State of Charge (SOC) of a Battery – Based on “Standing Voltage”
The “Standing Voltage” of a battery under open circuit conditions (no load connected
and letting the battery “stand” idle for 3 to 8 hours before the voltage measurement
TABLE 7.4: STATE OF CHARGE VERSUS STANDING VOLTAGE – 12V BATTERY
Percentage of
Full Charge
Standing Voltage of 6 Cell,
12V Nominal Battery
Standing Voltage
of Individual Cells
100% 12.63V 2.105V
12.6V 2.10V
80% 12.5V 2.08V
12.3V 2.05V
60% 12.2V 2.03V
50% 12.1V 2.02V
40% 12.0V 2.00V
30% 11.8V
20%
10% 11.6V
0%
require equalization. Please note that only the non-sealed / vented / ooded / wet cell
batteries are equalized. Do not equalize sealed / VRLA type of AGM or Gel Cell Batteries.
State of Discharge of a loaded battery – Low Battery /
DC Input Voltage Alarm and Shutdown in Inverters