Installation Guide
E-
10
There are two refrigerant pipes of different diameters:
A smaller one for the liquid refrigerant
A larger one for the gas refrigerant
A short length of piping is already fitted to the air conditioner. You must
extend this piping using assembly piping (optionally supplied).
The connection procedure for the refrigerant piping varies according to the
exit position of the piping from the indoor unit, as seen when facing the air
conditioner in position on the wall:
ˇ Right (A)
ˇ Left (B)
ˇ Rear
1 With a knife, cut out the appropriate knock-out piece on the rear of the
indoor unit (unless you are connecting directly from the rear).
2 Smooth the cut edges.
3 Remove the protection caps on the pipes and connect the assembly piping
to each pipe, tightening the nuts, first manually and then with a torque
wrench, applying the following torque.
Outer Diameter Torque (kgf•cm)
If the piping must be shortened or extended, refer to page 11.
4 Cut off any excess foam insulation.
5 If necessary, bend the pipe round, along the bottom of the indoor unit and
out through the appropriate hole, taking care to ensure that:
The piping does not jut out from the rear of the indoor unit
The bending radius is 100 mm or more
6 Pass the piping through the hole in the wall.
7 For further details on how to connect up to the outdoor unit and purge the
circuit, refer to page 12.
The piping will be insulated and fixed permanently into position once
the whole installation has been tested for gas leaks; refer to page 13
for
further details.
Installing and Connecting the Indoor Unit Assembly Piping
INSTALLING THE UNIT
6.35 mm 140~170
9.52
mm 250~280
A
B