SECTION 10 | Protections
The inverter has been provided with protections detailed below:
Overload / Short Circuit Shut Down


power limited to the continuous power rating of the inverter. If there is an overload


will be switched OFF. The unit will be latched in this shutdown condition and will require
OFF the power 
switch 
Warning Alarm - Low DC Input Voltage
-
tery terminals due to voltage drop in the battery wires and connectors. The drop in the


(Please read “Section 8, Installation; DC SIDE CONNECTIONS; Connection From the Bat-
teries To the DC Input Side of The Unit – Wire and External Fuse Sizes”

a buzzer alarm will be sounded. The 

alarm indicates that the battery is running low and that the inverter will be shut down
after sometime if the voltage at the inverter terminals further drops to 10 V for 12 V
versions or 20V for 24V versions.
Low DC Input Voltage Shut Down


 OFF. The unit will reset automatically when the

High DC Input Voltage Shutdown




Over-Temperature Shut Down
In case of failure of the cooling fan or in the case of inadequate heat removal due to

will increase. The temperature of a critical hot spot inside the inverter is monitored and

