 SSHP_II 5/7/07 4:00 PM Page 76 7-13. Electrical Wiring Be sure to do the wiring correctly (incorrect wiring will damage the equipment). CAUTION Recommended wire diameter and allowable length for signal receiving unit wiring and its branch wiring: AWG #18, MAX 1,300 ft. Terminal board for indoor unit remote controller wiring 1 2 WHT BLK 1 2 Signal receiving unit Wire from signal receiving unit Connection Signal receiving unit wiring (field supply) Wire joint (2 pcs.
07-115 SSHP_II 5/7/07 4:00 PM Page 77 7-15. Misoperation Alarm Indicators A blinking lamp for other than the signal receiving unit filter shows that a problem has occurred in the unit, so make an inspection. (Refer to servicing information in the service manual, etc.) Also, if wired remote controller and dedicated service check lines (854-9-9536044-97: service use) are available, then detailed error information can be obtained by connecting to the service connector as shown in the drawing.
07-115 SSHP_II 5/7/07 4:00 PM Page 78 7-16. Basic Wiring Diagram Be sure to do the wiring correctly (incorrect wiring will damage the equipment). CAUTION Use shielded wires for inter-unit control wiring and ground the shield on both sides. (Fig. 7-25) Otherwise misoperation because of electrical noise may occur. Remote controller Shielded wire 1 2 1 2 Fig. 7-25 Indoor unit No.
07-115 SSHP_II 5/7/07 4:00 PM Page 79 7-17. Wiring System Diagram for Group Control This diagram shows when several units (maximum of 8) are controlled by a signal receiving unit (main unit). In this case, a signal receiving unit can be connected at any indoor unit. Wiring procedure Wire according to the diagram at left: Address setting is executed automatically when the outdoor unit is turned on.
07-115 SSHP_II 5/7/07 4:00 PM Page 80 7-18. Wiring System Diagram for Multiple Remote Controllers When installing multiple remote controllers This multiple system is used for operating the unit(s) at different positions. (A maximum of 2 signal receiving units can be installed.) Setting method To execute this control, make the setting according to the following procedure. (1) Of the two installed signal receiving units, make one the main signal receiving unit (factoryshipped state).
07-115 SSHP_II 5/7/07 4:00 PM Page 81 7-19. Test Run Procedure Wall-mounted Type (K Type) Check the “Check Items Before the Test Run.” (Item 7-20) Verify the combination (wiring) of indoor and outdoor units. Set the indoor unit controller to “TEST.” Is operation possible? NO YES (Item 7-21-3) Check using the self-diagnostics function table. (Refer to 11-7) Correct any locations that require correction. Note: Check the indoor-side drainage. Return the indoor unit controller to “NORM.
07-115 SSHP_II 5/7/07 4:00 PM Page 82 7-21. Preparing for the Test Run 7-21-1. Changing the room temperature sensor Room temperature sensors are installed inside the indoor unit and the wireless remote controller. Either room temperature sensor can be used. When “Unit Sensor” is indicated on the wireless remote controller LCD, the indoor unit sensor is operating as the room temperature sensor. To change to the remote controller sensor, open the remote controller cover and press the SENSOR button once.
07-115 SSHP_II 5/7/07 4:00 PM Page 83 7-22. Precautions Request that the customer be present at the time the test run is performed. Explain the Operation Manual to the customer, and then have the customer actually operate the system. Be sure to pass the manual and warranty certificate to the customer. Verify that the AC 208 / 230 V wiring is not connected to the terminal plate which is used to connect the inter-unit control wiring.
07-115 SSHP_II 5/7/07 4:00 PM Page 84 7-23. When Setting Indoor Unit Control PCB Switch for Wall-Mounted Indoor Unit When using either the wired or wireless remote controller, refer to the tables below and accordingly slide the switch on the indoor unit control PCB. If this setting is not made correctly an alarm will occur. (The operation lamp on the display blinks.) This setting is not necessary if both the wired remote controller and wireless remote controller are used.
07-115 SSHP_II 5/7/07 4:00 PM Page 85 8. HOW TO INSTALL THE SYSTEM CONTROLLER (OPTIONAL PART) Do not supply power to the unit or try to operate it until the tubing and wiring to the outdoor unit are completed. 8-1. System Controller Installation CAUTION Switch box (with cover) Do not twist the control wiring with the power wiring or run it in the same metal conduit, because this may cause malfunction. M4 × 1-3/16 in.
07-115 SSHP_II 5/7/07 4:00 PM Page 86 8-2. Electrical Wiring How to connect electrical wiring Indoor unit PCB (1) (2) Connect B1, B2 to indoor PCB CRV connector using accessary 2P connector. (*No polarity) Total wire length is less than 985 ft. and size is AWG#18. B1 B2 Connect B5, B6 to indoor unit 2P terminal base. (*No polarity). Wire size is AWG#18.
07-115 SSHP_II 5/7/07 4:00 PM Page 87 8-3. Address Switch Setting SW1 SW1 ON Main/sub selection switch OFF: System controller operates as main controller. ON: System controller operates as sub-controller. 1 2 3 4 5 6 7 8 OFF ALL/ZONE mode selection switch ALL mode: All indoor units can be controlled by system controller ZONE 1, 2, 3, 4 mode: Indoor units in one of zone 1, 2, 3, or 4 can be controlled by system controller. All indoor units cannot be set.
07-115 SSHP_II 5/7/07 4:00 PM Page 88 SW2 SW2 Weekly timer input switches System controller operation can be set when weekly timer activates (ON/OFF). Switch No.
07-115 SSHP_II 5/7/07 4:00 PM Page 89 8-4. Mode Setting Central control mode According to the function of each system controller, set SW1 as shown in Fig. 8-5. (1) 2 3 4 5 6 Central control/Remote control mode Central control mode The system controller is used as the central control equipment.
07-115 SSHP_II 5/7/07 4:00 PM Page 90 8-5. How to Perform Zone Registration To operate the system controller properly, zone registration is required after finishing the test run (and after setting all indoor unit addresses) using one of the following methods. (a) Zone registration using the remote controller (RCS-SH80UG) Refer to page 91. (b) Zone registration using the system controller (SHA-KC64UG) Refer to page 92.
07-115 SSHP_II 5/7/07 (a) 4:00 PM Page 91 Zone registration using the remote controller (RCS-SH80UG) (Determination of central address) In this case, after confirming which indoor unit is connected to the remote controller and that the air conditioner in the OFF state, you set the central addresses one at a time. If the system has no remote controller, connect a remote controller to the system temporarily. Then follow this procedure.
07-115 SSHP_II 5/7/07 4:00 PM Page 92 (b) Zone registration using the system controller (SHA-KC64UG) In this case, you set all central addresses by the system controller at once manually. ZONE ZONE (1) and ZONE buttons at the same Press the time for more than 4 seconds. and CODE No. C1 will flash. (2) After confirming that CODE No. C1 is displayed, button. Once in this mode, a press the change takes place as shown in Fig. 8-8. (3) (4) 2 3 4 6 9 Selected group No. if no data is registered.
07-115 SSHP_II 5/7/07 4:00 PM Page 93 (c) Automatic zone registration using the system controller (SHA-KC64UG) (1) and buttons at the same Press the time for more than 4 seconds. and CODE No. C1 will flash. (2) Select CODE No. C2 by pressing ( ) button and press the and button. C2 changes from flashing to ON state and automatic zone registration will start. (3) Any registered GROUP Nos. will be erased.
07-115 SSHP_II 5/7/07 4:00 PM Page 94 How to check for overlapping of central address Nos. (1) Press the and buttons at the same time for more than 4 seconds. and CODE No. C1 will flash. (2) Select CODE No. C3 by pressing ( ) button and press the , button. C3 changes from flashing to ON state and will flash. Then auto overlap checking will start. (3) If C3 changes from ON to flashing and stops flashing and disappears, there is no overlapping.
07-115 SSHP_II 5/7/07 4:00 PM Page 95 ZONE registration table ZONE GROUP 1 2 Central address Indoor unit address (UNIT No.
07-115 SSHP_II 5/7/07 4:00 PM Page 96 Name Input/output Terminal ON/OFF output Alarm output Potential tree A contact, static (relay output) Contact capacity DC 30V, 0.5A All ON input All OFF input Pulse (photo coupler input) Equipment ON/OFF Terminal Example Input/output Wire length: less than 330 ft. CPEV AWG#16 Digital input Status output System controller Control input Digital input/output terminals Input/output item 8-6.
07-115 SSHP_II 5/7/07 4:00 PM Page 97 9. HOW TO PROCESS TUBING Deburring The liquid tubing side is connected by a flare nut, and the gas tubing side is connected by brazing. After Before 9-1. Connecting the Refrigerant Tubing Use of the Flaring Method Many conventional split system air conditioners employ the flaring method to connect refrigerant tubes which run between indoor and outdoor units. In this method, the copper tubes are flared at each end and connected with flare nuts. Fig.
07-115 SSHP_II 5/7/07 4:00 PM Page 98 Caution Before Connecting Tubes Tightly (1) Apply a sealing cap or water-proof tape to prevent dust or water from entering the tubes before they are used. (2) Be sure to apply refrigerant lubricant to the matching surfaces of the flare and union before connecting them together. This is effective for reducing gas leaks. (Fig. 9-4) Apply refrigerant lubricant here and here Fig.
07-115 SSHP_II 5/7/07 4:00 PM Page 99 Do not use a spanner to tighten the valve stem caps. Doing so may damage the valves. Depending on the installation conditions, applying excessive torque may cause the nuts to crack. Packed valve Charging port Valve stem Precautions for Packed Valve Operation If the packed valve is left for a long time with the valve stem cap removed, refrigerant will leak from the valve. Therefore, do not leave the valve stem cap removed.
07-115 SSHP_II 5/7/07 4:00 PM Page 100 9-4. Taping the Tubes (1) At this time, the refrigerant tubes (and electrical wiring if local codes permit) should be taped together with armoring tape in 1 bundle. To prevent condensation from overflowing the drain pan, keep the drain hose separate from the refrigerant tubing. Inter-unit control wiring Gas tube Liquid tube Armoring tape (2) Wrap the armoring tape from the bottom of the outdoor unit to the top of the tubing where it enters the wall.
07-115 SSHP_II 5/7/07 4:00 PM Page 101 10. LEAK TEST, EVACUATION AND ADDITIONAL REFRIGERANT CHARGE Perform an air-tightness test for this package A/C. Check that there is no leakage from any of the connections. Air and moisture in the refrigerant system may have undesirable effects as indicated below.
07-115 SSHP_II 5/7/07 4:00 PM Page 102 (3) Pressurize the system up to 4.15 MPa (42 kgf/cm2G) with dry nitrogen gas and close the cylinder valve when the gauge reading reaches 4.15 MPa (42 kgf/cm2G). Then, test for leaks with liquid soap. CAUTION Manifold valve Pressure gauge Hi To avoid nitrogen entering the refrigerant system in a liquid state, the top of the cylinder must be higher than the bottom when you pressurize the system. Usually, the cylinder is used in a vertical standing position.
07-115 SSHP_II 5/7/07 4:00 PM Page 103 Manifold valve 10-3. Charging Additional Refrigerant Charging additional refrigerant (calculated from the liquid tube length as shown on page 14, Amount of additional refrigerant charge) using the liquid tube service valve. (Fig. 10-5) Pressure gauge Lo Hi Valve Use a balance to measure the refrigerant accurately.
07-115 SSHP_II 5/7/07 4:00 PM Page 104 11. TEST RUN 11-1. Preparing for Test Run Before attempting to start the air conditioner, check the following: ON (Power must be turned ON at least 5 hours before attempting test run) (1) All loose matter is removed from the cabinet especially steel filings, bits of wire, and clips. (2) The control wiring is correctly connected and all electrical connections are tight.
07-115 SSHP_II 5/7/07 4:00 PM Page 105 X, T, U, K Type 11-2. Caution This unit may be used in a single-type refrigerant system where 1 outdoor unit is connected to 1 indoor unit. The indoor and outdoor unit control PCBs utilize a semiconductor memory element (EEPROM). The settings required for operation were made at the time of shipment. Only the correct combination of indoor and outdoor units can be used.
07-115 SSHP_II 5/7/07 4:00 PM Page 106 11-4. Items to Check Before the Test Run (1) Turn the breaker ON at least 12 hours in advance in order to energize the crank case heater. (2) Fully open the closed valves on the liquid tube and gas tube sides. 11-5. Test Run Using the Remote Controller (1) Press and hold the remote controller button for 4 seconds or longer. Then press the “TEST” appears in the LCD display during the test run.
P 0 9 displayed L 0 7 displayed L 0 2 displayed L 1 3 displayed P 0 5 displayed E 2 0 displayed E 1 6 displayed E 1 5 displayed E 0 6 displayed E 0 4 displayed E 1 4 displayed E 0 9 displayed Timer lamp and Standby lamp are blinking alternately. Both the Operation lamp and Standby lamp are blinking together. Operation lamp and Standby lamp are blinking alternately. Standby lamp is blinking. E 0 2 displayed is blinking.
07-115 SSHP_II 5/7/07 4:00 PM Page 108 11-8. Examples of Wiring Diagrams 11-8-1. Basic wiring diagram 1 Single-type system Be careful to avoid miswiring when connecting the wires. (Miswiring will damage the units.) System address rotary switch (Set to “0” at the time of shipment.
07-115 SSHP_II 5/7/07 4:00 PM Page 109 11-8-2. Basic wiring diagram 2 Group control (when a central control device is not used) Simultaneous-operation multi system A maximum of 8 indoor units can be connected to 1 remote controller. Set the system address (refrigerant tubing system address) before turning on the remote power switch. (Refer to 11-8-3. Setting the system addresses.) (Set using the system address rotary switch on the outdoor unit control PCB.
07-115 SSHP_II 5/7/07 4:00 PM Page 110 11-8-3. Setting the outdoor unit system addresses For basic wiring diagram 2 (Set the system addresses: 1, 2, 3...) Outdoor unit control PCB System address rotary switch (Set to “0” at time of shipment) System address rotary switch System address 10s digit and 20s digit DIP switch System address rotary switch 0 Automatic address button (black) System address 10s 20s DIP switch ON ON 1 2 OFF System address No. 0 Terminal plug (black) Fig.
07-115 SSHP_II 5/7/07 4:00 PM Page 111 11-8-5. Indicating (marking) the indoor and outdoor unit combination number Indicate (mark) the number after automatic address setting is completed.